• 제목/요약/키워드: Leakage Current waveform

검색결과 31건 처리시간 0.024초

공장전기설비에서의 누전차단기 오동작과 전력품질 분석 (Power Quality Analysis and Failure of Earth Leakage Breakers in Plant)

  • 이상의;유재근;전정채;전현재;허혜성;최규하
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2007년도 하계학술대회 논문집
    • /
    • pp.479-481
    • /
    • 2007
  • This paper presented a actual conditions on a false-tripping of ELB(Earth Leakage Breakers) and an assessment of the harmonics due to non-linear electronic equipment such as personal computers, rectifier, electric furnace and test equipments in plant installations. Actual conditions on a failure of ELB were surveyed and analyzed by making up a question to safety managers of plant installations. Also, power quality measurements such as harmonic currents, voltage and current waveform and current imbalance were made at various plant installations where nuisance tripping of ELB is often occurred. The results of this study can be used in making decisions regarding cause of ELB trip and operating and tripping characteristics test of ELB when subjected to distorted current waveform.

  • PDF

HF-CT센서를 이용한 고분자애자의 오손특성 (Contamination Characteristics of Polymer Insulator using High Frequency Current Transformer)

  • 박재준
    • 정보학연구
    • /
    • 제8권4호
    • /
    • pp.1-7
    • /
    • 2005
  • Investigations of high frequency current transformer(HF-CT) waveform characteristics of the surface leakage on kaolin polluted EPDM polymer insulators have been performed. This work is part of a program aimed at examining the potential for HF-CT waveform characteristics analysis to provide information about the environment contaminants and environment condition of polymer insulators. The investigation reported examined the HF-CT waveform characteristics at high frequencies. The use of high frequency measurements for on-line applications reduces electrical inference. This work was peformed utilizing HF-CT to monitor of surface polluted discharge. It was found that HF-CT waveform frequency spectrum, magnitude depend on importantly the duration of the surface discharge activity.

  • PDF

교류전동기를 위한 Parameter Adaptive Control 방식의 PWM 인버터에 관한 연구 (A Study on the Parameter Adaptive Current Controlled PWM Inverter for AC Drives.)

  • 황영문;안진우
    • 대한전기학회논문지
    • /
    • 제36권4호
    • /
    • pp.259-266
    • /
    • 1987
  • In order to drive motor control system precisely, the motor is to be controlled by mmfs and current with sinusoidal waveforms. In this paper the Delta Modulation (DM) Technique is used for generating PWM pulse with sinusoidal waveform. However the motor currents yet contain odd harmonics due to leakage inductances, speed and exitation. To reduce harmonics, the parameter adaptive control method is introduced. That is, Req.C parameter of Delta Modulator is controlled adaptively by parameter adaptor. The adaptive signal is achieved by the difference between motor current and reference waveform, and this signal is converted to the voltage commend signal by adaptive mechanism. The test reslts show that this system is operated smoothly over a wide range of motor speed and motor current is controlled to be sinusoidal waveform adaptively.

  • PDF

ESDD 오손에 따른 송전용자기애자의 누설전류 파형의 분석 (Analysis of Leakage Current Waveforms for Transmission Line Porcelain Insulators due to ESDD Contamination)

  • 박재준
    • 전기학회논문지
    • /
    • 제61권10호
    • /
    • pp.1461-1470
    • /
    • 2012
  • This paper reports the contamination performance of transmission line porcelain insulators tested under five different contaminant conditions - clean and ESDD (equivalent salt deposit density) level (A, B, C, and D) through measurement of their leakage current under drop of potential method. To estimate the contamination for transmission line porcelain insulators, leakage current waveform and its maximum value were measured under step-up power test. In the clean insulators test, % distortion factors decreased with increasing step-up power, and as the ESDD level increased, some characteristics such as frequency analysis, harmonics and % distortion facotor could be used for contamination diagnosis of the transmission line porcelain insulators.

직류 접지극의 전식보호 방법 연구 (Research on Protection Method for Ground Electrode of DC Systems from Corrosion)

  • 정우용;김효성
    • 전력전자학회논문지
    • /
    • 제26권2호
    • /
    • pp.90-95
    • /
    • 2021
  • In contrast to AC grounding systems, the ground electrode in DC systems continuously maintains positive or negative polarity. Ground electrodes with (+) polarity proceeds by oxidation reaction. Thus, the DC current should flow opposite to the polarity of the leakage current flowing through the (+) ground electrode by using a compensation electrode, and the current flowing through the (+) ground electrode can be 0A. However, according to protecting the (+) ground electrode, the compensation electrode corrodes and gets damaged. Thus, the (+) ground electrode must be protected from corrosion, and the service life of the compensation electrode must be extended. As an alternative, the average value of the current flowing through the compensation electrode should be equal with the value of the leakage current flowing through the (+) ground electrode by using the square waveform. Throughout the experiment, the degree of corrosion on the compensation electrode is analyzed by the frequency of the compensation electrode for a certain time. In the experiment, the frequencies of the square waveform are considered for 0.1, 1, 10, 20, 50, 100 Hz, and 1 kHz. Through experiments and analysis, the optimal frequency for reducing the electrolytic damage of the (+) electrode and compensation electrode in an LVDC grounding environment is determined.

애자/피뢰기 모니터링을 위한 유비쿼터스 센서 개발 (Development of a Ubiquitous Sensor for Monitoring Insulators and Arresters)

  • 길경석;신광철;박종국;심재원;송재용
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2006년도 추계학술대회 논문집
    • /
    • pp.736-741
    • /
    • 2006
  • In this study, a ubiquitous sensor for condition monitoring of insulators and lightning arresters installed in power distribution lines and electric traction vehicles is presented. The sensor consists of two parts; a leakage current measurement and a lightning surge detection. Measured data are transmitted to a supervisory computer through ZigBee protocol based on IEEE 802.15.4. To detect leakage current, a window type Mn-ZCT is used and a low-noise amplifier with a gain of 60dB is designed, and this can measure leakage current in ranges of $100{\mu}A{\sim}5mA$. A sample-hold(S/H) and a Rogowski coil are injected to analyze the magnitude of surge current in ranges from 500A to 10kA with $8/20{\mu}s$-waveform.

  • PDF

환경조건변화에 대한 실리콘애자의 누설전류 파형분석 (Waveform analysis of leakage current on silicon insulator for various environment condition variation)

  • 박재준
    • 정보학연구
    • /
    • 제7권2호
    • /
    • pp.69-76
    • /
    • 2004
  • 본 논문은 여러 가지 환경조건하(염무, 안개, 비)에서 오손된 실키콘애자의 누설전류파형과 파형의 스펙트럼 분석 결과를 나타내었다. 200ms동안 누설전류의 크기가 더욱 커지면 커질수록, 60Hz에서의 스펙트럼의 크기도 커짐을 알 수 있었다. 만일 오손된 애자들이 고밀도의 염무에 접촉되면 낮은 스펙트럼을 갖은 누설전류파형이 계측되었고, 간헐적으로 높은 파형이 계측되었다. 누설전류자료 분석의 경우, 전기적인 활동은 염무 측정시 애자표면에 누적된 오손물질로 인한 일시적인 아크거동으로 특성지어진다. 이것은 애자표면을 따라 흐르는 누설전류에 대한 경로를 제공하게 된 것이다. 그것은 특별한 애자의 퍼포먼스 측정을 평가하기위하여 오손누적의 지표를 갖은 것으로서 중요한 것이다. 만일 표면 저항의 떨어짐이 크게 되면, 그때의 누설전류는 전력품질이 저하시킨 섬락을 중단시키는 공급된 전류이 점차로 증가되어진다.

  • PDF

애자/피뢰기 모니터링을 위한 유비쿼터스 센서 개발 (Development of a Ubiquitous Sensor for Monitoring Insulators and Lightning Arresters)

  • 길경석;류길수;송재용;김일권;박대원;최수연
    • 한국철도학회논문집
    • /
    • 제10권2호
    • /
    • pp.117-123
    • /
    • 2007
  • In this study, a ubiquitous sensor for condition monitoring of insulators and lightning arresters installed in power distribution lines and electric traction vehicles is presented. The sensor consists of two parts; a leakage current measurement and a lightning surge detection. Measured data are transmitted to a supervisory computer through ZigBee protocol based on IEEE 802.15.4. To detect leakage current, a window type Mn-ZCT is used and a low-noise amplifier with a gain of 60dB is designed, and this can measure leakage current in ranges of $100{\mu}A{\sim}5mA$. A sample-hold (S/H) and a Rogowski coil are injected to analyze the magnitude of surge current in ranges from 100A to 10kA with $8/20{\mu}s$-waveform.

산화아연형 피뢰기 소자의 뇌충격전류에 의한 특성 변화 (Change of the Characteristics of ZnO Arrester Blocks by Lightning Impulse Current)

  • 한주섭;송재용;길경석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.907-909
    • /
    • 1998
  • This paper describes the effect of impulse current on degradation of ZnO blocks. In this study, an impulse current generator which can produce 8/20 [${\mu}s$], 3 [kA] and 4/10 [${\mu}s$], 5 [kA] waveform is designed and fabricated to simulate the lightning impulse current. The residual voltage, reference voltage, and leakage current flowing to the ZnO blocks are observed. The experimental results show that the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in operating voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

공장전기설비의 누전차단기 오동작 조사 및 전력품질분석 (Power Quality Analysis and Failure Survey of Earth Leakage Breakers in Factory Electrical Installation)

  • 이상익;최규하
    • 전력전자학회논문지
    • /
    • 제13권1호
    • /
    • pp.15-21
    • /
    • 2008
  • 공장전기설비에서 개인용 컴퓨터, 정류기, 전기로와 시험장치 등의 비선형 부하 사용 증가에 따른 고조파 발생으로 누전차단기가 오동작하거나 불필요 동작을 하고 있다. 따라서 공장전기설비의 안전관리자를 대상으로 누전차단기의 오동작 상태에 대한 조사를 실시하였다. 또한 누전차단기가 오동작하거나 불필요 동작을 하고 있다는 수용가에서 전압, 전류, 고조파와 불평형 등 전력품질을 측정하고 분석하였다. 본 연구결과는 왜형된 전류파형으로 누전차단기의 트립특성 시험과 누전차단기 오동작 원인분석시 자료로 활용하고자 한다.