HVDC 시스템에서 클리폰 릴레이 오동작 분석에 관한 연구 (A Study of Analysis on Klippon Relay Malfunction in HVDC System)

  • 김찬기;박종광;추진부
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제54권9호
    • /
    • pp.437-443
    • /
    • 2005
  • This paper deals with an experimental study for Klippon reiay in Cheju-Heanam HVDC system Klippon relay was troubled many times for years, and Klippon relay's fault caused the HVDC system trip. So for several years, these reasons of Klippon relay fault were investigated. The malfunction of Klippon relay in Cheju-Haenam HVDC system has been caused by the incoming of random surge(current source and voltage source). This paper has stu야ed the theoretic리 analysis and experimental study of Klippon relay, and the solutions against the problems were suggested according to their causes. Among the problems, grounding problem was removed by one-point earth connection and by modification of grounding circuit. The effects of inrush current was removed by inserting the blocking diodes by series in Klippon relay circuits. Finally, The over-voltage induced on Klippon relay, by a relay excitation coil, was removed by inserting a free-wheeling diode in Parallel with the excitation coil.

제주-해남 HVDC 시스템에서 클리폰 릴레이 오동작 분석에 관한 연구 (A Study on the Analysis of Klippon Relay Malfunction in Cheju-Heanam HVDC System)

  • 김찬기;박종광;최영도
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2005년도 전력전자학술대회 논문집
    • /
    • pp.173-175
    • /
    • 2005
  • Malfunction of Klippon relay in Cheju-Haenam HVDC system has been caused by the inflow of high voltage arc. In this paper, we have studied on the theoretical examination and data analysis of Klippon relay, and the countermeasures against the problems were suggested according to their causes. Grounding problem in Klippon relay is removed by one-point earth connection and by modification of grounding circuit. The effects of over current surge was removed by attaching blocking diodes by series In Klippon relay to remove surge input in Klippon relay's mercury contact. The problem of Induced overvoltage by 86re1ay excitation coil, was removed by attaching Free-wheeling diode in parallel with the excitation coil of Lock-out relay.

  • PDF