• 제목/요약/키워드: Interconnection Transformer

검색결과 12건 처리시간 0.025초

분산전원 연계 계통에서의 과전류계전기 오동작에 관한 연구 (A Study on the Over Current Relay Misoperation in Power System with Distributed Generations)

  • 박종일;이계병;박창현
    • 전기학회논문지
    • /
    • 제67권12호
    • /
    • pp.1705-1710
    • /
    • 2018
  • This paper deals with an analysis of the causes of over current relay(OCR) misoperation in power system with distributed generations(DG). In general, Y-D and Y-Y-D transformer connections are used for grid interconnection of DG. According to the interconnection guideline, the neutral point on Y side should be grounded. However, these transformer connections can lead to OCR misoperation as well as over current ground relay(OCGR) misoperation. Several researches have addressed the OCGR misoperation due to the interaction between transformer connections and zero-sequence voltage of distribution system. Recently, a misoperation of OCR at the point of DG interconnection to the utility system has been also reported. With increasing the interconnections of DG, such OCR as well as OCGR misoperations are expected to increase. In this paper, PSCAD/EMTDC modeling including DG interconnection transformer was performed and various case studies was carried out for identifying the cause of OCR misoperation.

지능형 보호기기 적용 태양광 인버터 성능시험 (Performance Test of an Integrated Electronic Protection Device Based Photovoltaic Inverter)

  • 김응상;김슬기;전진홍;안종보
    • 전기학회논문지
    • /
    • 제56권10호
    • /
    • pp.1744-1750
    • /
    • 2007
  • This paper addresses grid interconnection tests of a 3kW transformer-less photovoltaic (PV) inverter to verify the effectiveness of the PV inverter and promote its wide use. The 3kW transformer-less PV inverter, which was equipped with intelligent protection and control system, was manufactured. A hardware test bed was constructed for performance tests of the PV inverter. Control performance and grid protection tests were carried out using the test bed. Test results verify the performance of the power control and grid protection functions of the developed transformer-less PV inverter.

과전압에 의한 변압기 철공진 분석 및 방지대책 (Analysis for the Ferroresonance on the Transformer by Overvoltage and Prevention Measures)

  • 윤동현;신동열;차한주
    • 전기학회논문지
    • /
    • 제64권11호
    • /
    • pp.1543-1550
    • /
    • 2015
  • Ferroresonance is a non-linear vibrational phenomenon that is generated by the electrical interaction of the inductance component with the capacitor component of a certain capacitance as the device of the inductance component such as a transformer is saturated due to the degradation, the waveform distortion of current and voltage, and the oscillation of overcurrent and overvoltage in a system. Recently, ferroresonance was generated from the waveform distortion of current and voltage, or the overvoltage or undervoltage phenomenon caused by the nature of an electrical power system and design technology of the transformer in the three phase transformer system. Hence, in general, ferroresonance analyzed by converting to the LC equivalent circuit. However, in general, the aforementioned analytical method only applies to the resonance phenomenon that is generated by the interaction of the capacitance of bussbar and grounding, and switching as the capacitor component with PT and the transformer as the inductance component in a system. Subsequently, the condition where ferroresonance was generated since overvoltage was supplied as line voltage to the phase voltage and thus the iron core is saturated due to the interconnection between grounded and ungrounded systems could not be analyzed when single phase PT was connected in a ${\Delta}$/Y connection system. In this study, voltage swell in the configuration of grounded circuit of a step-up transformer with the ${\Delta}-{\Delta}$ connection linked to PT for control power and the ferroresonance generated by overvoltage when the line voltage of the ${\Delta}-{\Delta}$ connection was connected to the phase voltage of the grounded Y-Y connection were analyzed using PSCAD / EMTDC through the failure case of the transformer caused by ferroresonance in the system with the ${\Delta}-{\Delta}$/Y-Y connection, and subsequently, the preventive measure of ferroresonance was proposed.

분산전원 연계선로에서 지락고장시 중성선의 과전류 해석 및 보호계전기의 새로운 알고리즘 (An Overcurrent Analysis in Neutral Line and Algorithm to Prevent Malfunction of Relay in Distributed Generations)

  • 신동열;김동명;차한주
    • 전기학회논문지
    • /
    • 제58권10호
    • /
    • pp.1916-1922
    • /
    • 2009
  • Introducing distributed generators(DGs) to utility distribution system can cause malfunction of relay on the grid when ground faults or severe load unbalances are occurred on the system. Because DGs interconnected to the grid can contribute fault currents and make bidirectional power flows on the system, fault currents from DGs can cause an interference of relay operation. A directional over current relay(DOCR) can determine the direction of power flow whether a fault occurs at the source side or load side through detecting the phases of voltage and current simultaneously. However, it is identified in this paper that the contributed fault current(Ifdg) from the ground source when was occurred to contribute single-line-to-ground(SLG) fault current, has various phases according to the distances from the ground source. It means that the directionality of Ifdg may not be determined by simply detecting the phases of voltage and current in some fault conditions. The magnitude of Ifdg can be estimated approximately as high as 3 times of a phase current and its maximum is up to 2,000 A depending on the capacity of generation facilities. In order to prevent malfunction of relay and damage of DG facilities from the contribution of ground fault currents, Ifdg should be limited within a proper range. Installation of neutral ground reactor (NGR) at a primary neutral of interconnection transformer was suggested in the paper. Capacity of the proposed NGR can be adjusted easily by controlling taps of the NGR. An algorithm for unidirectional relay was also proposed to prevent the malfunction of relay due to the fault current, Ifdg. By the algorithm, it is possible to determine the directionality of fault from measuring only the magnitude of fault current. It also implies that the directionality of fault can be detected by unidirectional relay without replacement of relay with the bidirectional relay.

태양광전원이 연계된 고압배전선로의 보호협조 평가 방안에 관한 연구 (Evaluation Method for Protection Coordination of PV Systems Interconnected with Primary Feeders)

  • 김병기;김소희;유경상;노대석
    • 한국융합학회논문지
    • /
    • 제2권4호
    • /
    • pp.29-37
    • /
    • 2011
  • 종래의 배전계통에 있어서의 전력조류는 변전소에서 선로말단을 향한 단 방향이었지만, 신에너지전원(분산전원)이 연계된 배전계통의 경우에는 그 출력용량의 여부에 따라 양방향의 전력조류가 발생할 가능성이 있어, 계통운용상 여러 가지의 문제점이 야기될 수 있다. 분산전원은 대규모전원의 보완적 역할과 배전선로 상의 국부적 부하 감당 역할을 부과하여 그의 적극적 활용을 꾀하기 위해서는, 분산전원으로부터 배전계통에 전력을 공급하는 역 조류의 기능을 허용할 수 있는 양방향 보호협조방식의 체제를 확립할 필요가 있다. 따라서 본 연구에서는 분산전원 연계에 따른 보호협조 기본 방안과 부하절체 운전에 따른 보호협조 방안, 변압기결선에 따른 보호협조 방안 등에 대한 알고리즘을 제시하였다. 또한, 이론적인 계산법(대칭좌표법)과 MATLAB/SIMULINK에 의하여 실 계통에서의 양방향 보호협조에 관련된 문제점을 분석하고, 해결방안을 제시하였다.

분산전원 연계선로에서 보호계전기의 상전류 오차보정 알고리즘 개발 (The Development of an Algorithm for the Correction of Errors in the Phase Current of the Protective Relay on Distribution System Interconnected with Distributed Generations)

  • 신동열;윤동현;차한주
    • 전기학회논문지
    • /
    • 제62권11호
    • /
    • pp.1604-1609
    • /
    • 2013
  • When the ground fault on the power side occurs on distribution system interconnected with distributed generations, the abnormal current is generated in the neutral conductor by the connection type and the iron core structure of transformers for the interconnection of distributed power supplies due to the unbalanced voltage of the system, and subsequently the false operation of the protective relay on the load side occurs. Herein, this paper proposes the method to correct errors in the phase current to prevent the false operation of the protective relay by applying p-q theory and presents the simulation result of the error correction algorithm using PSCAD/EMTDC.

Research on Developing a Conversational AI Callbot Solution for Medical Counselling

  • Won Ro LEE;Jeong Hyon CHOI;Min Soo KANG
    • 한국인공지능학회지
    • /
    • 제11권4호
    • /
    • pp.9-13
    • /
    • 2023
  • In this study, we explored the potential of integrating interactive AI callbot technology into the medical consultation domain as part of a broader service development initiative. Aimed at enhancing patient satisfaction, the AI callbot was designed to efficiently address queries from hospitals' primary users, especially the elderly and those using phone services. By incorporating an AI-driven callbot into the hospital's customer service center, routine tasks such as appointment modifications and cancellations were efficiently managed by the AI Callbot Agent. On the other hand, tasks requiring more detailed attention or specialization were addressed by Human Agents, ensuring a balanced and collaborative approach. The deep learning model for voice recognition for this study was based on the Transformer model and fine-tuned to fit the medical field using a pre-trained model. Existing recording files were converted into learning data to perform SSL(self-supervised learning) Model was implemented. The ANN (Artificial neural network) neural network model was used to analyze voice signals and interpret them as text, and after actual application, the intent was enriched through reinforcement learning to continuously improve accuracy. In the case of TTS(Text To Speech), the Transformer model was applied to Text Analysis, Acoustic model, and Vocoder, and Google's Natural Language API was applied to recognize intent. As the research progresses, there are challenges to solve, such as interconnection issues between various EMR providers, problems with doctor's time slots, problems with two or more hospital appointments, and problems with patient use. However, there are specialized problems that are easy to make reservations. Implementation of the callbot service in hospitals appears to be applicable immediately.

태양광발전이 연계된 배전계통의 보호기기 오동작에 대한 최적 운용방안에 관한 연구 (A Study on the Optimal Method for Mal-function of Re-closer at the Distribution Feeders Interconnected with PV Systems)

  • 김찬혁;박현석;노대석;신창훈;윤기갑
    • 전기학회논문지
    • /
    • 제58권8호
    • /
    • pp.1512-1518
    • /
    • 2009
  • Recently, new dispersed power sources such as photovoltaics, wind power, fuel cell etc. are energetically interconnected and operated in the distribution systems, as one of the national projects for alternative energy. This paper deals with the optimal countermeasures for the mal-function of protective devices at primary feeder in distribution systems when new power sources like photovoltaic (PV) systems are interconnected, based on the symmetrical components of short circuit studies. When new power sources are considered to be interconnected to distribution systems, bi-directional power flow and interconnection transformer connection of new power sources may cause the operation problems of protective devices (mainly re-closer), since new power sources can change typical characteristics of distribution systems. Therefore, this paper shows an analysis skill of the mal-functional mechanism of protective relay and proposes the optimal solution for the mal-function problem using the symmetrical components of fault analysis. And, this paper also shows the effectiveness of proposed method by the simulation at the field distribution systems.

Application of SFCL on Bus Tie for Parallel Operation of Power Main Transformers in a Fuel Cell Power Systems

  • Chai, Hui-Seok;Kang, Byoung-Wook;Kim, Jin-Seok;Kim, Jae-Chul
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권6호
    • /
    • pp.2256-2261
    • /
    • 2015
  • In the power plant using high temperature fuel cells such as Molten Carbonate Fuel Cell(MCFC), and Solid Oxide Fuel Cell(SOFC), the generated electric power per area of power generation facilities is much higher than any other renewable energy sources. - High temperature fuel cell systems are capable of operating at MW rated power output. - It also has a feature that is short for length of the line for connecting the interior of the generation facilities. In normal condition, these points are advantages for voltage drops or power losses. However, in abnormal condition such as fault occurrence in electrical system, the fault currents are increased, because of the small impedance of the short length of power cable. Commonly, to minimize the thermal-mechanical stresses on the stack and increase the systems reliability, we divided the power plant configuration to several banks for parallel operation. However, when a fault occurs in the parallel operation system of power main transformer, the fault currents might exceed the interruption capacity of protective devices. In fact, although the internal voltage level of the fuel cell power plant is the voltage level of distribution systems, we should install the circuit breakers for transmission systems due to fault current. To resolve these problems, the SFCL has been studied as one of the noticeable devices. Therefore, we analyzed the effect of application of the SFCL on bus tie in a fuel cell power plants system using PSCAD/EMTDC.

STATCOM과 조상설비를 이용한 풍력단지가 연계된 전력계통의 전압제어 (Voltage Control of Power System Connected to a Wind Farm by Using STATCOM and Reactive Power Compensators)

  • 서규석;박지호
    • 한국산학기술학회논문지
    • /
    • 제16권4호
    • /
    • pp.2737-2743
    • /
    • 2015
  • 풍력발전은 풍력단지가 전력계통과 접속되는 모선의 전압을 유지 또는 제어하기 위한 충분한 무효전력을 공급할 수 있어야 한다. 하지만 풍력단지와 계통 접속점(POI - Point of Interconnection) 모선을 연결하는 선로의 무효전력 손실 때문에 풍력터빈의 무효전력공급은 접속점의 전압을 제어하기에는 불충분하다. 이 문제는 접속점에 STATCOM(Static Synchronous Compensator)과 같은 부수적인 무효전력 보상장치를 설치하여 해결할 수 있다. 본 논문에서 제시하는 STATCOM과 Switched-Shunt, 탭변환 변압기와 같은 기존의 무효전력 보상장치의 협조제어를 사용하면 더욱 효과적으로 접속점 모선의 전압을 제어할 수 있다. 본 논문에서 제시한 방법을 이용하여 초기부하에 대하여 임의의 부하 변동률을 가지는 모의 시스템에 적용한 결과 접속점 모선의 전압강하는 60%이상 개선되었고 부하 모선의 전압은 정격전압의 95%이상을 유지하였다.