• Title/Summary/Keyword: Lighting impulse breakdown

Search Result 7, Processing Time 0.02 seconds

Study on Electrical Properties of Ceramic Coated Al Bus Bar (세라믹 코팅 Al 부스바의 전기적 특성 연구)

  • Baek, Seung-Myeong;Kwak, Min-Hwan;Kwag, Dong-Soon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.66 no.11
    • /
    • pp.1647-1650
    • /
    • 2017
  • Bus bars are used in place of cables because they can carry more electrical energy with the same volume of conductors. This paper deals with the electrical properties of ceramic coating material for busbars. A ceramic coated samples were prepared for the electrical properties test. There are two types of samples. One is a sample without degradation, and the other is a sample degraded for 30 days. Four electrical properties tests were carried out in accordance with domestic standards. Four electrical characteristics tests are AC dielectric breakdown, V-t, lighting impulse dielectric breakdown, and discharge arc. Both samples showed excellent electrical properties, and the ceramic coating material is very good insulating materials for bus bar.

Design of Insulation and Bending Test for a 154 kV Class HTS Cable (154 kV급 HTS 케이블의 절연설계 및 굴곡시험)

  • Choi, Jin-Wook;Choi, Jae-Hyeong;Lim, Eung-Choon;Kim, Hae-Jong;Cho, Jeon-Wook;Kim, Sang-Hyun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.21 no.11
    • /
    • pp.1024-1028
    • /
    • 2008
  • It is important that study on cryogenic electrical insulation design to develop the cold dielectric(CD) type HTS cable because the cable is operated under the high voltage environment in cryogenic temperature. This paper proposes two types of insulation design to carry out the maximum insulation design for 154 kV-class HT cable. The proposed insulation design method takes into consideration AC and lightning impulse withstand voltage so as to prevent AC breakdown for power frequency operating voltage during operating the cable and breakdown for lightning impulse voltage. The final insulation thickness is determined by selecting high value out of two insulation thickness calculated through the two insulation design methods. And we researched electrical insulation characteristics of HTS cable according to bending ratio and the number of bending.

SLI, AC Breakdown Voltage Characteristics of $SF_6/CF_4$ Mixtures Gas in Nonuniform Field (불평등전계에서 $SF_6/CF_4$ 혼합 가스의 SLI, AC 절연내력 특성)

  • Hwang, Cheong-Ho;Sung, Heo-Gyung;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.2
    • /
    • pp.245-251
    • /
    • 2008
  • Although many studies have been carried out about binary gas mixtures with $SF_6$, few studies were presented about breakdown characteristics of $SF_6/CF_4$ mixtures. At present study the breakdown characteristics of $SF_6/CF_4$ mixtures in non-uniform field was performed. The experiments were carried out under AC voltage and standard lightning impulse(SLI) voltage. Breakdown characteristics were investigated for $SF_6/CF_4$ mixtures when AC voltages and standard lighting impulse voltage was applied in a needle-plane. The needle-plane electrode whose gap distance was 3 mm were used in a test chamber. $SF_6/CF_4$ mixtures contained from 0 to 100% $SF_6$ and the experimental gas pressure ranged from 0.1 to 0.5 MPa. The breakdown characteristics of $SF_6/CF_4$ mixtures in non-uniform field may be influenced by defects like needle-shaped protrusions. In case of slowly rising SLI voltage and AC voltage it is enhanced by corona-stabilization. This phenomena caused by the ion drift during streamer development and the resulting space-charge is investigated. In non-uniform field under negative SLI voltage the breakdown voltage was increase linearly but under positive SLI voltage the breakdown voltage increase non-linearly. The breakdown voltage in needle-plane electrode displayed N shape characteristics for increasing the content of $SF_6$ at AC voltage. $SF_6/CF_4$ mixture has good dielectric strength and arc-extinguishing properties than pure SF6. This paper presents experimental results on breakdown characteristics for various mixtures of $SF_6/CF_4$ at practical pressures. We could make an environment friendly gas insulation material with maintaining dielectric strength by combing $SF_6\;and\;CF_4$ which generates a lower lever of the global warming effect.

Influence of SF6/N2 Gas Mixture Ratios on the Lightning Streamer Propagation Characteristics of 22 kV MV Circuit Breaker

  • Gandhi, R.;Chandrasekar, S.;Nagarajan, C.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1663-1672
    • /
    • 2018
  • In recent times, gas insulated medium voltage (MV) circuit breakers (CB) form a vital component in power system network, considering its advantages such as reduced size and safety margins. Gas insulation characteristics of circuit breakers are generally measured by lightning impulse (LI) test according to IEC standard 60060-1 as a factory routine test. Considering the environmental issues of $SF_6$ gas, many research works are being carried out towards the mixture of $SF_6$ gases for high voltage insulation applications. However, few reports are only available regarding the LI withstand and streamer propagation characteristics (at both positive and negative polarity of waveform) of $SF_6/N_2$ gas mixture insulated medium voltage circuit breakers. In this paper, positive and negative polarity LI tests are carried out on 22 kV medium voltage circuit breaker filled with $SF_6/N_2$ gas mixture at different gas pressures (1-5 bar) and at different gas mixture ratios. Important LI parameters such as breakdown voltage, streamer velocity, time to breakdown and acceleration voltage are evaluated with IEC standard LI ($1.2/50{\mu}s$) waveform. Weibull distribution analysis of LI breakdown voltage data is carried out and 50% probability breakdown voltage, scale parameter and shape parameter are evaluated. Results illustrate that the $25%SF_6+75%N_2$ gas filled insulation considerably enhances the LI withstand and breakdown strength of MV circuit breakers. LI breakdown voltage of circuit breaker under negative polarity shows higher value when compared with positive polarity. Results show that maintaining the gas pressure at 0.3 MPa (3 bar) with 10% $SF_6$ gas mixed with 90% $N_2$ will give optimum lighting impulse withstand performance of 22 kV MV circuit breaker.

Insulating Design and Test of 22.9kV Class Mini-Model Transformer Considering AC Loss (AC Loss를 고려한 22.9kV급 Mini-Model 변압기의 절연 설계 및 시험)

  • 백승명;정종만;곽동순;김해종;석복렬;김상현
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.8
    • /
    • pp.420-424
    • /
    • 2004
  • This paper presents experimental data from model windings with different arrangement of coil in order to provide information to design a 22.9kV class HTS transformer. Before experiment, the composite insulation of two different type of HTS transformers are investigated. The first basic of investigation is a breakdown characteristic of liquid nitrogen and flashover characteristic on the GFRP surface under ac and impulse, The second investigation is insulation design, manufacture and test of model windings. These include a AC withstand voltage test of 50 kV rms and a lighting impulse test of 150 kV at peak.

Electrical Insulation Characteristics of HTS Cables according to Bending Strain (고온초전도 케이블의 굴곡 변화에 따른 전기절연 특성)

  • Kwang, Dong-Soon;Kim, Sang-Hyun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.11 no.1
    • /
    • pp.45-48
    • /
    • 2009
  • Research on the mechanical properties of the dielectric paper and mini-model cable are important for optimum electrical insulation design of HTS cable, because the HTS cable experience of mechanical stress, such as tensile and bending stress. Also, it is operated at cryogenic temperature. Therefore, this paper discusses the experiment results on the AC and lighting impulse breakdown characteristics, partial discharge inception and extinction characteristics, and external shape change of the insulation layer according to bending strain of the mini-model cable.

A Study on Insulating Design and Test of Mini-Model windings for a 22.9 kV Class HTS Transformer Reducing AC Loss (저손실 22.9 kV급 고온초전도 변압기를 위한 미니 모델 권선의 절연 설계 및 시험 연구)

  • Baek, Seung-Myeong;Cheon, Hyeon-Gweon;Nguyen, Van Dung;Kwag, Dong-Sun;Lee, Chang-Hwa;Kim, Hea-Jong;Kim, Sang-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.94-99
    • /
    • 2004
  • This paper presents experimental data from model windings with different arrangement of coil in order to provide information to design a 22.9 kV class HTS transformer. Before experiment, the composite insulation of two different type of HTS transformers are investigated. The first basic of investigation is a breakdown characteristic of liquid nitrogen and flashover characteristic on the GFRP surface under ac and impulse, The second investigation is insulation design, manufacture and test of model windings. These include a AC withstand voltage test of 50 kV rms and a lighting impulse test of 150 kV at peak.

  • PDF