• 제목/요약/키워드: IS6110

검색결과 531건 처리시간 0.022초

하이브리드 열펌프 열교환기 오염 진단 연구 (A Study on Diagnosing Fouling of Heat Exchangers of a Hybrid Heat Pump)

  • 신영기
    • 설비공학논문집
    • /
    • 제26권5호
    • /
    • pp.240-246
    • /
    • 2014
  • A fault detector was developed for heat exchangers of a hybrid heat pump (HP) for household. The proposed detector can be applied directly to raw operating data. It is to monitor a tracking error between a measured saturation temperature and its state observer. The observer was estimated from a state-space model simulating dynamics of a heat exchanger. The real hybrid HP was substituted with a dynamic simulator that implemented two-phased heat transfer and was validated by experimental data. And artificial fault data were generated using the simulator. Diagnosing the data showed the following. The residual calculated from the state observer error shows a relatively robust consistency with respect fouling level. The fault detector is practically useful because it detects a threshold fouling beyond which the performance starts to deteriorate significantly.

소성변형에 의한 배관 용접부의 잔류응력 개선 방법 (A Method of Residual Stress Improvement by Plastic Deformation in the Pipe Welding Zone)

  • 최상훈;왕지남
    • 설비공학논문집
    • /
    • 제25권10호
    • /
    • pp.568-572
    • /
    • 2013
  • The main components, such as a reactor vessel, in commercial nuclear power plants have been welded to pipes with dissimilar metal in which Primary Water Corrosion Cracking (PWSCC) has been occurred. PWSCC has become a worldwide issue recently. This paper addresses the results of experimental and numerical analysis to prevent PWSCC by changing the stress profile that is tensile stress to compressive stress at interesting regions with plastic deformation generated by mechanical pressure. Based on the results of experimental and numerical analysis with a 6 inch pipe and dissimilar metal welded pipes, compressive stress 68~206 Mpa is generated at all locations of inner surface in the heat affected zone.

커튼월의 단열 향상 및 결로 방지를 위한 통기구조 적용방안 연구 (Application of Ventilated Cavity for Enhancing Insulation and Preventing Condensation of Curtain-wall System)

  • 이선우
    • 설비공학논문집
    • /
    • 제29권1호
    • /
    • pp.21-28
    • /
    • 2017
  • Curtain-wall systems have been widely applied to buildings because of their lightweight and constructability characteristics. However, as curtain-wall systems include many building materials, vapor barriers can become damaged and condensation can occur. Due to the material properties of stone curtain-walls, the external appearance and structure of a building could be damaged and the insulating performance of the curtain-wall could be worse. Natural ventilation using an air cavity in a curtain-wall is expected to be effective for the prevention of condensation in inner walls and for the reduction of building cooling energy use in the summer. The purpose of this experimental study is to analyze the influence of a ventilated cavity on the insulating performance of a curtain-wall and the ventilated cavity depth and ratio of top opening needed to prevent condensation in a curtain-wall.

가정용 제습기의 운전에 따른 실내 온습도 변화 분석 (Analysis of Indoor Temperature and Humidity Changes with the Operation of the Condense Drying Dehumidifier)

  • 최연희;송두삼;손원우;임영훈
    • 설비공학논문집
    • /
    • 제27권12호
    • /
    • pp.626-632
    • /
    • 2015
  • The purpose of this paper is to analyze the indoor temperature and humidity changes with the operation of a condense drying humidifier. This paper illustrates the principles and composition of a condense drying dehumidifier, which is broadly used in Korean households. Experiments were conducted repeatedly on rainy days in a test chamber. The results showed that the indoor RH was lowered to 40% within 2 hours while the indoor temperature was increased by approximately $4.3^{\circ}C$ with the operation of the humidifier.

불균일한 풍속분포에 따른 응축기의 열전달 성능 변화 (Heat Transfer Performance Variation of Condenser due to Non-uniform Air Flow)

  • 이원종;정지환
    • 설비공학논문집
    • /
    • 제26권4호
    • /
    • pp.193-198
    • /
    • 2014
  • Heat transfer performance variation of a condenser caused by non-uniform distribution of air flow was investigated using a numerical simulation method. A heat exchanger used for a outdoor unit of a commercial heat pump system and represented by a numerical model was selected. Non-uniform profile of air-velocity was constructed by measuring the air velocity at various locations of the outdoor unit. Simulation was conducted for various refrigerant circuits and air flow conditions. Simulation results show that the heat transfer capacity was reduced depending on the air-flow rate and the refrigerant circuit configuration. It is also shown that the capacity reduction rate is increased as the average air velocity decreases.

출구 온도를 고려한 수평형 지중열교환기의 매설 지침에 관한 연구 (A Study on Burial Guideline of Horizontal Geothermal Heat Exchanger based on Exit Temperature)

  • 조성우;임병찬
    • 설비공학논문집
    • /
    • 제26권12호
    • /
    • pp.553-558
    • /
    • 2014
  • Geothermal energy can be used with a geothermal heat pump or an earth-to-air heat exchange system (EAHES), which is referred to as a "cooling tube" in Korea. In this study, we suggest EAHES burial guidelines in terms of the parameters of buried pipe length and air velocity regarding the exit air temperature of EAHES. The exit air temperature for EAHES in three regions (Changwon, Busan and Seoul) was calculated with variation in buried pipe length and air velocity at ${\Phi}100mm$ and ${\Phi}200mm$. In conclusion, variation in the buried pipe length is more effective than that of air velocity to achieve the required exit air temperature.

두 개의 가변 변수가 있는 냉매 증기압 상관식의 성능 평가 (Performance Assessment of Refrigerant Vapor-Pressure Equations with Two Adjustable Parameters)

  • 박경근
    • 설비공학논문집
    • /
    • 제24권2호
    • /
    • pp.129-135
    • /
    • 2012
  • Performance of various temperature-dependent vapor-pressure equations with two adjustable parameters is assessed. These are Antoine, Miller, Zia-Thodos, Mejbri-Bellagi and other 10 equations. The equations are fitted to correlate the data from NIST Chemistry WebBook for 43 pure substance refrigerants from the critical point to the triple point. It was found that the Mejbri-Bellagi equation yields the lowest average absolute deviation of 0.37% compared with that of 0.58% of the Miller equation which is known to give better fit to experimental data than the Antoine equation(1.42%) does.

선박 복합 밀폐공간 내 환기효율 분석을 통한 공기환경 개선에 관한 연구 (Study on Improvement of Air Quality through Analysis of Ventilation Efficiency in Complex Enclosures of a Ship)

  • 정재훈;송두삼
    • 설비공학논문집
    • /
    • 제27권8호
    • /
    • pp.440-447
    • /
    • 2015
  • In the shipbuilding process, the confined work spaces of the ship are formed continuously; the ventilation method can therefore be limited to dilution ventilation due to the complex structure and limited opening of the confined space. Also, it is difficult to evaluate air-quality using measurement and an adequate ventilation method. CFD simulation methods are typically used in analyzing ventilation efficiency in these cases. In this study, a method is suggested to analyze the air quality of the complex enclosures in shipbuilding using CFD. Especially, among the conventional indices, the ventilation efficiency scales or indices, the supply air contribution (SVE4), and the age of the air (SVE3) (fit for the confined and complex enclosure) were applied.

터빈 사이클의 보정 성능 계산을 위한 급수 유량의 검증 모델 (Verification Model of the Feedwater Flow for the Calculation of Corrective Performance of Turbine Cycle)

  • 김성근;양학진;이강희;최광희
    • 설비공학논문집
    • /
    • 제24권6호
    • /
    • pp.538-544
    • /
    • 2012
  • Analysis of thermal performance is required for the economic operation of turbine cycle of power plant. We developed corrective model of main feed water flow which is the most important parameter for the precise analysis of turbine cycle performance. Classification model for the identification of feed water flow measurement status was applied to increase the suitability of the corrective model. We used neural network and support vector machine to develop estimation model of main feed water flow with more generalization capability. The estimation model can be used practically to evaluate corrective performance of turbine cycle plant.

공조설비 운전방법 및 시설개선을 통한 에너지절약 효과분석 (An Analysis of the Energy Saving Effect Through the Retrofit and the Optimal Operation for HVAC Systems)

  • 김용기;이태원
    • 설비공학논문집
    • /
    • 제24권4호
    • /
    • pp.343-350
    • /
    • 2012
  • The major goal of building energy management is to minimize the energy consumption while maintaining the comfortable environment condition. Nowadays building energy management to save HVAC energy and so on is the most critical issue for existing building service branch with high efficiency equipments and their optimal operation. The effects on the building energy savings of the building equipment retrofit and the improvement of its operation method, especially in the field of HVAC system, were analyzed in this study for domestic small and/or medium sized buildings. Over 8.8% of energy saving was achieved compared withe total energy consumption in commercial building. These results could be used for reasonable maintenance and efficient management of the various building service equipments and related systems.