A Study on Electrical Fire Disaster Prevention Device used in Double Circuit Break (고정밀 전류센서를 이용한 이중 차단용 전기화재 방재장치에 관한 연구)

  • Park, Dong-Pil;Kwak, Dong-Kurl;Jung, Do-Young;Kim, Choon-Sam;Shin, Ho-Joon
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2102-2103
    • /
    • 2008
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device(RCD) of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms](KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this paper is proposed to a electrical fire disaster prevention device(EFDPD) for a RCD trip or a self circuit-breaking function on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.

  • PDF

Development of Prevention Apparatus for Short-Circuit Faults Using the Line Voltage Drop of Neutral Wire (중성선 선로 전압강하를 이용한 단락사고 방지용 보호장치 개발)

  • Kwak, Dong-Kurl;Kim, Jin-Hwan;Lee, Bong-Seob
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.12
    • /
    • pp.1953-1958
    • /
    • 2012
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with such electric faults, specially short circuit faults. Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB), that is, Residual Current Protective Devices (RCDs) used on low voltage distribution lines cut off earth leakage and overload, but the RCD can not cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied in low voltage distribution panel are prescribed to rated breaking time about 30ms(KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To improve such problem, this paper proposes a prevention apparatus using the line voltage drop of neutral wire and some semiconductor switching devices. Some experimental tests of the proposed apparatus confirm the validity of the analytical results.

A Study on the Real Condition and Life Time of the RCD (누전차단기 실태조사 및 교체주기에 관한 연구)

  • Kim, Chong-Min;Choi, Myeong-Il;Kim, Young-Seok;Bang, Sun-Bae;Shong, Kil-Mok;Seo, Jung-Youl
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.4
    • /
    • pp.467-472
    • /
    • 2010
  • In this study, an analysis of the used RCD's condition is conducted to assess the effect on environment of installation area, terms of use, corrosion, contamination etc. According to KS C 4613, the used RCDs were tested to get date which is the RCD's life time. And then, the date is analysed using Minitab which is a statistical program for reliability analysis. As a result, The RCD's MTTF for the all samples is $12.7{\pm}0.23$ years. and the MTTF of RCDs which are used indoor area is $12.9{\pm}0.34$ years, the MTTF of RCDs which are used outdoor area is $11.9{\pm}0.30$ years. Futhermore, the MTTF of RCDs which are used in dry area is a $13.1{\pm}0.26$ years, the MTTF of RCDs which are used in dust area is $13.0{\pm}0.57$ years, the MTTF of RCDs which are used in moisture area is $8.4{\pm}0.77$ years.

The Implementation of Active Leakage Current Detecting Algorithm based on 16 bit Signal Processor (16비트 신호처리 프로세서 기반 유효성분 누설전류 감지 알고리즘 구현)

  • Han, Young-Oh
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.11 no.6
    • /
    • pp.605-610
    • /
    • 2016
  • The ELCB(: Earth Leakage Circuit Breaker) is the only way being used to prevent accidents from happening caused by electrical disaster. However, the existing ELCB has a limit to prevent damages to life and property due to a electric fire and a human body electric shock caused by the resistive leakage current, because of detecting the total leakage current in the block range of 15mA~30mA. It also has problems such as reduced productivity and reliability due to malfunctions by capacitive leakage currents. In this study, we have implemented the algorithm for the resistive leakage current detection technique and developed the resistive leakage current detection module based on a MSP430 processor, 16bit signal processor and this module can be operated in a desired block threshold within 0.03 seconds as specified in KS C 4613.

Development of electric safety control system for incapable operation of ELB and MCB using the low voltage distribution line (저압 배전선로의 누전 및 배선용 차단기의 오동작 방지를 위한 전기안전 제어장치 개발)

  • Kwak, Dong-Kurl;Shin, Mi-Young;Jung, Do-Young;Kim, Hyo-Jin;Baek, Seong-Hyun;Choi, Byung-Seub
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.371-372
    • /
    • 2007
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device (RCD), that is Earth Leakage Circuit Breaker(ELB) and Molded_case Circuit Breaker (MCB), of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this research development is proposed to a auxiliary control apparatus for RCD trip on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.

  • PDF