Variation in Leakage Current Characteristics of Polymer Insulator for Various Environmental Condition (여러 환경조건에 대한 고분자애자의 누설전류 특성 변화)

  • Park Jae-Jun;Choi In-Hyuk;Lee Dong-il
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.19 no.2
    • /
    • pp.169-175
    • /
    • 2006
  • This study investigated variation leakage current maximum value and waveform considering applied voltage phase angel by simulating three environmental conditions, such as fog, salt fog, and kaolin contamination .As the result of applied voltage phase angel characteristics, leakage currents presented almost in phases in the early stage regardless of environmental conditions just after applying the voltage, and the phase of leakage currents certain phase lags for the discharge of the applied voltage when surface discharges occurred due to the continuous environmental contamination. In addition, the difference in phase significantly increased according to the intensity of discharges. The change in distortion rates according to the environmental contamination presented a nearly same level just after applying the voltage. The distortion rate of third harmonic for the fundamental wave presented by the order of fog>salt fog>kaolin when surface discharges occurred due to the applied voltage for certain continued periods. In the case of the fog and salt fog, the scale of spectrums decreased according to the increase in frequencies from the results of the analysis of high frequencies. In addition, the even number frequency presented a relatively large level compared to the odd number frequency under the kaolin contamination.

Contamination Characteristics of Polymer Insulator using High Frequency Current Transformer (HF-CT센서를 이용한 고분자애자의 오손특성)

  • Park, Jae-June
    • The Journal of Information Technology
    • /
    • v.8 no.4
    • /
    • pp.1-7
    • /
    • 2005
  • Investigations of high frequency current transformer(HF-CT) waveform characteristics of the surface leakage on kaolin polluted EPDM polymer insulators have been performed. This work is part of a program aimed at examining the potential for HF-CT waveform characteristics analysis to provide information about the environment contaminants and environment condition of polymer insulators. The investigation reported examined the HF-CT waveform characteristics at high frequencies. The use of high frequency measurements for on-line applications reduces electrical inference. This work was peformed utilizing HF-CT to monitor of surface polluted discharge. It was found that HF-CT waveform frequency spectrum, magnitude depend on importantly the duration of the surface discharge activity.

  • PDF

Classification Technique of Kaolin Contaminants Degree for Polymer Insulator using Electromagnetic Wave (방사전자파를 이용한 고분자애자의 오손량 분류기법)

  • Park Jae-Jun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.19 no.2
    • /
    • pp.162-168
    • /
    • 2006
  • Recently, diagnosis techniques have been investigated to detect a Partial Discharge associated with a dielectric material defect in a high voltage electrical apparatus, However, the properties of detection technique of Partial Discharge aren't completely understood because the physical process of Partial Discharge. Therefore, this paper analyzes the process on surface discharge of polymer insulator using wavelet transform. Wavelet transform provides a direct quantitative measure of spectral content in the time~frequency domain. As it is important to develop a non-contact method for detecting the kaolin contamination degree, this research analyzes the electromagnetic waves emitted from Partial Discharge using wavelet transform. This result experimentally shows the process of Partial Discharge as a two-dimensional distribution in the time-frequency domain. Feature extraction parameter namely, maximum and average of wavelet coefficients values, wavelet coefficients value at the point of $95\%$ in a histogram and number of maximum wavelet coefficient have used electromagnetic wave signals as input signals in the preprocessing process of neural networks in order to identify kaolin contamination rates. As result, root sum square error was produced by the test with a learning of neural networks obtained 0.00828.

Characteristics Leakage Current of Surface Discharge according to Kaolin Contamination by Deteriorated Polymer Insulators (열화된 고분자애자의 카올린 오손에따른 표면방전특성)

  • Park, Jae-Jun;Ga, Pyung-Hyun;Seo, Ui-Won;Jung, Myeong-Yeon;Song, Il-Kwen;Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1100-1103
    • /
    • 2004
  • The paper presents the results of using the fundamental and the low frequency harmonic components of leakage current to study aging of EPDM insulator for contaminated condition by kaolin. The largeer the leakage current during 200ms, the higher harmonic component at 60hz. The harmonic component at 60hz and the odd order harmonics is increase relation without Kaolin Conent. Arcing on the surface was always associated with distortion in the leakage current; hence the low frequency components of the leakage currnent can be used as a means to evaluate the surface degration. Both the fundamental and 3rd & 5th harmonics increase dry-band activity.

  • PDF

A Study on Mechanism about Contaminant Accumulation of Insulator Surface (애자표면의 오손물 누적에 관한 메커니즘 연구)

  • Park, Jae-Jun
    • The Journal of Information Technology
    • /
    • v.8 no.2
    • /
    • pp.85-91
    • /
    • 2005
  • We studied a pollution mechanism for simulation of contamination environment in industrial concentrated area of around a metropolitan that made to circulated flow in the chamber. In case of the virgin both side of EPDM or Silicon insulator, we confirmed that the pollution to much more than service insulator in the field. Also contamination of initial state of the virgin didn't falling in spite of physical outside factor easily. This study confirmed to that the silicon was too much accumulated pollution contrast to EPDM insulator from scatter(spray) point to regular interval position use the Kaolin contaminant in the chamber. There are effected to the hydrophobicity of polymer insulator due to the pollution. In ceramic insulator, we get to know that pollution is much more at the Post insulator with vertical than with horizontal setup insulator.

  • PDF

옥외에서 사용되는 배전급 폴리머 현수애자의 오손특성에 관한 연구

  • Lee, Byung-Sung;Han, Sang-Ok
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.7
    • /
    • pp.340-345
    • /
    • 2001
  • Because they have superior insulating properties and lower in price than their ceramic equivalents, polymeric insulators have been used in outdoor insulators. But polymeric insulators mainly using in an heavy contamination area of outdoor could be easily attached to contaminants such as salt and by-products of industrial processes. To understand its effect on contaminants adhered to these insulators, we dismounted polymeric insulators adhered contaminant in the field, and evaluated its electrical characteristics, CA, and ESDD. We also manufactured slurry mixed by some kaolin and salt for the artificial contamination test and measured the degree of contaminant, AC leakage current for these contaminated samples. Consequently, the adhered contaminants to its surface is likely to be affected the performance of insulation.

  • PDF

Signal analysis of surface discharge and electromagnetic wave for insulator by kaolin contamination (카올린으로 오손된 애자의 표면방전 및 방사전자파의 신호 분석)

  • Park, Jae-Jun
    • The Journal of Information Technology
    • /
    • v.7 no.3
    • /
    • pp.113-118
    • /
    • 2004
  • Recently, diagnosis techniques have been investigated to detect a partial discharge associated with a dielectric material defect in a high voltage electrical apparatus. However, the properties of detection technique of PD aren't completely understood because the physical process of PD. Therefore, this paper analyzes the process on Surface Discharge of Polymer Insulator using Wavelet transform. Wavelet transform provides a direct quantitative measure of spectral content in the time frequency domain. As it is important to develop a non-contact method for detecting the Contamination Degree, this research analyzes the electromagnetic waves emitted from PD using Wavelet transform. This result experimentally shows the process of PD as a two-dimensional distribution in the time-frequency domain. The method is shown to be useful for detecting prediction of contamination degree.

  • PDF

Analyses of Leakage Current of Transmission Insulator as a Function of Environmental Condition (환경에 따른 송전용 애자의 누설전류 분석)

  • Choi, In-Hyuk;Lee, Dong-Il;Kim, Chan-Young
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1166-1170
    • /
    • 2004
  • The leakage currents of transmission insulator were investigated as a function of environmental conditions, such as temperature, humidity, and rainfall. The insulators were artificially contaminated with insoluble yellow soil and kaolin which helped salt to stick on the surface of insulator. The insulators contaminated with the grade of B, C, and D were installed in the KoChang Testing Center. The leakage currents were measured and compared with non-contaminated insulators. The results indicated that the most important factor affecting leakage current was humidity. After heavy rain, the artificially contaminated salt was dissolved, resulting in similar characteristics between with and without contamination

  • PDF

Mineralogical Study on the Clay Formation and Heavy Metal Speciation in the Acidified Soil Profile of the Onsan Industrial Area (온산공업지역 산성 토양 프로화일 내에서의 점토광물의 생성과 중금속 이온의 거동에 관한 광물학적 연구)

  • 이상수;김수진
    • Journal of the Mineralogical Society of Korea
    • /
    • v.15 no.1
    • /
    • pp.1-10
    • /
    • 2002
  • The present study is focused on the granite weathering and soil formation, and the heavy metal contamination in soils in the Onsan industrial area. For profile study, soil sampling was conducted on each depth and experimental analyses have been conducted on those samples. X-ray diffraction analyses show that clay minerals consist mainly of kaolin minerals, vermiculite, and minor illite. Most of kaolin minerals in the lower kiwi of the profile consist of halloysite as confirmed by formamide intercalation, but the content of halloysite decreases gradually toward the surface since it has been transformed to kaolinite in the upper part of the profile. Thermal treatment by heating at $110^{\circ}C,\;300^{\circ}C,\;and\;550^{\circ}C$ shows a diffuse and broad peak the between 10 and $14\;{\AA}$ region in X-ray diffractograms. This suggests the possible existence of the hydroxy-Al interlayerecl vermiculite. Na-citrate extraction method reaconfirms this result showing transition of $14\;{\AA}$ peak to $10\;{\AA}$ In by removing the interlayer materials and restoring the vermiculite to its original state. The occurrence of hydroxy-Al interlayered vermiculite is also supported by soil pH distribution room 3.9 In the lower part to 3.6 in the upper part of the profile. Sequential extraction experiment was conducted to investigate the states of heavy metals in soils. The experiment shows that relatively high amounts of heavy metals are concentrated in the upper part of the profile and that most of them are bound to Fe/Mn oxides and organic matters while less concentration in clay minerals. The result indicates that most of heavy metal pollutants are concentrated in the surface soil and that the low concentrations of heavy metals in clays are mainly due to the low adsorption capacities of clay minerals such as kaolin minerals and hydroxy-Al interlayered vermiculite in acidified soil condition.

Application of coagulation pretreatment for enhancing the performance of ceramic membrane filtration (세라믹 막여과의 성능향상을 위한 응집 전처리의 적용)

  • Kang, Joon-Seok;Song, Jiyoung;Park, Seogyeong;Jeong, Ahyoung;Lee, Jeong-Jun;Seo, Inseok;Chae, Seonha;Kim, Seongsu;Kim, Han-Seung
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.31 no.6
    • /
    • pp.501-510
    • /
    • 2017
  • In this study, it is estimated that ceramic membrane process which can operate stably in harsh conditions replacing existing organic membrane connected with coagulation, sedimentation etc.. Jar-test was conducted by using artificial raw water containing kaolin and humic acid. It was observed that coagulant (A-PAC, 10.6%) 4mg/l is the optimal dose. As a results of evaluation of membrane single filtration process (A), coagulation-membrane filtration process (B) and coagulation-sedimentation-membrane filtration process (C), TMP variation is stable regardless of in Flux $2m^3/m^2{\cdot}day$. But in Flux $5m^3/m^2{\cdot}day$, it show change of 1-89.3 kpa by process. TMP of process (B) and (C) is increased 11.8, 0.6 kpa each. But, the (A) showed the greatest change of TMP. When evaluate (A) and (C) in Flux $10m^3/m^2{\cdot}day$, TMP of (A) stopped operation being exceeded 120 kpa in 20 minutes. On the other hand, TMP of (C) is increased only 3 kpa in 120 minutes. Through this, membrane filtration process can be operated stably by using the linkage between the pretreatment process and the ceramic membrane filtration process. Turbidity of treated water remained under 0.1 NTU regardless of flux condition and DOC and $UV_{254}$ showed a removal rate of 65-85%, 95% more each at process connected with pretreatment. Physical cleaning was carried out using water and air of 500kpa to show the recovery of pollutants formed on membrane surface by filtration. In (A) process, TMP has increased rapidly and decreased the recovery by physical cleaning as the flux rises. This means that contamination on membrane surface is irreversible fouling difficult to recover by using physical cleaning. Process (B) and (C) are observed high recovery rate of 60% more in high flux and especially recovery rate of process (B) is the highest at 95.8%. This can be judged that the coagulation flocs in the raw water formed cake layer with irreversible fouling and are favorable to physical cleaning. As a result of estimation, observe that ceramic membrane filtration connected with pretreatment improves efficiency of filtration and recovery rate of physical cleaning. And ceramic membrane which is possible to operate in the higher flux than organic membrane can be reduce the area of water purification facilities and secure a stable quantity of water by connecting the ceramic membrane with pretreatment process.