Modeling and Analysis of Modified Active Frequency Drift Method (개선된 AFD기법의 모델링 및 분석)

  • An, Jin-Ung;Yu, Gwon-Jong;Choy, Ich;Choi, Ju-Yeop;Lee, Ki-Ok
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.16 no.2
    • /
    • pp.145-151
    • /
    • 2011
  • In this paper, among the active islanding detection techniques, the modified active frequency drift method was analyzed, which is relatively easy to apply to the single-phase grid-connected PV PCS. The existing designs for turbulences in these applications were empirically conducted, and do not have sufficient reliability and performance. Therefore, three application forms of the modified active frequency drift technique were modeled, based on which the proper magnitude of turbulence, which is the frequency acceleration component, was calculated. Using the results, the magnitude of and injection method for turbulence for ensuring the islanding detection performance and improving the output power quality were proposed, and they were verified via simulations and experiment to prove that the reliable islanding detection technique can be developed merely by measuring the basic output power quality, without the need for expensive islanding simulation equipment.

Islanding detection method for distributed generations using the change of the voltage unbalance and the output power of DG (전압 불평형과 발전기 출력 변동을 이용한 분산전원의 단독운전 판단 기법)

  • Kang, Yong-Cheol;Jang, Sung-Il;Lee, Ji-Hoon;Cha, Sun-Hee;Kim, Yeon-Hee;Lee, Byung-Eun;Kim, Yong-Guen
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.240-241
    • /
    • 2006
  • Islanding operations of DG usually occur when power supply from the main utility is interrupted due to several reasons but the DG keeps supplying power into the distribution networks. These kinds of islanding conditions cause negative impacts on protection, operation, and management of distribution systems. Therefore, it is necessary to effectively detect the islanding conditions and swiftly disconnect DG from distribution network. This paper proposes the islanding detection algorithm for DG using the change of the voltage unbalance and the output power of DG. The proposed method effectively combines the conventional parameters for detecting the islanding conditions. The proposed methods were verified using the radial distribution network of IEEE 34 bus.

  • PDF

A Novel Active Anti-islanding Method using Effective Power Variation (유효전력변동방식을 이용한 새로운 단독운전 검출기법 연구)

  • Yu Byung-Gyu;Jung Young-Seok;Matsui Mikihiko;Yu Gwon-Jong
    • Proceedings of the KIPE Conference
    • /
    • 2006.06a
    • /
    • pp.213-215
    • /
    • 2006
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and power supply facilities as a result of unsynchronized reclosure. In order to prevent the phenomenon, various anti-islanding methods have been studied. This paper proposes the variation method of inverter output current magnitude to prevent the islanding phenomenon as a novel method, which causes the large frequency variation of inverter output voltage after islanding. Unlike most active anti-islanding method deteriorating power quality, this novel method will have high performance of islanding detection and good power quality. For the verification of the proposed method, the simulated result and analyses are presented.

  • PDF

Islanding Detection Technique using Wavelet Energy in Grid-Connected PV System (웨이블렛 에너지를 이용한 태양광 발전시스템의 단독운전 검출 기법)

  • Park, Hae-Chan;Kim, Il-Song
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.20 no.5
    • /
    • pp.471-478
    • /
    • 2015
  • The new islanding detection method using wavelet energy is proposed in this paper. The proposed method is based on the autocorrelation of the wavelet energies, which is obtained from the high-frequency components of the grid voltage. It has the enhanced detection capabilities in the UV/OV/UF/OF region, which the conventional passive methods cannot obtain. The mathematical theories on the wavelet are presented, and the performance effectiveness is proved by the experimental results.

A Case Study on the Islanding Detection Protection of PV System and ESS System (태양광 발전과 ESS 시스템의 연계운전시 단독운전 방지 사례 연구)

  • Lim, Jong Rok;Hwang, Hye-Mi;Shin, Woo Gyun;Ju, Young-Chul;Jung, Young Seok;Kang, Gi-Hwan;Ko, Suk-Whan
    • Journal of the Korean Solar Energy Society
    • /
    • v.39 no.1
    • /
    • pp.59-66
    • /
    • 2019
  • BIPV or BAPV installation applied to building is increasing through public utility mandates enterprise. Solar PV energy generates only during the day, but if it is operated in convergence with ESS, which stores electrical energy, it can restrain the fossil energy used in buildings throughout the day. A solution is to converge with PV system and ESS. However, PV systems and ESS connected to the power grid in parallel can cause problems of electrical stability. A study was conducted on the case of failure to detect islanding operation under the parallel operation of PV generation and ESS that are connected in parallel to power grid. Experiments conducted various non-islanding detections under the operating conditions. In the experiment results, when one PCS - PV inverter or ESS inverter - was operating under the islanding condition, it stopped working within 0.5 seconds of the Korean grid standard. However, when both of PV inverter and ESS inverter were operating at the same time under the islanding situation, the anti-islanding algorithm did not operate normally and both inverters continuously supplied power to the connected RLC loads. islanding detection Algorithm developed by each inverter manufacturer has caused this phenomenon. Therefore, this paper presented a new test standard for islanding detection.

Novel Islanding Detection Method for Distributed Generation Interconnected with Utility Grid (계통연계 분산전원의 새로운 단독운전 판별기법)

  • Bae, Byung-Yeol;Lee, Doo-Young;Ko, Jong-Sun;Choi, Nam-Sub;Han, Byung-Moon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.1
    • /
    • pp.65-72
    • /
    • 2008
  • This paper describes the development of a novel islanding detection method, which uses the signal cross-corelation scheme between the injected reactive current and the power frequency deviation. The existing method, which injects the reactive current of 2.5-5% to the rated current and detects the frequency deviation directly, brings about lowing the power quality due to the harmonic pollution. The proposed method eliminates the weak point of the existing method, because it injects the reactive current less than 1% to the rated current. The operational feasibility was verified through computer simulations with PSCAD/EMTDC software, and experimental works with a 10kVA hardware prototype. The proposed method can detect the islanding status effectively without lowing the power quality of interconnected distributed generation system.

Islanding Detection Method of Embedded Generator connected to Power Distribution System (분산형전원이 도입된 배전계통에 대한 ISLANDING DETECTION METHOD)

  • Hwang, J.S.;Kim, J.E.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.522-524
    • /
    • 2000
  • The installation of small sized Embedded Generator(EG) in parallel with the utility supply was required several technical complications for protection of the system. One of the most important protection is to provide protection against islanding and out of synchronism reclosing with the utility source. This paper explains several current methods of detecting 'Loss Of Mains'(LOM). But they have not proved completely dependable, in particular when the islanded load's capacity matches that of the EG. A new loss of mains protection algorithm is presented in this paper which based on measurement of the reactive power and node voltage for detecting the islanding condition even though the EG operate in the capacity.

  • PDF

A Study on Application of Islanding Detection Algorithm for Dispersed Generation Unit. (분산전원의 고립운전 검출 알고리즘 적용에 관한 연굴)

  • Jung Won Wook;Chung Il Yop;Moon Seung Il
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.217-219
    • /
    • 2004
  • The installation of small sized dispersed generation(DG) units operating in parallel with the utility supply presents several technical problems for the protection and control of the system. One of the critical concerns is the occurrence of islanding. Hence, this paper propose the Digital Universal Relay(DUR) including anti-islanding function as DG interconnection interface. The existent islanding detection algorithms are examined. And the most effective and reliable method of those is modified for DUR application. The modified algorithm is evaluated through the modeling of the test system by PSCAD/EMTDC.

  • PDF

Islanding detection of grid-connected photovoltaic inverters using Automatic phase-shift method (계통연계형 PV 인버터의 자동 위상 이동법에 의한 고립운전 검출)

  • Yun, Jung-Hyeok;Kim, Heung-Geun;Choi, Jong-Woo;Chun, Tae-Won;Lee, Hong-Hee
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.591-594
    • /
    • 2005
  • Islanding of PV systems occurs when the uitilty grid is removed but local sources continue to operate and provide power to local loads. Islanding Is one of the serious problems in an electric power system connected with dispersed power sources. Also, this scan present safety hazards and the possibility of damage to other electric equipments. If the real and reactive power of RLC load and PV system are closely matched, islanding phenomena can't be detected by the passive methods. Several active methods were proposed to detect islanding phenomena. The most effective method is SFS method which was suggested by Sandia National Laboratory. In this paper, a new anti-islanding algorithm is proposed and its validity is verified through simulation and experimental results for utility interconnection of PV system.

  • PDF

Study on the Islanding Detection Technique of the Grid-Connected Photovoltaic System using Grid Voltage Harmonic Coefficients (계통전원 하모닉을 이용한 태양광 발전 시스템의 단독운전 검출기법에 관한 연구)

  • Kim, Il-Song
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.15 no.6
    • /
    • pp.417-424
    • /
    • 2010
  • This paper proposes a new islanding detection method for a grid-connected photovoltaic system. It is based on the fact that the equivalent harmonic components vary according to the grid connection status. The advantage of the proposed method is the reduced Non-Detection Zone and fast detection time. Also it can have the robust detection capability against grid disturbances. The theoretic analysis using grid-harmonic modeling is performed and verified by test result using 32-bit high performance DSP processor.