• Title/Summary/Keyword: IED (Intelligent Electrical Device)

Search Result 54, Processing Time 0.031 seconds

A Study on structure of embedded OS module for intelligent electronic device (전력기기의 임베디드 OS 모듈 구성에 관한 연구)

  • Kwon, Hyo-Chul;Oh, Jea-Hun;Oh, Sung-Min;Hong, Jung-Ki
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.938-939
    • /
    • 2008
  • Embedded OS is used widely in many case of today's systems. Using of Embedded OS for IED(Intelligent electronic device) is vary useful method of the processing of complex operations. In this paper, we designed embedded OS module for use as a more effective way in IED systems.

  • PDF

A Study on Digital Filter for Intelligent Electronic Device of Power Transformer (전력용 변압기용 통합보호제어장치를 위한 디지털 필터에 관한 연구)

  • Park, Chul-Won;Park, Jae-Sae;Shin, Myong-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2004.07e
    • /
    • pp.30-32
    • /
    • 2004
  • In this paper, as the preceding research for development of Intelligent Electronic Device(IED) for digital based substation automation system(SAS), we tried to selection of the most suitable digital filter by comparison of frequency response characteristic. performance of wanted frequency component extraction.

  • PDF

Precision time sync. HW/SW platform for power system protection (전력시스템 보호를 위한 정밀 시각 동기 적용 HW/SW 플랫폼 기술)

  • Nam, Kyung-Deok;Son, Kyu-Jung;Chang, Tae-Gyu;Kang, Sang-Hee
    • Journal of IKEEE
    • /
    • v.22 no.4
    • /
    • pp.1036-1043
    • /
    • 2018
  • This paper presented future power system protection technologies through the HW/SW integration platform with IEC 61850 and IEEE c37.238 standards. To determine the implementation performance of the integrated platform, an example of EVM (Evaluation Module) was constructed to satisfy the standards. The platform has been identified as a future power system integrated IED(Intelligent Electronic Device) HW/SW technology that meets the level of error required by the time sync standard and the level of delay required by protecting the power system.

Study on the Metamaterial Design Methodology to Reduce the Size of the Bandpass Filter for the Smart Grid IED (스마트그리드 IED용 대역통과여파기 소형화를 위한 메타재질구조 설계법 연구)

  • Kahng, Sung-Tek;Kim, Hyeong-Seok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.12
    • /
    • pp.2299-2304
    • /
    • 2011
  • In this paper, we propose the methodology to make the bandpass filters for the Smart Grid IED(Intelligent Electronic Device) smaller than the conventional bandpass filters. The size-reduction of the filters and the filter performances are indebted to devising small CRLH(composite right- and left-handed) resonators and coupling them as the metamaterial structures. The design methodology is validated by the equivalent circuit to be compared with the reliable full-wave EM simulation, and the proposed metamaterial filter outperforms the standard parallel-edge coupled filter with respect to the miniaturization and frequency response.

A Study on Implementation of a Test System for lED Performance Verification (lED 성능검증을 위한 시험시스템 구현에 관한 연구)

  • Jang, B.T.;Yun, S.M.;Lee, N.H.;Han, J.Y.;Kim, Y.H.;An, Y.H.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.235-237
    • /
    • 2009
  • 변전자동화시스템이 IEC 61850 규격도입 이후 통신에 대한 적합성 시험과 함께 보호계전기의 보호 및 제어기능에 대한 시험도 통신과 결부되어 자동화하려는 추세에 있다. 기존에 변전소에 적용된 디지털 보호계전기는 IEC 61850 통신서비스와 접목되어 IED(Intelligent Electronic Device)로 불려진다. 기존의 보호계전기와 달리 IED의 경우 변전자동화시스템으로 통합구현되기 때문에 IED 단위시험 보다는 시스템 수준의 성능시험을 요구하게 된다. 따라서 CMC 256 전용프로그램을 가지고는 변전자동화시스템의 성능시험을 완벽하게 다루게 어렵게 때문에 사용자가 CMC 256 장비를 자유롭게 다룰 수 있는 환경개발을 필요로 한다. 본 논문에서는 CMC 256 장비의 운용을 사용자 정의로 구현할 수 있는 CM Engine을 소개하고 실제 구현사례를 통해 변전자동화시스템의 성능시험을 위한 기반 자료를 다루고자 한다.

  • PDF

A Study on the Communication Test of Substation Automation System based on IEC 61850 (IEC 61850 규격 기반 디지털 변전자동화시스템 통신성능 시험에 관한 연구)

  • Lee, Nam-Ho;Jang, Byung-Tae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.1
    • /
    • pp.14-19
    • /
    • 2008
  • In order to verify a substation automation system based on IEC 61850, Korea Electric Power Research Institute under the project related to SAS has constructed IED testing system, which consists of HMI, IED(Intelligent Electronic Device), network equipment, V/I generator, and performed a various of communication tests such as the interoperability test between two IEDs made by other vendors. The test was proceeded based on SCL(Substation Configuration Description Language). This paper presents ways and procedures to simulate those tests and solutions to clear up SCL based engineering problems and compatibility among the individual manufacture tools.

A development of two-winding transformer protective IED based on IEC61850 (IEC61850 기반의 2권선 변압기 보호용 IED 개발에 관한 연구)

  • Oh, Sung-Min;An, Yong-Ho;Song, In-Jun;Oh, Jae-Hoon;Kwon, Hyo-Chul;Hong, Jung-Gi
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.193-194
    • /
    • 2008
  • IEC 61850 기반의 변전소자동화시스템이 세계적으로 많은 관심을 가지면서 IEC 61850 프로토콜 기반의 IED(Intelligent Electronic Device) 개발을 위해 전 세계적으로 많은 노력이 진행되고 있다. 본 연구에서는 IEC 61850 표준규격에서 제안하는 객체 모델링 및 통신프로토콜을 이용하여 2권선 변압기 보호용 IED를 개발하고 그 구현방법을 설명하였다. 구현을 위해 리눅스 OS(Operation System)가 포팅된 통신보드에 MMS(Manufacturing Message Specification), GOOSE(Generic object oriented substation event) 통신모듈을 탑재하였고 데모 시스템을 구성하여 성능을 검증하였다.

  • PDF

Construction of IED Conformance Testing System (IED 적합성 인증시험 장치 구축)

  • Lee, N.H.;Kim, J.H.;Jang, B.T.;An, Y.H.;Hwang, K.C.
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.489-490
    • /
    • 2007
  • In order to construct a digital substation based on IEC61850, All of the utility company should used IEDs to be verified and also vendors should get a certification from the international conformance testing organizationsuch as KEMA. So KEPRI in charge of POWER IT project related to SAS was required to IED conformance testing system, which can perform the test previously. The system, KEPCO developed, consists of HMI, IED (Intelligent Electronic Device), network equipment, V/I generator etc

  • PDF

Hardware Design of IED using DSP for Power Transformer Protection (DSP를 이용한 전력용 변압기용 IED의 하드웨어 설계)

  • Park C. W.;Jung Y. M.;Ha K. J.;Koo C. S.;Shin M. C.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.363-365
    • /
    • 2004
  • This paper proposes a hardware implementation of intelligent electronic device for power transformer protection. And proposes an advanced main protection algorithm by voltage-current trend and flux-differential current slope characteristics. The secondary protection functions include UR, OCGR, OVR, and W etc. The main board of IED is based on the DSP chip TMS32C32 processor The IED was tested with relaying signals obtained for EMTP simulation package.

  • PDF

A Study on the Information Exchange Technology Between IEDs Using SOAP in Network Based Substation Automation System (네트워크 기반 자동화 변전소에서 SOAP을 이용한 IED간 정보교환기술 연구)

  • Ko, Yun-Seok
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.9
    • /
    • pp.376-383
    • /
    • 2006
  • In this paper, autonomous information exchange methodology is studied between IEDs using SOAP protocol based on XML and PtP communication to archive the safety and reliability of large-scale system operation. The SOAP protocol has the advantages in the independency Problem for operating systems, using language, platforms and the security problem because it is XML-based RPC protocol. Inference-based solution of the IED is designed as rule-based solution so that the IED internal status, the system status or the faulted zone can be inferred autonomously using the internal data as well as information data obtained from free information exchange among other IEDS, Also, it is designed so that the inference results and the operation information are transmitted to the above SCADA system, and determined autonomously whether the commands from the SCADA are executed or not. Finally, The inference-based solution of IED and information exchange system among IEDS is implemented using MS Visual C++ MFC, MS SOAP and MS XML. Availability and accuracy of the proposed methodology and the design is verified from diversity simulation reviews for typical distribution substation.