• Title/Summary/Keyword: Insulation Diagnosis test

Search Result 70, Processing Time 0.032 seconds

Analysis of Insulation Characteristic for Small Hydro Generator (소수력발전기 절연특성분석)

  • Oh, Bong-Keun;Chang, Jeong-Ho;Lee, Kwang-Ho;Kang, Dong-Sik
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2008.05a
    • /
    • pp.142-145
    • /
    • 2008
  • Electrical insulation of small hydro generator stator winding is one of the most important parts in generator facilities. Some stator winding insulation problems can be identified through analysis of insulation diagnostic test. So, Diagnosis of stator winding insulation is an important measure of ensuring the safe operation and extending the remaining life of small hydro generator. This paper presents case studies of insulation failure in generator stator windings and the results of insulation diagnostic test for small hydro generator stator windings. Especially, Conducting the insulation diagnostic test before the generator installed in site is very important process to keep the good insulation condition in service.

  • PDF

Power Cable Insulation Diagnosis Using Low Frequency Power (저주파수 전원을 이용한 전력케이블 절연평가에 관한 연구)

  • Kim, Sung-Min;Lee, Sang-Hun;Jang, Jae-Yel
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1603-1603
    • /
    • 2011
  • As time goes by these cables make a insulation problems, and ask for a preventive diagnosis method. Cable has very high electrostatic capacity and insulation defects mainly caused by water-tree(WT). Dissipation factor test is very useful for detecting WT but it needs huge power supply. In this paper we presented a cable insulation diagnosis by dissipation factor using low frequency power supply.

  • PDF

Example study of the insulation characteristic change according to the dryness condition in high voltage motor stator winding (고압전동기 고정자권선의 건조상태에 따른 절연특성 변화사례 고찰)

  • Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2056-2057
    • /
    • 2008
  • This paper is purpose to understand the insulation properties of the high voltage motor stator winding according to the different dryness conditions. we carried out the three times insulation diagnosis test for the same motor stator winding. the first test object is the contaminated winding, second is the washed-out, and natural dried during the 24 hours, and the last is the heating dried in 110$^{\circ}C$ during the 48 hours. the insulation diagnosis tests are consist of the megger, the polarization index, the AC current test, the dissipation factor test and the partial discharge test, we analyzed and made a comparison of the three cases test result.

  • PDF

A technology State of Life Estimation and Insulation Diagnosis for High Voltage Rotating Machine (고압회전기 절연진단 및 수명평가 기술현황)

  • Choi, Young-Chan;Wang, Jong-Bae;Kim, Ki-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.10a
    • /
    • pp.31-35
    • /
    • 2000
  • We worried about the technology difference between our company and the advanced company at present motor market and are asked to set up the independent coil insulation system to accumulate insulation technology data. And to export our products at oversee market, we are asked to the evaluation of insulation performance to show our product excellence. In this study, we evaluated the insulation system of our motor, and studied the insulation diagnosis technology systematically to do site diagnosis. We are now accumulating the measured data. And also to reduce the initial insulation failure, we performed the insulation characteristic test and acquired the data to evaluate the initial soundness. We are doing the improvement of the insulation system. And also these data were used to new product development as very useful data, also will be used in the insulation deterioration diagnosis to estimate the remained life time which is very important data for the maintenance management. As the result, we were able to get our product reliability.

  • PDF

Analytic Issues for Trend Management on Insulation Diagnositic for High Voltage Motors (고압전동기 절연진단 결과 추이관리의 문제점 분석)

  • Lee, Young-Jun;Ju, Young-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2052-2053
    • /
    • 2008
  • High voltage motors are the core equipment of electric generation facilities and need to guarantee stable operation. Therefore, keeping healthy state is of importance by means of insulation diagnosis periodically. However, if the diagnosis went through in the different circumstances such as temperature, humidity, and impedance applied to the test equipment, the trend analysis have no significance. This paper presents the experimental results supporting the importance of keeping the same conditions under insulation diagnosis.

  • PDF

On-Line Insulation Diagnosis Techniques for Stator Winding of Rotating Machines (회전기 고정자 권선에서의 운전 중 절연열화 진단기법)

  • 윤대희;황돈하;신병철;김용주;이광식
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.89-93
    • /
    • 2000
  • Recently many research activities on the diagnosis of stator winding insulation of large rotating machines have been reported. Capacitive couplers are widely used as sensors for on-line partial discharge (PD) measurement of high voltage rotating machines. This paper presents laboratory test to compare Stator Slot Coupler (SSC), Resistance Temperature Detector (RTD), 80 [pF] coupler and 500 [pF] coupler for on-line PD measurement of rotating machines. And a novel on-line monitoring system for an insulation diagnosis is proposed.

  • PDF

A Study on the Water Absorption Diagnosis Method through Capacitance Measurement for Generator Stator Windings (발전기 고정자 권선의 정전용량 측정을 통한 흡습 진단 방법에 관한 연구)

  • Kim, Hee-Soo;Bae, Yong-Chae;Kee, Chang-Doo
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.23 no.11 s.188
    • /
    • pp.50-57
    • /
    • 2006
  • The water leak in water-cooled generator stator windings can generate the serious accidents such as insulation breakdown and it brings a generator to the unexpected sudden outage. Accordingly, it is important to diagnose the water absorption of them for the effective operation of power plant. Especially, the capacitance value which is measured for diagnosis is very small so the special diagnosis methods like stochastic theory are needed. KEPRI developed the water absorption test equipment and diagnosis technology for them. The developed diagnosis technology is applied to the real system and the results of water absorption test for stator windings are agreed to them of water leak test.

A study of Insulation Diagnosis for Large-Capacity Mold Transformer (대용량 몰드변압기 정밀절연진단 결과 고찰)

  • Lee, Eun-Chun;Kim, Jae-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.10
    • /
    • pp.75-81
    • /
    • 2014
  • When the large-capacity Mold type Transformer was passed through rain, after it was dried and it's parts were changed, Insulation Diagnosis was made to evaluate the condition of it and decide to recharge. Using the evaluation of Insulation Diagnosis, the urgent decision-making for recharge made blackout time minimum. In this study, it was considered that Insulation Diagnosis for the large-capacity Mold type Transformer is applied to decision-making for reuse of high voltage electric power equipment by analysis of the case study.

Fault Prediction & Reliability Estimation of the Traction Motor by the Complex Accelerating Degradation and Condition Diagnosis (견인전동기의 복합가속열화 상태진단에 의한 고장예측 및 신뢰성 평가)

  • 왕종배;김명룡
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.07a
    • /
    • pp.763-766
    • /
    • 2000
  • In this paper, stator form-winding sample coils based on silicone resin and polyimide were made for fault prediction and reliability estimation on the 200 Class insulation system of traction motors. The complex accelerative degradation was performed by periods during 10 cycles, which was composed of thermal stress, fast rising surge voltage, vibration, water immersion and overvoltage applying. After aging of 10 cycles, condition diagnosis test such as insulation resistance & polarization index, capacitance & dielectric loss and partial discharge properties were investigated in the temperature range of 20∼160$^{\circ}C$. Relationship among condition diagnosis test was analyzed to find an dominative degradation factor and an insulation state at end-life point.

  • PDF

Field Application of Power Cable Diagnosis System (전력케이블 열화진단기법의 현장적용)

  • Kim, Ju-Yong;Han, Jae-Hong;Song, Il-Keun;Kim, Sang-Jun;Lee, Jae-Bong;Oh, Jae-Hyung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.05c
    • /
    • pp.148-151
    • /
    • 2002
  • In order to prevent the failures of underground distribution power cables we need to measure insulation condition in the field. Until now we used DC high voltage as a power source for the cable diagnosis but it was not proper method to the XLPE insulation cables because DC high voltage can affect sound insulation and can't diagnose exactly insulation degradation. For these reasons we imported isothermal relaxation current measurement system called by KDA-1 from germany but it's reliability did not proved in our URD cables. DC voltage decay measurement system was developed by domestic company but they don't have field experience. In this paper we tried to prove reliability of these two systems in the field. Through the field diagnosis and Ac breakdown test the two systems showed similar results.

  • PDF