The Study of Economical Efficiency for the Ice Storage System of more Energy Consumption Building (에너지 다소비형 건물 축냉 시스템의 경제성에 관한 연구)

  • Lee, Je-Myo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.10
    • /
    • pp.733-738
    • /
    • 2012
  • It is important issue to reduce the electric energy to save the operating cost of HVAC system. Even if electrical energy is the clean energy, it is difficult and takes high cost for storage of electricity. These cause the high peak load of electric energy for HVAC in summer season. In korea, government impose the electric charge with several grade for the purpose of cut-off the peak load of electricity. Government has a policy to support to design and install the heat/ice storage system using midnight electricity. In this study, analysis of cooling load and operating characteristics for ice storage system are performed. And, also economical efficiency is compared between ordinary charge system of electricity and midnight rate charge of electricity. The systematic and economical supports are needed for expansion of usage of energy saving equipments.

Comparative analysis of the minimum capacity of an ice-on-coil thermal storage system for various operation strategies (관외 빙착형 빙축열시스템의 운전방식에 따른 최소용량 비교)

  • 이대영;정성훈;강병하
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.3
    • /
    • pp.401-413
    • /
    • 1999
  • An ice storage cooling facility with cooling capacity of 150㎾ has been constructed for the purpose of developing optimal design and control strategy for an ice storage system. As the first step to this purpose, a computer program has been developed to simulate the operation of the ice storage system and examined precisely by comparing the results with those measured from the test facility. With the simulation program verified from the comparison, a design procedure has been developed to determine the minimum capacity required for each operation strategy available commercially. It is shown that the minimum sizes of the chiller and the storage tank are strongly dependent on the control strategy, i.e., chiller priority or storage priority, but less affected by the arrangement method, i.e., chiller upstream or chiller downstream.

  • PDF

Control strategy for economic operation of an ice-storage system considering cooling load variation (냉방부하 변동을 고려한 빙축열시스템의 경제적 운전방식)

  • 정성훈;이대영;강병하;김우승
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.2
    • /
    • pp.140-149
    • /
    • 2000
  • A comparative analysis was peformed on the operation cost at partial loads between ice storage systems with the two conventional control strategies, i.e., storage priority and chiller priority. The storage priority control is shown to be more economic for small cooling loads, while the chiller priority control is superior when the cooling load is as large as the design value. Based on this finding, a new control strategy is devised for an ice-storage system to minimize the operation cost at any cooling load. The new control strategy is found to be comparable to the chiller priority for large cooling loads, while it is more economic for small loads compared to the conventional control strategies. The practicality of the new control strategy is also confirmed through a performance test applying the new control strategy to an existing ice-storage system.

  • PDF

An Estimation of Cooling Load for Control of Ice Storage System (빙축열 시스템의 제어를 위한 냉방부하 예측)

  • Yoo, Seong-Yeon;Han, Seung-Ho;No, Kwan-Jong;Lee, Je-Myo;Kang, Tae-Seok
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.205-210
    • /
    • 2005
  • Ice storage system stores cold energy using ice, which is used for cooling on next day. Ice storage system is the effective cooling system that uses cheep electric energy during a night, and also suppresses the peak load of electricity. In this study, the normalized temperature, relative humidity and specific humidity are analyzed using the weather data for past five years in order to estimate the cooling load for the control of ice storage system. The calculated cooling loads show fairly good agreement with the measured data of model hospital, especially at the outdoor design temperature of $25^{\circ}C$.

  • PDF

Heat Transfer Analysis of a Thermal Storage System using the Ice Capsule of Bar and Ring Module (봉과 링 조합형 아이스캡슐을 적용한 축열시스템의 열전달 해석)

  • Kim, Myoung-Su;Choi, Hyoung-Gwon;Byon, Sung-Kwang
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.32 no.2
    • /
    • pp.268-275
    • /
    • 2008
  • The shape and array of ice capsules are very important factors in ice thermal storage system because the heat transfer rate of the system strongly depends upon them. In this paper, a new type of ice capsule composed of bar and ring module is proposed to increase the efficiency of the ice thermal storage system. To investigate the heat transfer rate of the proposed ice capsule, numerical analysis of the incompressible Navier-Stokes equations is performed to compare the proposed bar and ring system with the conventional ice capsules. It is shown that the ice capsule composed of bar and ring has a higher heat transfer rate and a low outlet temperature than the conventional ice capsules for various packing ratios and entrance velocities. Furthermore, it is found that the optimal entrance velocity exists between 0.005 m/s and 0.007 m/s from the present numerical analysis.

Effects of Refrigerant Subcooling on the Performance of indirectly Ice Thermal Storage Cooling System (축열조 간접이용 냉매 과냉각형 시스템에서 과냉도가 시스템 성능에 미치는 영향)

  • Lee, Soo-Yang;Park, Shung-Sang;Peck, Jong-Hyeon;Chung, Dong-Yeol;Park, Il-Hwan
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.979-983
    • /
    • 2009
  • This study has been conducted the possibility of the subcooling type ice storage cooling system that the stored ice used to subcool the condensed refrigerant. The experimental study was done to fine the characteristics of the cooling capacity according to the variation of the subcooling degree and the analysis for the peak shift effect of the full storage, partial storage and subcooling type ice storage system compared to the normal air conditioning system was also done. The result of the analysis was shown that the peak shift effect of this subcooling type ice storage system could be 61%.

  • PDF

The Experimental Study on Heat Transfer during Melting Process in the Low Temperature Heat Storage System(Ice on Coil Type) (Ice on Coil형 저온 잠열 축열시스템에서의 용융과정시 열전달에 관한 실험적 연구)

  • Kim, Y.K.;Kim, D.C.;Kim, I.G.;Choi, K.K.;Yim, C.S.
    • Solar Energy
    • /
    • v.19 no.1
    • /
    • pp.19-27
    • /
    • 1999
  • In this study, basic design data which were required for development of highly efficient ice storage system with low temperature latent heat were experimentally obtained. The ice storage system considered in this study was the one that has been widely used in the developed country and called the ice-on-coil type. Using the system, the ice storage performance for various design parameters which were the flow direction and the inlet temperature of the secondary fluid was tested. In addition, the clockwise variation of the heat transfer characteristics of the PCM in the ice storage tank were investigated. During the melting processes in the ice storage tank with several vertical tubes, decrease of the solid-liquid interface area, which was the heat transfer area, between the floating ice and the water made the decreasing rate of IPF less. Also, the total melting energy for the upward flow of the secondary fluid was higher than that for the downward flow during the melting process, but this trend did not appear if the initial temperature of the PCM was $4^{\circ}C$. The average ice recovery efficiency for the upward flow of the secondary fluid was higher than that for the downward flow.

  • PDF

Modelling of Thermal Discharge Performance for Ice-on-coil Type Ice-Storage Tank (관외착빙형 빙축열조의 방열성능 모델링)

  • Lee, Sang-Ryoul;Lee, Kyoung-Ho;Choi, Byoung-Youn;Han, Seong-Ho
    • Proceedings of the KSME Conference
    • /
    • 2001.06d
    • /
    • pp.280-285
    • /
    • 2001
  • This paper presents a modelling of thermal discharge performance for a static ice-on-coil ice-storage tank. Through the present study, discharging characteristics were examined with the existing results of theoretical and numerical heat transfer analyses. Also, an experiment was conducted to obtain a real set of discharge performance. The thermal effectiveness, the ratio of the actual heat transfer rate to the maximum possible heat transfer rate, decreased when the stored energy decreased during discharging period. And the effectiveness increased as the coolant flow rate through the storage increased, of which increasing rate decreased abruptly near the maximum and the minimum stored energy. An empirical correlation was obtained from the experimental and the numerical analysis data.

  • PDF

The Study on Intelligent Cooling Load Forecast of Ice-storage System (빙축열 시스템의 지능형 냉방부하예측에 관한 연구)

  • Koh, Taek-Beom
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.11
    • /
    • pp.2061-2065
    • /
    • 2008
  • In the conventional operation of ice-storage system based on operator's experience and judgement, the failure in forecast of cooling load occurs frequently due to operator's misjudgement and unskilled operation. This study presents the method of constructing self-organizing fuzzy models which forecast tomorrow temperature, humidity and cooling load periodically for economic and efficient operation of ice-storage system. To check the effectiveness and feasibility of the suggested algorithm, the actual example for forecasting temperature, humidity and cooling load of ice- storage system in KEPCO training institute, Sokcho, is examined. The computer simulation results show that the accuracy of temperature, humidity, cooling load forecast of the suggested algorithm is higher than that of the conventional methods.

A Study on Daily Cooling Load Forecast Using Fuzzy Logic (퍼지 논리를 이용한 일일 냉방부하 예측에 관한 연구)

  • 신관우;이윤섭
    • Journal of Institute of Control, Robotics and Systems
    • /
    • v.8 no.11
    • /
    • pp.948-953
    • /
    • 2002
  • The electric power load during the peak time in summer is strongly affected by cooling load, which decreases the preparation ratio of electricity and brings about the failure in the supply of electricity in the electric power system. The ice-storage system and heat pump system are possible solutions to settle this problem. In this study. the method of estimating temperature and humidity to forecast the cooling load of ice-storage system is suggested, then the method of forecasting the cooling load using fuzzy logic is suggested by simulating that the cooling load is calculated using actual temperature and humidity. The forecast of the temperature, humidity and cooling load are simulated, and it is shown that the forecasted data approach to the actual data. Operating the ice-storage system by the forecast of cooling load with night electric power will improve the ice-storage system efficiency and reduce the peak electric power load during the summer season as a result.