• Title/Summary/Keyword: LiBr/물

Search Result 32, Processing Time 0.025 seconds

Simulation of the Characteristics of High-Performance Absorption Cycles (고성능 흡수냉동 사이클의 특성 시뮬레이션)

  • 윤정인;오후규;이용화
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.19 no.1
    • /
    • pp.231-239
    • /
    • 1995
  • This paper describes a computer simulation of the triple effect, water-lithium bromide absorption cooling cycles. The performance of the absorption systems is investigated through cycle simulation to obtain the system characteristics with the cooling water inlet temperature, the working solution concentrations, the ratio of the amount of the weak solution to the high, middle and low temperature generators, and the temperature difference of each solution heat exchanger. The efficiency of different cycles has been studied and the simulation results show that higher coefficient of performance could be obtained for the parallel cycle of constant solution distribution rate. As a result of this analysis, the optimum designs and operating conditions were determined based on the operating conditions and coefficient of performance.

흡수식 고효율화 방안

  • 문인식
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.33 no.3
    • /
    • pp.29-32
    • /
    • 2004
  • 이중효용 흡수냉동기의 고효율화 방안과 당사(한국 캐리어)에서 개발한 흡수식 냉동기를 소개 하고자 한다. 흡수냉동기는 1777년 영국의 NAIRNE에 의해 흡수냉동기 이론을 발표한 이후 1945년 미국 CARRIER사가 냉매로서 물, 흡수제로서 리튬브로마이드(LiBr)를 이용한 일중 효용 흡수냉동기가 세계 최초로 상용화되면서 공조용 및 산업용 냉방기기로서 보급되기 시작하였다. 이러한 흡수식 기술은 일본에서 이중효용 흡수냉동기 및 냉온수기를 개발하면서 공조용 및 산업용 냉. 난방기기로서 널리 보급되기 시작하였으며, 최근에는 고 효율 이중효용 흡수냉동기 및 냉온수기(COP 1.2-l.3)를 개발하여 제작. 판매하고 있으며 또한 삼중효용 흡수냉온수기(COP 1.6)를 개발하고 있다. 그리고 세계 흡수냉동기 시장은 일본 및 중국을 중심으로 고 효율 흡수냉동기 시장으로 재편되고 있다. 그러나, 우리나라에는 아직 일본기술에 의존한 표준 COP 이중효용 흡수냉동기 및 냉온수기(COP 1.01)를 제작 판매하고 있는 실정이다. 따라서 본 고에서는 이중효용 흡수냉동기의 고효율화 방안과 당사(한국 캐리어)에서 개발한 흡수식 냉동기를 소개하고자 한다.

  • PDF

Thermal Analysis and Optimum Design of Water-Cooled, Series-Flow Type, Double-Effect Absorption Heat Pump (수냉형 직렬방식 2중효용 흡수식 냉방기의 열해석과 최적 설계)

  • Oh, M.D.;Kim, Y.L.;Kim, S.C.;Kim, Y.I.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.4 no.4
    • /
    • pp.332-341
    • /
    • 1992
  • An absorption heat pump cycle has been modeled and simulated to analyze the system performance of water-cooled, series-flow, double-effect absorption heat pump, which can be applied to a direct gas fired cooling system with the medium range of cooling capacity (15RT level). Effect of absorption cooling system parameters, such as concentration difference, inlet temperature of cooling water, 1st generator temperature, leaving temperature differences of condenser and evaporator and efficiency of solution heat exchanger, has been investigated in the view of system cooling performance.

  • PDF

Analysis of Absorption Refrigeration Cycles to Utilize Treated Sewage (하수처리수이용 흡수식냉동사이클의 해석)

  • Lee, Y.H.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.2
    • /
    • pp.288-298
    • /
    • 1996
  • The gas-fired absorption refrigeration system to utilize treated sewage is available for environmental protection and energy conservation. Simulation analysis on the double-effect absorption refrigeration cycles with parallel or series flow type has been performed. The working fluid is Lithium Bromide and water solution. The main purpose of this study is evaluating the possibilities of effective utilization of treated sewage as a cooling water for the absorber and condenser. The efficiency of a couple of cycles has been studied and simulation results show that higher coefficient of performance could be obtained for parallel flow type. The other purpose of the present study is to determine the optimum designs and operating conditions based on the operating constraints and the coefficent of performance in the paralledl flow type.

  • PDF

Effects of Ion Specificity on the Expansion Behavior of Polymer Gel with Phenyl Ring (Phenyl 고리를 갖는 고분자 겔의 팽윤거동에 대한 이온 특성화 효과)

  • Ahn, Beom-Shu
    • Journal of the Korean Applied Science and Technology
    • /
    • v.29 no.2
    • /
    • pp.278-285
    • /
    • 2012
  • Effects of ion species on the expansion behavior of Poly(styrene sufonic acid)(PSSA) hydrogel were investigated in aqueous solution of selected anions, cations and hydrophobic ions. The deexpansion extent of Poly(stylene sulfonic acid) gel follow the sequence $SCN^-$<$Br^-$<$Cl^-$<$F^-$ in low concentration solutions due to the destabilization of anions to hydrogen bond between ${SO_3}^-$ and water. The deexpansion in cations followed the sequence of counterion interactions between ${SO_3}^-$ and cations. It was discussed the effects of ions on the hydrogen bonding through ${SO_3}^-$ and phenyl ring in salt solutions. Other interactions, such as the cation-${\pi}$ interaction, hydrophobic interaction, and dispersion force, contributed to the ion specific swelling of PSSA hydrogel.

A Study on the COP Improvement of Absorption Chillers by Recovering Heat from the Condenser (응축기 배열회수에 의한 흡수식 냉동기의 고효율화에 관한 연구)

  • Park, Chan-Woo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.9
    • /
    • pp.738-744
    • /
    • 2006
  • In order to utilize the condensation heat of refrigerants in condenser on the absorption chiller system, the solution cooled condenser (SCC) was proposed using the weak solution of absorber as a cooling medium. The increase of COP with the increase of UA of the solution cooled condenser was approximately 0.009 in maximum with single effect one, and is about maximum 0.008 in occasion of double effect one with series flow compared to that without. In the case of heat exchanger, effectiveness is about 0.85, it's increments are 0.008 and 0.0072, respectively. And solution cooled condenser is more effective device in the single effect absorption system than double effect system for the principle of operation. On the other hand, as the solution split ratio increases when the value of UA is fixed, COP is increased and as the solution split ratio increases when the value of UA is fixed, COP is increased. If the flow rate of cooling water or the value of UA is reduced in order to increases the heat recovery of solution cooled condenser, heat recovery of solution cooled condenser is increased a little but COP is decreased as the system pressure is increased.

Performance Experiment of Generator for Household Absorption Chiller and Heater (가정용 흡수식 냉난방기 개발을 위한 재생기 성능실험)

  • Yu, Sun-Il;Kwon, Oh-Kyung;Yoon, Jung-In
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.23 no.10
    • /
    • pp.1347-1354
    • /
    • 1999
  • Recently, the markets of the air conditioner are enlarging. The market size will reach 2.0 billion won in 2000. Electric heat pumps have been utilized as main residential air conditioners. especially in Korea. They cause a surge up electric power demand during summer. Moreover, the use of HCFCs and HFCs causes serious problem to the global environment such as global warming and ozone layer destruction. Absorption chiller and heater could solve such problems. It was built and tested for analyzing the performance of the generator for absorption chiller and heater. Experiment was done with a high temperature generator, a low temperature generator, heat exchangers, a condenser and a solution tank. It was tested that the double effect series flow cycle with two kinds of solution cycle. Solution cycle B showed better than solution cycle A. Two kinds of heat exchanger were used, where one's heat transfer area is bigger than the other. Bigger one increased a little performance of absorption chiller and heater. But it was not economical. From this study, we got that the coefficient of performance(COP) is 0.82 and the capacity is 7.24 kW for an absorption chiller and heater.

Heating and Cooling System using the Sewage Source Absorption Refrigeration and Heat Pump Cycle (하수열을 이용한 냉난방시스템에 관한 연구)

  • Lee, Yong-Hwa;Shin, Hyun-Joon;Yoon, Hee-Chul;Park, Hyun-Gun
    • Journal of the Korean Solar Energy Society
    • /
    • v.27 no.4
    • /
    • pp.19-26
    • /
    • 2007
  • This paper concerns the study of absorption refrigeration and heat pump cycle to use sewage. Simulation analysis on the double-effect absorption refrigeration cycle with parallel and two-stage heat pump cycle has been performed. The working fluid is Lithium Bromide and water solution. The absorption refrigeration cycle use sewage as a cooling water for the absorber and condenser, and absorption refrigeration cycle does that as a chilled water for the evaporator of the first stage cycle. And the two-stage cycle consists of coupling double-effect with parallel and single effect cycle so that the first stage absorber and condenser produces heating water to evaporate refrigerant in the evaporator of the second stage. The effects of operating variables such as a absorber temperature on the coefficient of performance have been studied for absorption refrigeration and heat pump cycle.

A study on the Characteristics of the High Efficiency absorption Chiller by Heat Recovering from Condenser (응축기 배열 회수에 의한 흡수식 냉동기의 고효율화에 관한 연구)

  • Park, Chan-Woo
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.46-51
    • /
    • 2006
  • In order to utilize the refrigerants condensation heat of condenser on the absorption chiller system, the solution cooling condenser(SCC) were proposed, which weak solution of absorber outlet use as a cooling water. As the UA of the solution cooling condenser increased, increasement of COP is about maximum 0.09 in occasion of single effect and is about maximum 0.08 in occasion of double effect series flow. In the case of heat exchanger efficiency is about 0.85, it's increments are 0.08 and 0.072, each. And solution cooling condenser is a more effective device in the single effect absorption system more than double effect system for the principle of operation. In order to increases the heat of solution cooling condenser, if reduce the flow rate of cooling water or the value of UA, it makes COP increase a little, but it brought COP decrease because of increasing the pressure of system.

  • PDF

Performance analysis for the Characteristics of Double Stage Evaporator/Absorber for Large temperature Difference Absorption System (흡수식 대온도차 시스템에서 2단 증발/흡수기의 성능 특성에 관한 수치적 연구)

  • Park, Chan-Woo;Kang, Yong-Tae;Im, Ick-Tae;Moon, Sang-Done
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.304-308
    • /
    • 2008
  • The optimal design of two stage evaporation & absorption system which is related to the large temperature difference system was investigated numerically in the absorption refrigeration system. The concentrations at inlet & oulet of absorber are 62.9% and 56.9%, but in two stage absorption system the values are 62.2% and 56.2%. Therefore strong solution & weak solution became diluted than the standard value. The amount of weak solution circulation can be reduced in absorption refrigeration system, and the sensible heat load is more reduced to enhance the COP of system. As UAR is increased, COP becomes larger, and this means the role of top section is more important than bottom section in two stage evaporation & absorption system. But the increase of COP becomes slower at 0.7 of UAR ratio. The performance of Type2 is higher than Type1 in COP with the flow direction of cooling waters. This phenomena is due to the active absorption of vapor -absorption & lower temp. cooling water is more effective. The pressure at bottom section becomes higher & that at top section becomes lower and therefore the circulation rate can be diminished more.

  • PDF