• Title/Summary/Keyword: Jet-fan for smoke control

Search Result 14, Processing Time 0.021 seconds

Study of the Smoke Control Characteristics for Fire Near Jet Fans (Jet fan 근접 화재 발생 시 제연 특성 연구)

  • Kim, Jong-Yoon;Seo, Tae-Beom;Lim, Kyung-Bum;Yoo, Ji-Oh;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.21 no.1 s.65
    • /
    • pp.82-89
    • /
    • 2007
  • In this research, we conducted a PIV-visualization experiment to smoke control from fires by using a neighboring Jet fan at minimum distance. We also compared our experiment results with FDS numerical analysis ones. As a result of quantitative data analysis of smoke control modes against fires in tunnel, we concluded that a neighboring Jet fan should be placed at least 25 m away from its fire source in order to produce satisfactory smoke control results. Jet fan showed the best smoke-controlling performance, if placed 50 m away from its fire source. It tended to show an overspeed around the center of tunnel when it is placed more than 75 away from its fire source.

A Study on Smoke Control Characteristic by the Effect off Jet Fan Installation Distance (제트팬 이격거리에 따른 연기제어특성에 관한 연구)

  • Kim, Jong-Yoon;Jeon, Yong-Han;Seo, Tae-Beom;Yoo, Ji-Oh;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.22 no.1
    • /
    • pp.16-23
    • /
    • 2008
  • In this research, the visualization experiment for a scaling tunnel was conducted to establish the optimum fire protection system in tunnel fires. In order to find the optimal operating condition of jet fan with the fire, the characteristics of smoke propagation was considered to find the optimal operating condition of jet fan at the time of tunnel fire, the concentration of smoke was measured experimentally for various jet fan position and it's operating condition. As a result, when jet fan in the vicinity of fire operates at the upstream, the back-layering of the smoke should be considered with separation distance from the fire source. The distance between the jet fan and the fire should be longer than 50 m. On the other hand, when the vicinity jet fan operates at the downstream, the back-layering of smoke does not occur, but stratification is not maintained because the smoke dispersion occurs at the downstream due to the operation of the jet fan.

Evaluation of Smoke Control Performance of Ventilation System Using by Hot Smoke Test (Hot Smoke Test를 이용한 주차장 환기설비의 제연 성능평가)

  • Joung, Suckhwan
    • Journal of Korean Society of Disaster and Security
    • /
    • v.12 no.2
    • /
    • pp.47-56
    • /
    • 2019
  • Recently, in order to overcome the difficulty of entering a fire source due to the occurrence of a large amount of smoke in the event of a fire in a parking lot, it has used that a method of discharge smoke using air supply, exhaust fans and jet fans installed for ventilation of parking lots. In this study, the variation of flow in the smoke layer was observed using CCTV under two conditions, in which only the air supply fan operates and the manned fan operates together, and the temperature around the plume was compared to Albert eq. to assess its suitability as a parking lot ventilation performance evaluation method. As a result, it was found that the smoke layer could be disturbed if the Jet Fan was operated at the same time, which could lead to the possibility of an initial evacuation disturbance. However, the additional operation of the Jet Fan has been confirmed by the observation CCTV that the emission performance is improved, which is believed to help conduct the suppression operation. The temperature around the plume was measured and compared to Alpert eq, and was analyzed to be about $2^{\circ}C$ lower at the center axis of the plume and $9.0^{\circ}C$ higher at 8 m in the direction of the discharge of smoke. The results of temperature measurements around the plume were lower than the maximum temperature expected in AS 4391 and did not exceed the expected temperature risk caused by the experiment. As with these results, the temperature risk from the progression of hot smoke tests is foreseeable, so it will be available as one of the general evaluation methods for assessing smoke control performance in a parking lot without relevant criteria.

A Numerical Study on Effective Smoke-Control System of a Rescue Station in a Tunnel Fire (터널내 열차 화재시 효과적인 구난역 제연 설비를 위한 수치 해석 연구)

  • Yang, Sung-Jin;Won, Chan-Shik;Hur, Nahm-Keon;Cha, Chul-Hyun
    • 유체기계공업학회:학술대회논문집
    • /
    • 2006.08a
    • /
    • pp.575-578
    • /
    • 2006
  • In designing smoke-control system of rescue station in train tunnel, a purpose is to prevent a disaster by proposing the jet fan operation together with smoke-control curtain in tunnel fire. This study has investigated the relationship of the Heat Release Rate(HRR) and a adequate ventilation velocity to control the fire propagation in tunnel fire, and has improved the effect of the smoke-control curtain on preventing the flow of pollutants. In this study, Computational Fluid Dynamics(CFD) simulations with ST AR-CD(ver 3.24) were carried out on predicting the fire spreading and the flow of pollutants, considering jet fan operations and effect of smoke-control curtain. Our simulation domain is the full scale model of the 'DAEGWALLYEONG' 1st tunnel. The results represent that ventilation operation can control the fire spreading and pollutants effectively to prevent a disaster.

  • PDF

An Experimental Study of Smoke Control in Tunnel Fires with Jet Fan (터널화재시 제트팬에 의한 연기제어에 관한 실험적 연구)

  • 이성룡;김충익;유홍선;방기영
    • Tunnel and Underground Space
    • /
    • v.12 no.2
    • /
    • pp.92-98
    • /
    • 2002
  • In this study reduced-scale experiments were conducted to analyze smoke movement in tunnel fire with jet fan, The 1/20 scale experiments were carried out under the froude scaling using gasoline pool fire range from 6.6 to 12.5 cm in diameter with total heat release rate from 0.714 to 4.77 kW. In the case of fires under the 2.5kW, backlaying was reduced about 40cm and smoke was effectively controled in downstream of the fan when operating the fan. The smoke layer was moved down and the ceiling temperature was decreased compared to that of without fan case in upstream of the fan, but the temperature in the lower part of the tunnel was increased.

A NUMERICAL STUDY OF THE VENTILATION AND FIRE SIMULATION IN A ROAD TUNNEL (도로터널 환기/제연 시스템 시뮬레이션)

  • Park, Jong-Tack;Won, Chan-Shik;Hur, Nahm-Keon;Cha, Cheol-Hyun
    • Journal of computational fluids engineering
    • /
    • v.11 no.4 s.35
    • /
    • pp.20-25
    • /
    • 2006
  • In the present study, flow characteristics inside a road tunnel are simulated for the ventilation flows due to jet fan system and flows induces by the traffic. Traffic ventilation is numerically simulated by multiple reference frame. From the results of steady state simulation of tunnel ventilation, it is found that the proper ventilation is achieved by the designed jet fan system along with ventilating flow induced by the traffic. A transient simulation is also performed for the case of vehicle fire in the tunnel reversing the direction of rotation of some fans. The results suggest that the heat and smoke can be controlled by the proper changing of fan operation mode. The present results can be used to design proper ventilation system and effective smoke control system as well.

Analysis of Smoke Control According to Jet Fan Location in Straight Long Tunnel (제트 팬 설치 위치에 따른 직선터널 내의 제연해석)

  • Byun, Ju-Suk;Lim, Hyo-Jae;Kang, Shin-Hyung;Lee, Jin-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.9
    • /
    • pp.662-668
    • /
    • 2007
  • In this study, jet fans are installed with 4 cases in the straight long tunnel; inlet-side setup, middle-side setup, outlet-side setup, and dispersion setup. A bus is selected as fired car, of which fire size is 20MW. And fired car locates at 100m, 700m, 1500m position from tunnel inlet, respectively. FLUENT, commercial finite-volume code, is used to analyze the performance. The velocity profile, $CO_2$ concentration, temperature distribution are examined for analysis. Performance of smoke control is compared by the backlayering length. Consequently, inlet-side setup of jet fans is a little more efficient than other cases considering the fire occurrence frequency in tunnel.

A fundamental study on the jet fan capacity for smoke control considering thermal buoyancy force in tunnel fires (터널 화재 시 열부력을 고려한 제연용 제트팬 용량산정에 관한 기초 연구)

  • Lee, Ho-Hyung;Choi, Pan-Gyu;Jo, Jong-Bok;Lee, Seung-Chul;Lee, Chang-Woo
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.20 no.2
    • /
    • pp.501-511
    • /
    • 2018
  • As a result of the recent revision of the 'Guideline for Installation and Management of Fire Prevention Facility in Road Tunnels', the thermal buoyancy has to be taken into account when calculating the capacity of jet fans for smoke control in tunnel fires. However, there is no detailed methodologies for considering thermal buoyancy, so further study is needed. In this study, the thermal buoyancy in the tunnel is calculated by 3-D numerical simulation to consider the thermal buoyancy in case of fire in tunnels, and the relationship between heat buoyancy and vehicle drag, And the method of calculating the capacity of the jet fan for smoke control in tunnels. According to the analysis results, heat buoyancy acts as a resistance force in the case of a down-slope tunnel, and the pressure rise of jet fan for smoke control is not simply determined by the value of heat buoyancy at the entrance of the tunnel and the value of the vehicle drag at the exit. And it is analyzed that it is necessary to carry out a comprehensive review according to the location of the fire vehicle in tunnels.

Retraction: A numerical study on the fire smoke behavior by operating the fire prevention system in tunnel-type structure (논문 취소: 터널형 구조물의 방재시설 가동에 따른 화재연기 거동에 관한 수치 해석적 연구)

  • Lee, Ho-Hyung;Choi, Pan-Gyu;Lee, Sang-Don;Heo, Won-Ho;Jo, Jong-Bok
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.21 no.1
    • /
    • pp.189-199
    • /
    • 2019
  • In this study, behaviors of fire smoke in the operation of disaster prevention facilities (smoke damper, jet fan) in a tunnel-type structure (soundproof tunnel) were investigated numerically and results of the investigation were compared and analyzed. Through the simulation and analysis, it was found that there was a significant change in the patterns of fire smoke between the opening of the ceiling of a fire vehicle and the closing, and it was shown that the critical temperatures of PC and PMMA, main materials of a soundproof tunnel were not exceeded. In addition, the simulation of installation intervals of smoke dampers showed that the maximum temperature of a soundproof tunnel without smoke dampers was $552^{\circ}C$ while it reached $405^{\circ}C$ when smoke dampers were installed at the installation interval of 50 m. The simulation of the operation of a jet fan showed that the maximum temperature of a soundproof tunnel without a jet fan was $549^{\circ}C$ while it reached only $86^{\circ}C$ when a jet fan was operating. Therefore, it is highly expected that they could create a favorable environment for evacuation and protection of soundproofing materials, and it would be necessary to promote basic studies on tunnels serving various functions and purposes.

A comparative study on the relationship between estimates of critical velocity and number of jet fans for smoke control - A 'Fire-JF' contour map in road tunnels (임계속도와 제연팬 용량의 상관관계 연구 - 도로터널의 제연팬 특성도 연구)

  • Kim, Hyo-Gyu;Kim, Eun-Soo;Kim, Nam-Young;Lee, Chang-Woo
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.6 no.4
    • /
    • pp.269-278
    • /
    • 2004
  • Recently, critical velocity has become a topic to attract most interests from the researchers in the field of tunnel safety. As the minimum velocity to prevent smoke backlayering during a fire, many equations have been proposed so far, and the following three equations are being considered as a standard method in Korea to calculate the capacity of smoke extraction fans. Equation by Kennedy based on Froude number, Tetzner' s equation with additional variable, ${\beta}$ to modify the Kennedy's equation, and the equation with the concept of super critical velocity by Wu are studied in this paper for the comparative purpose. A contour map describing the relationship between the critical velocity and the capacity of smoke extraction fans is proposed as a tool to calculate the number of jet fans for smoke control during a fire in the local tunnels.

  • PDF