고압전동기 고정자 권선의 PRPD 부분방전 결함신호 해석 (Analysis on Partial Discharge Fault Signals of PRPD for High Voltage Motor Stator Winding)

  • 박재준;이성룡;문대철
    • 한국전기전자재료학회논문지
    • /
    • 제19권10호
    • /
    • pp.942-946
    • /
    • 2006
  • We simulated insulation defects of stator winding wire on high voltage generator by 5 types. 4 types have one discharge source and other one has multi discharge source by simulation. For accurate decision, measurements used to PRPD pattern to occurred partial discharge source of various types. In this research, when PRPD pattern carried out or analyzed pattern recognition of discharge source, it used to powerful tools. In this result, PRPD Pattern defined to have single discharge source of 4 types by insulation defect. When insulation defect simulated, all the defected winding have not the same result. Errors for a little different can make mistakes from a subtle distinction. The difference between internal and void discharge have magnitude of pulse amplitude of inner discharge bigger than void discharge and have a shape of bisymmetry. But void discharge has a shape of bisymmetry against maximum value on polarity respectively. In cases of slot and surface discharge, we confirmed to show similar results those other researchers. In case of multi-discharge, as a result of we could classify not perfect match with occurred patterns in single discharge eachother. In the future, we will have to recognize and classify with results of multi-discharge.

고압전동기 고정자권선의 부분방전 특징추출 (Feature Extraction of Partial Discharge for Stator Winding of High Voltage Motor)

  • 박재준
    • 정보학연구
    • /
    • 제7권4호
    • /
    • pp.61-69
    • /
    • 2004
  • 본 논문에서는 6.6kV급 고압전동기 모델 코일을 4가지의 권선의 인공적인 결함을 갖도록 제작하였다. 운전중 모의를 위해 모델 코일에 80pF의 에폭시-마이카 커플러를 설치하였으며, TGA를 사용하여 NQN, 부분방전 크기 및 부분방전 패턴 등을 측정하였다. 웨이블렛 변환기법을 이용한 고압전동기의 고정자권선의 결함에서 발생된 부분방전신호의 파형을 통하여 여러 가지의 통계적인 파라메터를 통하여 특징을 추출하였다.

  • PDF

고압전동기 모델 코일에서 부분방전 분석 (Analysis of Partial Discharge in High Voltage Motor Model Coils)

  • 김희동
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제55권4호
    • /
    • pp.178-182
    • /
    • 2006
  • Five model coils of 6.6 kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals. The voltage applied to the coils was 3.81 kV, 4.76 kV, 6.0 kV and 6.6 kV, respectively. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns are consistent with the result of measurement using PDD and TGA instruments. AC breakdown test was performed on five model coils in order to confirm the result of PD measurements. All the failures were located in a line-end coil at the exit from the core slot.

한중콘크리트의 현장 표면단열 양생공법 시공사례 연구 (Field Application of Surface Insulation Curing Method to Cold Weather Concreting)

  • 김종백;임춘근;한민철;김성수;한천구
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2005년도 추계 학술논문 발표대회
    • /
    • pp.25-28
    • /
    • 2005
  • This study investigates the field application of surface insulation curing method, which combined double layer bubble sheet(DBS) and thick-curing-material(TCM) for cold weather concreting. According to the test, deck slab, curing only upper section with DBS and TCM, does not make big different temperature history with that, curing both upper and bottom section during daily average temperature 6.5t. It is concluded that combination of DBS and TCM in only upper section can be safely cured in early period of time during cold water concreting. The field test was carried out with this favourable data. The upper deck slab was insulated by combination of DBS and TCM, and the construction was surrounded by tent. in order to protect from outside wind. The test result shows that the lowest temperature of deck slab indicated 6$ ^{circ}C $. It demonstrated that this curing method can resist early frost and save construction cost in the side of management and saving labor cost, compared with previous method. In addition, the column specimen, combined both form and bubble board, exhibited favorable temperature history, due to internal hydration heat insulation effect.

  • PDF

건축물의 창틀과 벽체 사이 열교 차단을 위한 단열공법 개발 (Development on Thermal Bridge Barrier Between Window Frame and Wall)

  • 박철용;김웅회;이상희
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2018년도 추계 학술논문 발표대회
    • /
    • pp.10-11
    • /
    • 2018
  • Internal Insulation system is applied to the most apartment building in Korea. However due to the importance of building energy enhanced the interest of the exernal insulation system. The extermal insulation system has better thermal performance because the thermal bridge through the structure are rarely formed. But the thermal bridge around the window decrease the thermal performance of the envelope system. Therefore the technology for reducing the thermal bridge around window improves energy efficiency of the building. In order to this it is necessary to minimize the thermal bridge around window of building. In this study it is aimed to minimize the thermal bridge around the window of building. It was confirmed that the use of thermal bridge barrier imporved the heat transfer rate by 64% or more and the condensation reduction phenomenon by 42% or more compared with the exist technology. These thermal bridge barrier will be used as the main technology to improve the energy efficiency of building.

  • PDF

고압전동기 모델 코일의 절연상태 분석 (Analysis of Insulation Condition in High Voltage Motor Model Coils)

  • 김희동;공태식;김병래
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1612-1614
    • /
    • 2003
  • 80pF capacitive couplers were connected to six 6.6kV motor model coil terminals. The voltage applied to the coils were 3.81kv, 4.76 kV and 6.6kV, respectively. These stator coils have various types of artificial insulation defects such as large voids, semi-conductive coating damage and strand insulation fault. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in PD were measured with a conventional digital PD detector. Most of the defect mechanism of large motor stator winding can be associated with PD patterns such as internal and slot discharges. PD patterns coincide with PDD and TGA. These instruments have an input bandwidth of 40-400kHz and 0.1-350MHz. Surge testing detects faults in inter-turn winding of high voltage motor model coils.

  • PDF

Cost Effective Design of High Voltage Impulse Generator and Modeling in Matlab

  • Javid, Zahid;Li, Ke-Jun;Sun, Kaiqi;Unbreen, Arooj
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권3호
    • /
    • pp.1346-1354
    • /
    • 2018
  • Quality of the power system depends upon the reliability of its components such as transformer, transmission lines, insulators, circuit breakers and isolators. The transient voltage due to internal or external reasons may affect the insulation level of the components. The insulation level of these components must be tested against these conditions. Different studies, testing of different electrical components against high voltage impulses and different industrial applications rely on the international manufactures for pulsed power generation and testing, that is quite expensive and large in size. In this paper a model of impulse voltage generator with capacitive load of pin type insulator is studied by simulation method and by an experimental setup. A ten stage high voltage impulse generator (HVIG) is designed and implemented for different applications. In this proposed model, the cost has been reduced by using small and cheap capacitors as an alternative for large and expensive ones while achieving the same effectiveness. Effect of the distributed capacitance in each stage is analyzed to prove the effectiveness of the model. Different values of front and tail resistances have been used to get IEC standard waveforms. Results reveal the effectiveness at reduced cost of the proposed model.

이중버블시트의 포설방법에 따른 콘크리트의 온도이력특성 (Temperature History of Concrete According to the Covering Method of Double Layer Bubble Sheet)

  • 백대현;손호정;홍석민;한민철;한천구
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2010년도 춘계 학술논문 발표대회 1부
    • /
    • pp.71-72
    • /
    • 2010
  • The study is compared temperature history and strength of concrete followed by covering method of insulation curing of cold weather concrete with double bubble sheet. The results were as follows. First of all, in temperature history of concrete, the internal temperature of concrete fell down to $0^{\circ}C$ before/after 60 hours, having nothing to do with covering method. The study could see that, when sheet was isolated, it fell down to low temperature quickly in early curing. When the study measured compressive strength of core specimen, there were no large differences among placing methods. However, compressive strength fell down in all ages when sheet was isolated.

  • PDF

Epoxy 복합체의 내부 보이드에 따른 부분방전특성 (Partial Discharge Characteristics of Epoxy Composite due to Internal Void)

  • 김탁용;신종열;이준환;이덕진;홍진웅
    • 한국컴퓨터산업교육학회:학술대회논문집
    • /
    • 한국컴퓨터산업교육학회 2003년도 제4회 종합학술대회 논문집
    • /
    • pp.55-58
    • /
    • 2003
  • Stability of inside power equipments are required for electron equipment in order to operate those safely. Also, the power circuits for these have been developing, but research of dielectric strength of power supply is insufficient. In this paper, for test insulation condition variation by void it is tested insulation characteristics variation, using $\phi-q-n$ distribution variation in partial discharge test.

  • PDF

수력발전기 고정자 권선의 운전중 부분방전 특성 (Properties of On-Line Partial Discharge in Hydrogenerator Stator Windings)

  • 김병한;김희동
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제55권4호
    • /
    • pp.172-177
    • /
    • 2006
  • During normal machine operation, partial discharge(PD) tests were performed with partial discharge analyzer(PDA) in two hydrogenerators. Six cable couplers were installed in circuit ring bus and endwinding of three phases. PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude$(Q_m)$ were very low in hydrogenerator #1 and #2, respectively. The trend analyses of NQN and $Q_m$ value are available for monitoring of the insulation condition in hydrogenerator stator windings. The insulation condition of stator winding can be assessed. Discharge at conductor surface was discovered in B phase(C2 coupler) of hydrogenerator #1. Internal discharges were generated in A and C phases(C2 coupler) of hydrogenerator #1 and in A, Band C phases(C1 and C2 couplers) of hydrogenerator #2. Slot discharges occurred in A, Band C phases(C1 coupler) of hydrogenerator #1. The stator windings of two hydrogenerators were in good condition.