• 제목/요약/키워드: Insulation Oil

검색결과 258건 처리시간 0.021초

변압기 층간 절연지의 열열화 특성 평가에 관한 연구 (The Study on Characteristics for Thermal Aging of the Layer Insulation in Transformers)

  • 이병성;송일근;김동명;박동배;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 하계학술대회 논문집
    • /
    • pp.406-409
    • /
    • 2002
  • The primary insulation system used in an oil-filled transformer is Kraft paper, wood, porcelain and, of course, oil. Modern transformers use paper that is chemically treated to improve its tensile strength properties and resistance to aging caused by immersion in oil. These insulation papers are mainly aged to thermal stress. Over the course of the insulation paper and oil's life it is exposed to high temperatures, oxygen and water. Its interaction with the steel of the tank and core plus the copper and aluminium of the windings will eventually cause the chemical properties of the oil to decay. High temperature have an effect on mechanical strength of cellulous paper using the layer insulation. We made two aging cell in which thermal aging tests of insulation papers and mineral oil are conducted. It is measured dielectric strength, number of acid, moisture, etc. of insulation paper and oil aged in the aging cells.

  • PDF

가속열화 방법에 의한 주상변압기 절연물의 열 열화 특성 평가 (The Evaluation of Thermal Aging Characteristics in Insulating Materials of the Pole Transformers)

  • 이병성;송일근;이재봉;한상옥
    • 한국전기전자재료학회논문지
    • /
    • 제16권12호
    • /
    • pp.1136-1141
    • /
    • 2003
  • The primary insulation materials used in an oil filled transformer are kraft paper, wood, porcelain and oil. Modern transformers use chemically treated paper to improve its tensile strength and resistance to aging caused by immersion in oil. But these insulation papers are mainly aged by thermal stress. Over the life time of the insulation paper and oil, it is exposed to high temperatures, oxygen and water. Its interaction with the steel of the tank and core plus the copper and aluminium of the windings will eventually cause the chemical properties of the oil to decay. High temperature have an effect on mechanical strength of cellulous paper used in the layer insulation. We made two aging cells in which insulation papers and mineral oil are conducted to test thermal properties. It is measured dielectric strength, number of acid, moisture, etc. of insulation paper and oil aged in the aging cells.

온도에 따른 액체 절연유의 전기적 특성 (Electrical Properties of Liquid Insulation as a Function of Temperature )

  • 김태희;최용성
    • 한국전기전자재료학회논문지
    • /
    • 제37권3호
    • /
    • pp.280-285
    • /
    • 2024
  • In this paper, the electrical properties of liquid insulating oil were analyzed by changing the ambient temperature change at 10℃ in-tervals from 0℃ to 30℃ through an insulation breakdown experiment in order to analyze the insulation performance of liquid in-sulating oil that varies according to temperature changes. As a result, it was confirmed through experiments that the lower the am-bient temperature, the higher the insulation breakdown voltage, depending on both the electrode shape and the electrode interval, and it was determined that the lower the ambient temperature, the higher the insulation performance of the liquid insulating oil.

Influence of Electrical Aging on Space Charge Dynamics of Oil-Impregnated Paper Insulation under AC-DC Combined Voltages

  • Wang, Yan;Li, Jian;Wu, Sicheng;Sun, Peng
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권6호
    • /
    • pp.1512-1519
    • /
    • 2013
  • Oil-impregnated paper is a major type of insulation used in oil-filled converter transformers for both traditional and new energy systems. This paper presents and analyzes the results of the experiment conducted on the electrical aging of oil-impregnated paper under AC-DC combined voltages using the pulsed electro-acoustic (PEA) technique. The formation and dynamics of space charge affected the performance of insulation material. The electrical aged oil-paper insulation was obtained through electrical aged experiments under the voltages. Based on the PEA technique, measurements were carried out when the oil-paper insulation system was subjected to different stressing and aging times. The space charge dynamics in the bulk of the oil-paper insulation system with different aging times were measured and analyzed. Characteristic parameters such as the total charge injection amount, the total charges of fast moving and slow moving, and the distortion factor of electric field were calculated and discussed. Results show that the longer electrical aging time, the more charges trapped in the bulk of aging sample. It leads to larger distortion factor of electric field in the bulk of aging samples and accelerate degradation of oil-paper insulation under AC-DC combined voltages.

가속열화 방법에 의한 주상변압기 절연물의 열열화 특성 평가 (The Evaluation of Thermal Aging Characteristics in Insulating Paper for the Use of the Pole Transformers)

  • 이병성;송일근;이재봉;박동배;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.1
    • /
    • pp.100-103
    • /
    • 2003
  • The primary insulation system used in an oil-filled transformer is kraft paper, wood, porcelain and oil. Modern transformers use paper that is chemically treated to improve its tensile strength properties and resistance to aging caused by immersion in oil. But these insulation papers are mainly aged to thermal stress. Over the course of the insulation paper and oil's life it is exposed to high temperatures, oxygen and water. Its interaction with the steel of the tank and core plus the copper and aluminium of the windings will eventually cause the chemical properties of the oil to decay. High temperature have an effect on mechanical strength of cellulous paper using the layer insulation. We made two aging cell in which thermal aging tests of insulation papers and mineral oil are conducted. It is measured dielectric strength, number of acid, moisture, etc. of insulation paper and oil aged in the aging cells.

  • PDF

유침절연 변압기에서 연속적 수분제거 유효성에 관한 연구 (Study on the Effectiveness of Continuous Water Removal in Oil Immersed Transformers)

  • 선종호;황돈하;김진수
    • 조명전기설비학회논문지
    • /
    • 제30권2호
    • /
    • pp.20-25
    • /
    • 2016
  • This paper describes the effectiveness of continuous water removal in oil immersed transformers. Insulation oil in which insulation papers were immersed were prepared for tests and water concentrations in oil with heating time were measured at five oil temperatures. Also, the tests that water dissolved in $100^{\circ}C$ oil was removed at once and continuously at $50^{\circ}C$ and $100^{\circ}C$ were performed for consideration of effective method for water removal. Test results indicated that the oils for water measurement have to be extracted at similar temperatures and water in oil has to be continuously removed at higher temperatures for more effective water management of transformers.

팔라듐이 코팅된 광섬유 격자를 이용한 절연유속의 용존 수소가스 검출 (Detection of Hydrogen Gas Dissolved in Insulation Oil Based on Palladium-coated Fiber Bragg Grating)

  • 김광택;최누리;백세종
    • 센서학회지
    • /
    • 제27권6호
    • /
    • pp.403-406
    • /
    • 2018
  • We have investigated a fiber-optic sensor for detecting the hydrogen gas dissolved in insulation oil based on a palladium (Pd)-coated fiber Bragg grating (FBG). As the palladium absorbs the hydrogen gas dissolved in the insulation oil, its volume expands and the Bragg wavelength shifts to a longer wavelength. The experimental results showed that the Bragg wavelength of FBG increased to 70 nm when the concentration of hydrogen dissolved in the insulation oil was 409 ppm.

Comparative Study of DC Breakdown and Space Charge Characteristics of Insulation Paper Impregnated with Natural Ester and Mineral Oil

  • Hao, Jian;Zou, Run-Hao;Liao, Rui-Jin;Yang, Li-Jun;Liao, Qiang;Zhu, Meng-Zhao
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권4호
    • /
    • pp.1682-1691
    • /
    • 2018
  • Natural ester is a suitable substitute for mineral oil and has been widely used in AC transformer in many countries. In order to further application of natural ester in direct current (DC) equipment, it is needed to investigate its long term insulation property under DC condition. In this paper, a thermal ageing experiment was conducted for both mineral oil-paper and natural ester-paper insulation. The DC breakdown and space charge characteristics of insulation paper impregnated with natural ester and mineral oil was compared. Results show that the resistivity of the paper immersed in natural ester and mineral oil both increase as the ageing goes on. While insulation paper impregnated with natural ester has higher resistivity and DC breakdown voltage than the paper impregnated with mineral oil. The DC breakdown voltage for the oil impregnated insulation paper being DC pre-stressing is higher than that without pre-stressing. The average DC breakdown field strength difference between the test with pre-stressing and without pre-stressing clearly shows that there is an apparent enhancement effect for the homo-charge injection on the DC breakdown.

열 열화에 따른 변압기 절연물의 절연특성 분석 (Analysis of Insulation Characteristics for Transformer Insulating Materials According to Thermal Degradation)

  • 이민구;심재명;임경범;이대동
    • 전기학회논문지
    • /
    • 제65권10호
    • /
    • pp.1688-1693
    • /
    • 2016
  • In this study shall investigate the influence upon the electrical property of transformer oil due to the heat among accelerated heat degradation experiment for a constant hour in the typical insulation oils of mineral base oil, silicon base oil and vegetable oil. In addition, the electric insulation performance of insulation materials in transformer shall be evaluated through the electric property analysis according to the heat degradation of epoxy insulation material, which has been used for electric facilities such as a molded transformer.

주상변압기 적용을 위한 친환경 식물성절연유의 절연특성 연구 (Research on Dielectric Characteristics of Environmental-Friendly Vegetable Insulation Oil for the Pole Transformer)

  • 곽동순
    • 한국안전학회지
    • /
    • 제25권6호
    • /
    • pp.81-85
    • /
    • 2010
  • In recent years, environmental concerns have been raised on the use of poorly biodegradable fluids in electrical apparatus in regions where spills from leaks and equipment failure could contaminate the surroundings. The vegetable insulation oils are highly biodegradable, have negligible effect on the environment, human health and ecosystem. Therefore, to assure their safe use in electrical power systems, it may require some processing and modification to improve some of their physical, chemical, thermal and electrical properties. This paper provides a comparative results of the electrical breakdown properties of several vegetable insulation oils and mineral oil to use as dielectric fluid in environmental-friendly pole transformer. Also, the electrical breakdown property of the Nomex and kraft insulation papers in vegetable insulation oil is examined.