• 제목/요약/키워드: Insulation diagnosis

검색결과 266건 처리시간 0.027초

CV케이블의 부분방전 신호를 통한 열화과정의 정량적 진단 (Normalization Diagnosis of Aging Process on Partial Discharge Signals of CV Cable)

  • 소순열;임장섭;김진사;이준웅;김태성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1997년도 추계학술대회 논문집
    • /
    • pp.451-455
    • /
    • 1997
  • The partial discharge has been blown as the chief breakdown of power equipments. The analysis and the recognition is much difficult because the partial discharge signal is very small and has complex aging pattern. Recently, insulation aging diagnosis based on pattern of phase(Ф), partial discharge magnitude(q), number(n) has been very important. Owing to depreciate the reappearance of aging progress at the electrical tree pattern and to be difficult to analyze visually, the study on partial discharge pattern is suggested to normalizing analysis method of partial discharge signals. This parer is purposed on prediction of life-time measurement of cv-cable, on decision of risk degree with normalization and real-time measurement of partial discharge signals for aging diagnosis of cv-cable. As normalizing the aging signals of electrical tree in cv-cable, it is able to confirm risk degree of insulation material with the distribution of Ф-q-n and recognize the process of aging pattern using neural network.

  • PDF

GIS 진단시스템의 평가를 위한 PD 모의 펄스발생기 개발에 관한 연구 (A Study on the Development of PD Simulation Pulse Generator for Evaluation of GIS Diagnosis System)

  • 김성주;장석훈;조국희
    • 한국안전학회지
    • /
    • 제33권2호
    • /
    • pp.21-27
    • /
    • 2018
  • The expansion and stable operation of electric power facilities are important factors with development of industrial facilities in modern society. In high-voltage equipment such as GIS, the insulation characteristics may be deterioated by environment-friendly gas adaption and miniaturization. There is also the possibility of accidents due to insulation breakdown due to the deterioration of power facilities. Therefore, it is necessary to extend the diagnosis system to continuously monitor the danger signals of these power equipment and to prevent accidents. Most of the internal defects in the GIS system are conductive particles, floating electrode defects, protrusion defects, and the like. In this case, a partial discharge phenomenon is accompanied. These partial discharge signals occur irregularly and various noise signals are included in the field, so it is difficult to evaluate the reliability in the development of the diagnostic system. In this paper, a study was made on equipment capable of generating a partial discharge simulated signal that can be adjusted in size and frequency to be applied to a diagnostic device by electromagnetic wave detection method. The PD simulated pulse generator consists of a user interface module, a high-voltage charging module, a pulse forming circuit, a voltage sensor and an embedded controller. In order to simulate the partial discharge phenomenon similar to the actual GIS, a discharge cell was designed and fabricated. The application of the prototype pulse generator to the commercialized PD diagnosis module confirmed that it can be used to evaluate the performance of the diagnostic device. It can be used for the development of GIS diagnosis system and performance verification for reliability evaluation.

신경회로망을 이용한 절연 열화진단에 관한 연구 (A Study on Insulation Degradation Diagnosis Using a Neural Network)

  • 박재준
    • 정보학연구
    • /
    • 제2권2호
    • /
    • pp.13-22
    • /
    • 1999
  • 본 논문에서, 부분방전 메카니즘을 진단하고 그리고 신경망을 도입하여 수명을 예측하기 위한 기초연구로서, 온라인상에서 자동진단을 제안했다. 제안한 방법에서 우리는 음향방출 감지시스템과 그리고 펄스 수와 펄스진폭에 의해서 정량적인 통계파라메타를 사용하였다. 통계적인 파라메타인 가령, 무게중심(G)와 방전분포 경도(C)를 이용하였고 그리고 초기단계와 중기단계에 대해서 분석하였다. 정량적인 통계파라메타들은 신경망에 의해서 학습되어졌다. 초기단계에 의해서 수명예측과 절연열화의 진단이 이루어졌다. 열화가 진행하는 동안 신경망 학습을 통한 휼륭한 진단능력이 있음이 근본적으로 드러났고, 신경망이 부분방전에 있어서 절연진단 및 수명예측을 위해서 적절하다는 것이 증명되었다.

  • PDF

모의 GIS 내부에 유전체 파티클 존재시 부분방전 진전에 따른 방사전자파의 특성 (Characteristics of Radiated Electromagnetic Waves with Partial Discharge Propagation in Model GIS Being Insulation Particle)

  • 박광서;김이국;김종환;주재현;송현직;이광식
    • 조명전기설비학회논문지
    • /
    • 제19권2호
    • /
    • pp.69-76
    • /
    • 2005
  • 본 논문에서는 모의 GIS 내부에 유전체 파티클 들을 놓아둠으로서 전하의 축적과 전계의 집중이 용이하도록 하여 부분방전을 모의하였다. 이때 부분방전 발생과 진전에 따른 방사전자파를 스펙트럼 분석기와 $EMI{\cdot}EMC$ 측정용 안테나$(30\~2000(MHz))$를 사용하여 측정$\cdot$분석하였다. 모의 GIS내부에 유전체 파티클 존재에 따른 부력방전의 검출과 방진전전 과정의 판단을 위한 절연진단의 방법으로서 본 논문에서 제안한 측정 주파수의 대역의 분리와 데이터 측정과 분석법을 이용하면 부분방전의 검출과 방전과정의 판단이 가능함을 확인하였다.

백화현상이 나타난 고압전동기 고정자권선의 절연특성 연구 (A Study on Insulation Property of White Powder Found on High Voltage Motor Stator Winding)

  • 공태식;김희동;이상길;김경열;주영호
    • 전기학회논문지
    • /
    • 제60권8호
    • /
    • pp.1627-1631
    • /
    • 2011
  • During a routine inspection of a large pump motor at power plant, white powder was found on the surface of the stator end windings. Visual inspection and high voltage insulation diagnosis was performed to determine whether this motor is available. The purpose of this paper is to understand the insulation properties of white powder found on high voltage stator and to know prevention of insulation weakness.

견인전동기 고정자 코일의 전기적 열화특성 (Properties of Electrical Performance on Stator Coil of Traction Motor by Accelerated Test)

  • 박현준;장동욱;김길동
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2003년도 추계학술대회 논문집(III)
    • /
    • pp.623-627
    • /
    • 2003
  • Aging and failure of motor insulation depend on the stresses imposed on it. The insulation life time depends on the severity of the stresses. The electrical aging by transient surge is very important to traction motor in EMU(electric multiple unit). This paper presents the insulation characteristics of stator coil by transient surge from inverter. There are several nondestructive tests available for checking the condition of motor insulation, the probable extent of aging, and the rate of which aging is taking place. So the insulation characteristics of stator coil were each analyzed by measurement of leakage current, dielectric loss($tan{\delta}$), capacitance, polarization index(PI) and partial discharge. The method of diagnosis is able to analyze the aging condition and predict the life of the traction motor in EMU.

  • PDF

수력발전기의 절연보강 전${\cdot}$후 절연상태 비교평가 (Assessment of Insulation Condition between Diagnosis and Impregnation for Hydro-Generator)

  • 변일환;이은웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 B
    • /
    • pp.1124-1126
    • /
    • 2004
  • The measurements were performed to assess the insulation deterioration condition of the stator winding of Dae-Cheong hydro-generator ${\sharp}2$ which had been in service after being constructed 1980. After repair of the stator winding insulation. we conducted insulation diagnostic tests which include resistance, polarization index(P. I). AC current, dissipation factor($Tan{\delta}$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to the previous records. On the basis of these test results. this paper tried to present the importance of insulation repair for the generator stator winding.

  • PDF

대용량 수차발전기의 절연진단과 절연보수 상관관계 평가 (Assessment of Insulation Condition between Diagnosis and Impregnation for Hydro-Generator)

  • 오봉근;정진달;이광호;김현일;곽희진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.39-41
    • /
    • 2004
  • The measurements were performed to assess the insulation deterioration condition of the stator winding of Dae-Cheong hydro-generator #2 which had been in service after being constructed 1980. After repair of the stator winding insulation, we conducted insulation diagnostic tests which include resistance, polarization index(P.I), AC current, dissipation factor($Tan\delta$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to the previous records. On the basis of these test results, this paper tried to present the importance of insulation repair for the generator stator winding.

  • PDF

전자환경 측정에 의한 방전전류 파형추정과 절연진단의 기초 연구 (A Basic Study on the Estimation of Discharge Current Waveform and the Insulation Diagnosis by the Measurement of Electromagnetic Environment)

  • 박광서;김기채;김이국;박원주;이광식
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제51권10호
    • /
    • pp.492-499
    • /
    • 2002
  • This paper presents the method for an estimation of discharge current waveform in short gap discharge by radiated electromagnetic fields. The method of current waveform estimation is to use the one antenna method (single field method) with a measured electric or magnetic field at given field point by a time domain antenna. In order to verify the availability of the estimation theory, the discharge current waveform estimation was performed by one antenna methods using the measured electric fields of Wilson & Ma and compared with experiments. In addition diagnosis technique for power equipments is able to prevent from large accidents by finding signs of tile accidents before they happen. From the results of the estimation of discharge current, we have a possibility for the application of insulation diagnosis technique for power equipments using S$F_6$ gas. From this point of view, this paper simulated discharge progress and partial discharge by using needle-plan electrodes system in S$F_6$, studied the distribution of frequency spectrum of the radiated electromagnetic waves using a biconical antenna and a spectrum analyzer. From the experimental results of this study, according to the consideration of the mutual relation between frequency spectrum of the radiated electromagnetic waves and discharge progress, it was confirmed that detecting Partial discharge and estimating discharge progress in S$F_6$ could be Possible.