A Study on the Electrical Diagnostic Methods In GIS (GIS에 있어서 전기적 절연진단법에 대한 연구[1])

  • Choi, Jae-Gu;Kim, Young-Bae;Kim, Ik-Soo;Lee, Hyeong-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1998.11c
    • /
    • pp.904-906
    • /
    • 1998
  • PD pulses have about one nanosecond rise time in the $SF_6$ gas insulation. These pulses propagate in the apparatus to PD sensors in the form of the voltage oscillation, high frequency current and the electromagnetic radiation. In this paper, we investigated the characteristics of two types of PD sensors, by putting high frequency signals in the form of sine waves and pulse into the test apparatus in air. Also, we measured PD quantity from the needle electrode and the sensitivity of the sensors. We found that PD of 70pC could be detected with this method and the study in $SF_6$ gas should be carried out for application to $SF_6$ GIS.

  • PDF

On-line Insulation Diagnostic by PD Monitoring Field Practical of UHF Technique for On-line PD Monitoring (UHF 기술을 이용한 온라인 부분방전 모니터링)

  • Oh, Yong;Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.2
    • /
    • pp.176-180
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers is designed, which has been installed inside the oil tank of transformer in a substation by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

Field Test of On-line Monitoring System for Oil-filled Power Transformers (대용량 유입변압기의 온라인 진단시스템 적용연구)

  • Lee, Chang-R.;Kim, Yong-H.;Kim, Nam-H.;Kim, Jung-H.;Yoon, Ja-H.;Nam, Keuk-C.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1644-1646
    • /
    • 2003
  • This paper presents recent studies on the on-line insulation monitoring and diagnostic systems for transformers developed by HHI. Sufficiently high sensitivity and accuracy for practical use were achieved for the system, combined with communication networks to provide an on-line remote monitoring system. Several alarm criteria are formulated to enable a superimposed monitoring system to perform decisive action. The reasons for monitoring the condition and maintaining the health of electrical apparatus were discussed. The experience at the fields and the criteria for the judgment are also discussed in detail.

  • PDF

An Amendment of the VLF tanδ Criteria to Improve the Diagnostic Accuracy of the XLPE-insulated Power Cables (XLPE 절연케이블의 열화진단 정확도 향상을 위한 VLF tanδ 판정기준 개선)

  • Lee, Jae-Bong;Jung, Yeon-Ha
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.9
    • /
    • pp.1644-1651
    • /
    • 2010
  • VLF $tan{\delta}$ diagnosis technology is introduced in IEEE Std 400 and proposed as evaluation criterion in an effective way of detecting water tree which mainly causes the failure of XLPE insulated cables. In order to inspect the accuracy of the VLF $tan{\delta}$ method for XLPE insulated power cables in Korean distribution system, diagnosis for 41 cables which were being serviced in the fields has been carried out and they were removed for AC breakdown voltage test after. Regarding the 41 cables, it was hard to confirm any relation between the VLF $tan{\delta}$ values and AC breakdown voltages and also water tree in the insulation was not detected. However, the other cables were failed several days after the diagnosis of the 41 cables. Water trees were found and their VLF $tan{\delta}$ values were also much higher than the criterion of IEEE standard. It has been ascertained that we need to change the IEEE criteria in order to improve the accuracy of detecting water trees by additional analyzing of field examples of failure and case studies from overseas countries and therefore amended VLF $tan{\delta}$ test voltage and evaluation criteria have been proposed.

UHF Narrow Band Type Partial Discharge Diagnosis Method for the Internal Insulation Performance Verification of the Gas Insulated Switchgear (가스절연 개폐장치의 내부절연 성능검증을 위한 UHF 협대역 부분방전 진단법)

  • Song Won-Pyo;Kim Jung-Bae;Kim Min-So;Jung Jae-Ryong;Park Seung-Jae;Ko Heui-Suk
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.9
    • /
    • pp.414-420
    • /
    • 2005
  • A method for partial discharge diagnosis based on UHF narrow band type for GIS has been developed and calibrated. In generally, PD cannot be directly measured under on-line condition, but we can indirectly measure the electromagnetic wave made by PD using the high-frequency antenna. Compared with VHF band, electromagnetic waves of UHF band have a low influence for external noise in high-voltage substation. Therefore, we can detect the real abnormality with several pC in GIS using UHF narrow-band type method. For the case of no internal VHF sensor for GIS of the domestic substation, it has applied to use the external UHF sensor attached in spacer in GIS of existing substation. In this paper, we firstly described the technique of partial discharge measurement using frequency analysis and phase analysis in UHF band. Secondly, we presented the results of sensitivity test, the relationship of dBm-pC and diagnosis result of the cause of PD source by phase analysis. And then, we report the diagnosis result of partial discharge on the real GIS in domestic substation. These results make above method applicable for measurement of quantity and cause of PD for real operation GIS in high-voltage substation.