판형 열교환기를 이용한 과냉각수용액에서 유동과냉도 및 냉각속도가 연속제빙에 미치는 영향 (Influence of the Supercooling Degree and Cooling Rate on a Continuous Ice Formation by a Supercooled Aqueous Solution in Flow Using a Plate Heat Exchanger)

  • 이동규;백종현;홍희기;강채동
    • 설비공학논문집
    • /
    • 제19권9호
    • /
    • pp.647-653
    • /
    • 2007
  • In dynamic ice storage system(DISS), ice slurry is formed not only from solution freezing by mechanical removing parts but also supercooled solution. However, in order to perform continuous ice formation in the system without mechanical moving parts, supercooled aqueous solution should be formed stable through cooling heat exchanger and be dissolved uniformly in storage tank. In previous study, the time of ice slurry increased as the pressure of the cooling heat exchanger(PHX) increased. In this study, a cooling experiment of an ethylene glycol 7mass% solution was performed with various inlet temperature of the PHX, which has constant brine inlet temperature of $-7^{\circ}C$. The temperature in the storage tank maintained to freezing point of the solution. At results, the time of ice slurry formation increased as the supercooling degree decreased and the cooling rate increased.

판형 열교환기에서 유동 과냉도 및 냉각속도가 연속제빙에 미치는 영향 (Effect of supercooling and cooling rate on a continuous ice slurry formation using a plate heat exchanger)

  • 이동규;백종현;홍희기;강채동
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.138-143
    • /
    • 2006
  • The peculiarity of ice slurry, such as liquidity, high heat transfer rate and easy storage can also find to supercooled type dynamic ice storage system(DISS) which is one of the DISS. However, in order to accomplish continuous ice formation in the system without mechanical moving parts, supercooled aqueous solutionshould be formed stable through cooling heat exchanger and be dissoluted in storage tank. In previous research, the time of ice slurry increased as the pressure of the cooling heat exchanger(PHX) increased. In this study, a cooling experiment of an ethylene glycol 7mass% solution was performed with various inlet temperature of the PHX, which has constant brine inlet temperature of $-7^{\circ}C$. The temperature in the storage tank maintained to freezing point of the solution. At results, the time of ice slurry formation increased as the supercooling degree decreased and the cooling rate increased.

  • PDF

축냉 시스템을 적용한 쇼케이스 운전에 대한 실험적 연구 (Experimental Study of Showcase Using Cold Storage System)

  • 이은지;이동원;김용찬
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1111-1116
    • /
    • 2008
  • The purpose of this study is to maintain high efficiency and reasonable use of cold-heat storage systems operated the showcase. An experimental study is carried out to manufacture the showcase system in a laboratory. Comparing the result at general operation condition with that at the new condition using ice storage system, this study showed the effects of the refrigerant sub-cooling, and with using inverter. At the condition using ice storage system, the ice making process was operated during midnight being not needed the cooling of the showcase through the continuous running of the condenser unit. And then, the refrigerant was sub-cooled using stored cold-heat after being discharged from the air cooling condenser during the day time. The cooling performance was increased owing to the sub-cooling of refrigerant during day time, hence the running time of the compressor was effectively decreased. In other words, this study showed that power consumption during daytime can be transferred to the midnight for making use of the refrigerant sub-cooling.

  • PDF

빙축열조를 이용한 냉매과냉각 시스템 기초연구 (Basic Study on Sub-cooling System using Ice storage tank)

  • 이은지;이동원;김용찬
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.990-995
    • /
    • 2009
  • Experimental basic study was performed to understand the characteristics of sub-cooled refrigerant using a cold heat storage system. This system was made up general vapor-compression refrigeration cycle added sub-cooler and ice storage tank. The purpose of this study are to application use of cold-heat storage systems multiplicity of fields and to understand of sub-cooling system. At the condition using ice storage system, the ice making process was operated during night time by electric power. And then, the refrigerant was sub-cooled using stored cold-heat after being discharged from the air cooling condenser during the day time. Comparing the result at general operation with the operation using sub-cooling system. This study showed the effects of the sub-cooled degree. The cooling performance was increased owing to the sub-cooling of refrigerant during day time, and the compressor consume power was a little decreased. Thus the COP was also increased owing to the sub-cooling of refrigerant.

  • PDF

수중 하베스트형 빙축열 시스템의 운전특성 실험 (Experiments on Operation Characteristics of In-Water Harvest-Type Ice Storage System)

  • 최인수;김재돌;윤정인
    • 대한기계학회논문집B
    • /
    • 제25권5호
    • /
    • pp.653-659
    • /
    • 2001
  • This paper is concerned with the development of a new method for making and separating ice in-water and saving floated ice by installing an evaporation panel in an ice storage tank. The new method shows very good heat transfer efficiency than that of the convectional method. It is because the evaporation panel is directly contacted with water in the storage tank. The experiments were performed by varying inlet and outlet refrigerant temperatures of its evaporator. From the experimental results, the operating characteristics of in-water harvest-type ice storage system were investigated by measuring temperature and pressure at each point of the ice storage system and power required to operating compressor respect to the changes of the inlet and outlet refrigerant temperature of evaporator. It can be think that defrost frequency decreased and heavy ice created as the refrigerant temperature of evaporator outlet and defrost setting temperature is low so gotten result can effect to release efficiency. Also, consumption power, condensing heat quantity, refrigerating capacity and performance efficiency decreased as time goes by. Therefore, these results provide the basic data for system optimization, performance improvement and the possibility of application to other fields.

공압구동형 제빙기의 열전달 특성에 관한 실험적 고찰 (The Experimental Study on the Heat Transfer Characteristics of Ice Slurry Generator Using Air Cylinder)

  • 김민준;김종하;윤재호;박일환;이규칠
    • 설비공학논문집
    • /
    • 제19권11호
    • /
    • pp.743-750
    • /
    • 2007
  • In this study, ice slurry generator using air cylinder was designed and manufactured to investigate the heat transfer characteristic of the ice slurry generator. The ice slurry generator has the same shape as the shell-and-tube type heat exchanger. Refrigerant is flowing in the shell side and ethylene glycol solution in the tube side. The experiment was conducted on performance of ice slurry generator using air cylinder with standard condition and the results are plotted on the time scale. The experimental tests on the various concentration of ethylene glycol solution, the various solution velocity in the tube side and the various tube size have been carried. For the above experimental conditions, ice making characteristics of the ice slurry generator are evaluated in terms of the overall heat transfer coefficient. And the experimental results show that the overall heat transfer coefficient of the system is increased as the tube size and the concentration of ethylene glycol decreases.

쇼케이스 운전상태를 고려한 축냉시스템 적용타당성 연구 (A study on the Cold-heat Storage System for Operation Status Monitoring of Showcase)

  • 이은지;이동원
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1261-1266
    • /
    • 2008
  • Experimental study was performed to understand the operations of a showcase working in a discount store. Temperatures of evaporation, condenser were measured and also electric power consumption of compressor were measured. The purpose of this study is to application use of cold-heat storage systems operated the showcase. At the condition using ice storage system, the ice making process was operated during midnight being not needed the cooling of the showcase through the continuous running of the condenser unit. And then, the refrigerant was sub-cooled using stored cold-heat after being discharged from the air cooling condenser during the day time. The cooling performance was increased owing to the sub-cooling of refrigerant during day time, hence the running time of the compressor was effectively decreased. In other words, this study showed that power consumption during daytime can be transferred to the midnight for making use of the refrigerant sub-cooling. So the operating characteristics of the showcase system under various working conditions were analyzed and discussed.

  • PDF

R290/R32, R290/DME 적용 소프트 아이스크림 제조기 (Soft ice-cream maker using R290/R32, R290/DME)

  • 박태균;한성필;함정호;김내현;박형채
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.64-67
    • /
    • 2006
  • Drop-in tests were conducted using R290/R32 (31:69) or R290/DME (65:35) mixture in a ice-cream maker for possible replacement of R-502 and R-404A. At the standard room temperature ($20^{\circ}C$), the time required for initial ice-cream making was 4'7' for R290/32, 4'39' for R404A and 4'59' for R290/DME. The electric energy consumed was 436 kJ for R290/32, 425 kJ for R404A and 439 kJ for R290/DME. The mass flow rate as well as the temperature and pressure data are also provided.

  • PDF

과냉각 축냉시스템을 적용한 쇼케이스의 운전 특성에 대한 실험적 연구 (Experimental Study on The Running Characteristics of Showcase Using Cold Storage System)

  • 이동원;김정배
    • 한국태양에너지학회 논문집
    • /
    • 제32권6호
    • /
    • pp.22-28
    • /
    • 2012
  • The purpose of this study was to show how tomaintain high efficiency and to use reasonably when being applied the cold-heat storage systems to the showcase. An experimental study was performed to manufacture the showcase system in a laboratory. Comparing the result at general operation condition with that of the new condition using ice storage system, this study showed the effects of the refrigerant sub-cooling, and with using inverter. Using ice storage system, the ice making process was operated during midnight being not needed the cooling of the showcase through the continuous running of the condenser unit. And then, the refrigerant was sub-cooled using the stored cold-heat after being discharged from the air cooling condenser during the day time. Through the experiments, the load transfer rate for the showcase using inverter and ice storage was estimated about 30.0%. And showed that the total power consumption of the showcase with inverter could be reduced about 37% than that of the showcase without inverter.

역전 유동층 내의 유동해석 및 슬러리아이스 생성에 관한 연구 (Flow Analysis and an Experimental Study on Formation of Slurry Ice in the Reversing Flow Layer)

  • 오철;최영규
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제35권4호
    • /
    • pp.421-428
    • /
    • 2011
  • 최근 지구 온난화와 더불어 급격한 기후 변화 등으로 여름철 주간 냉방 수요가 급격히 증가하여 이에 따른 전력 수요량이 증가하고 있다. 또한 주간 전력 피크로 인한 급격한 전력부하 상승은 전력 수급의 불균형을 가져 와 사회적 문제로 대두되고 있다. 이를 위해 개발된 축냉시스템은 전력사용량이 상대적으로 적은 심야시간에 냉열을 만들어 탱크에 저장해 두었다가 그것을 주간 냉방 전력 사용 피크시간에 이용함으로써, 냉동기의 용량이 작아지고 냉동기를 고효율로 운전할 수 있으며, 갑작스런 부하 증가에 적절히 대응할 수 있는 등 여러 가지 장점을 갖고 있다. 이로 인하여 주간전력 피크를 줄여주는 효과를 가진다. 축냉시스템 중 하나인 슬러리아이스형은 슬러리아이스가 과냉되지 않은 작은 입자형태를 갖고 있어 해빙특성이 뛰어나므로 부하변동에 빠르게 반응할 수 있으며, 그 저장과 재생 및 수송 분야에서 그 장점과 기능이 입증되었다. 본 실험에서는 슬러리아이스 생성 효율을 높이기 위하여 역전유동층을 이용하였다. 이러한 역전유동층은 냉각관 표면에 얼음 부착이 심화되기 전에 얼음 입자를 분리시켜 수 내지 수십 미크론 단위(0.1~0.001 mm)의 슬러리아이스를 생성하도록 하였다.