A Study on the Analysis of Klippon Relay Malfunction in Cheju-Heanam HVDC System

제주-해남 HVDC 시스템에서 클리폰 릴레이 오동작 분석에 관한 연구

  • Published : 2005.07.04

Abstract

Malfunction of Klippon relay in Cheju-Haenam HVDC system has been caused by the inflow of high voltage arc. In this paper, we have studied on the theoretical examination and data analysis of Klippon relay, and the countermeasures against the problems were suggested according to their causes. Grounding problem in Klippon relay is removed by one-point earth connection and by modification of grounding circuit. The effects of over current surge was removed by attaching blocking diodes by series In Klippon relay to remove surge input in Klippon relay's mercury contact. The problem of Induced overvoltage by 86re1ay excitation coil, was removed by attaching Free-wheeling diode in parallel with the excitation coil of Lock-out relay.