• 제목/요약/키워드: Hydrocarbon refrigerants

검색결과 51건 처리시간 0.028초

내면 핀관을 사용하는 열교환기에서 R-22 대체 탄화수소계 냉매의 증발 열전달 특성 (Evaporating heat transfer characteristics of R-22 alternative hydrocarbon refrigerants at heat exchanger using grooved inner tube)

  • 홍진우;박승준;노건상;구학근;오후규
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제24권4호
    • /
    • pp.414-420
    • /
    • 2000
  • In this paper, evaporation heat transfer characteristics at a inner grooved tube were studied using a new natural refrigerants R-290, R-600a and HCFC refrigerant R-22. Experiments were performed in the inner tube with outside diameter of 12.70mm, having 75 fins with a fin height of 0.25mm. The following results were obtained from this research. On the evaporating heat transfer characteristics, the maximum increment of heat transfer coefficient was found in R-290. Average heat transfer coefficient was obtained the maximum value in R-290 and the minimum value in R-22. It reveals that the natural refrigerant can be used as a substitute for R-22. In the grooved inner tube, 70% of the increment of the heat transfer coefficient was obtained compared to the smooth tube. Comparing the heat transfer coefficient between experimental results and simulation data of other's, the Kandlikar's correlated equation was closely approximated to the author's experimental results in the smooth tube or grooved inner one.

  • PDF

탄화수소계 냉매 R-290, R-600a의 수평관내 응축 열전달 특성에 관한 연구 (Condensation heat transfer characteristics of hydrocarbon refrigerants R-290 and R-600a inside horizontal tubes)

  • 박승준;박기원;노건상;정재천;오후규
    • 설비공학논문집
    • /
    • 제12권1호
    • /
    • pp.20-25
    • /
    • 2000
  • An experimental study on the condensation heat transfer coefficients of R-22, R-290 and R-600a inside horizontal tube was performed. Heat transfer measurements were performed for smooth tube with inside diameter of 10.07 mm and outside diameter of 12.07 mm and inner grooved tube having 75 fins whose height is 0.25 mm. This study was performed for condensation temperatures were from 308 K to 323 K, and mass velocity of $51 kg/m^2s - 250kg/m^2s$. The test results showed that the local condensation heat transfer coefficients increased as the mass flux increased, and also the effect of mass flow rate on heat transfer coefficients of R-290 was less than R-22. In addition, heat transfer coefficient of R-22 increased to a larger extent than R-290 and R-600a as the mass flow rate increased. Average condensation heat transfer coefficients of natural refrigerants were superior to that of R-22. The present results had a good agreement with Cavallini-Zecchin's correlation for smooth and inner grooved tubes.

  • PDF

7.73 mm와 5.80 mm 수평관내 탄화수소 냉매의 응축 열전달 특성 (Condensation Heat Transfer Characteristics of Hydrocarbon Refrigerants in Horizontal Tubes of 7.73 mm and 5.80 mm)

  • 손창효
    • 한국수소및신에너지학회논문집
    • /
    • 제19권4호
    • /
    • pp.331-339
    • /
    • 2008
  • 본 논문은 내경 7.73 mm와 5.80mm의 수평관내 프레온계 냉매 R-22와 탄화수소계 냉매 R-290과 600a의 응축 열전달 계수의 실험적 결과를 나타내었다. 실험장치는 압축기, 응축기, 팽창밸브, 증발기 등으로 구성된다. 응축 실험은 질량유속 $35.5{\sim}210.4\;kg/m^2s$이고, 응축온도 40$^{\circ}C$인 조건에서 수행하였다. 주요 결과를 요약하면 다음과 같다. 탄화수소계 냉매 R-290과 R-600a의 평균 열전달 계수는 프레온계 냉매 R-22보다 높게 나타났으며, R-600a의 평균 열전달 계수가 모든 관경에 대해 가장 높게 나타났다. 실험결과와 종래의 상관식을 비교한 결과, 모든 관경과 냉매에 대해 Haraguchi 등의 상관식이 가장 좋은 일치를 보였다. 그 중에서 Cavallini-Zecchin의 상관식은 7.73 mm 관경의 실험데이터와, Dobson 등의 상관식은 내경 5.80 mm 관경의 데이터와 좋은 일치를 보였다.

열교환기 구조 변화에 따른 $NH_3$와 R22의 성능특성연구 (The Study on Performance Characteristics of $NH_3$ and R22 due to Structure of Heat Exchanger)

  • 하옥남;하경수;이승재;정송태
    • 한국공작기계학회:학술대회논문집
    • /
    • 한국공작기계학회 2005년도 춘계학술대회 논문집
    • /
    • pp.60-65
    • /
    • 2005
  • Nowadays HCFCs refrigerant are restricted because it cause depletion of ozone layer. However, natural gases such as ammonia as an organic compound, propane and propylene as hydrocarbon are easy and cheap to obtain as well as environmental. Accordingly, this experiment apply the $NH_3$ and R22 to study the performance characteristic from the superheat control and compare the energy efficiency of two refrigerants from the high performance. The condensing pressure of refrigeration system is increased from 15bar to 16bar and degree of superheat is increased from 0 to $10^{\circ}C$ at each condensing pressure. As the result of experiment, when comparing the each COP, we knew the $NH_3$ is suitable as the alternative refrigerant of the R22.

  • PDF

Non CO2 온실가스 처리기술에 관한 연구 동향 (Review of Studies on Treatment Technology for Non-CO2 Greenhouse Gases)

  • 장태현;길상철;나도백;김상우
    • 한국산업융합학회 논문집
    • /
    • 제13권3호
    • /
    • pp.133-143
    • /
    • 2010
  • A methodology is described to assess the potential long term contribution of $Non-CO_2$ greenhouse gases. Many studies aimed at minimizing the charge in a refrigerating machine were thus developed. On a global level, reduction of refrigerant charges must not effect energy aspects while respecting environmental constrains[Montreal 1987, Koto 1997]. In this paper, recent studies on non $CO_2$ are reviewed since it is one of the key technologies. Hydrocarbons are one of the candidates for refrigerants of next generation.

  • PDF

탄화수소계 냉매들과 DME의 수평 평활관내 흐름 응축 열전달 특성 (Flow Condensation Heat Transfer Characteristic of Hydrocarbon Refrigerants and DME in Horizontal Plain Tube)

  • 박기정;이민행;박현신;정동수
    • 설비공학논문집
    • /
    • 제19권7호
    • /
    • pp.545-554
    • /
    • 2007
  • Flow condensation heat transfer coefficients(HTCs) of R22, propylene, propane, DME and isobutane are measured on a horizontal plain tube. The main test section in the experimental flow loop is made of a plain copper tube of 9.52 mm outside diameter and 530 mm length. The refrigerant is cooled by passing cold water through an annulus surrounding the test section. Tests are performed at a fixed refrigerant saturation temperature of $40{\pm}0.2^{\circ}C$ with mass fluxes of 100, 200, $300kg/m^2s$ and heat flux of $7.3\sim7.7kW/m^2$. The data are obtained in the vapor Quality range of $10\sim90%$. Test results show that at same mass flux the flow condensation HTCs of propylene, propane, DME and isobutane are higher than those of R22 by up to 46.8%, 53.3%, 93.5% and 61.6% respectively. Also well-known correlations developed based upon conventional fluorocarbon refrigerants predict the present data within a mean deviation of 30%. Finally, the pressure drop increase as the mass flux and Quality increase and isobutane shows the highest pressure drop due to its lowest vapor pressure among the fluids tested.

Utilization Of Ethane As Working Fluid At Two-Stage Cascade Vapour Compression System

  • Kim, Yeong-Geun;Shin, You-Sik;Jeong, Hyo-Min;Chung, Han-Shik;Lubi, Rahadiyan
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.414-420
    • /
    • 2005
  • For supporting future demands of lower temperature. environmental friendly low- temperature refrigerants must be studied and developed to replace halocarbon. Ethane. which is one of hydrocarbon compound. is an environmental friendly refrigerant because it has zero ODP and GWP ${\sim}$ 20[per 100yr]. On this study, two-stage cascade refrigeration system was utilized to investigate performance of ethane on the low-stage. By employing R22 at higher stages. energetic performance as well as operating condition of R22/R170 system is compared to R22/R23. At low stage evaporation pressure ranges from 1.10 to 2.74 bar, R22/R170 shows higher COP over R22/R23. Furthermore, at the same range evaporation temperature R22/R170 can reach lower temperature.

  • PDF

냉매 R717과 R22를 작동유체로 이용한 냉동장치의 성능특성에 관한 연구 (The Study on Performance Characteristics in Refrigeration System using R717 and R22 as working fluid)

  • 김진현;김재근;김종길;김양현;홍석주;하옥남
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.495-500
    • /
    • 2006
  • Nowadays HCFCs refrigerant are restricted because it cause depletion of ozone layer. However, natural gases such as ammonia as an organic compound, propane and propylene as hydrocarbon are easy and cheap to obtain as well as environmental. Accordingly, this experiment apply the $NH_3$ and R22 to study the performance characteristic from the superheat control and compare the energy efficiency of two refrigerants from the high performance. The condensing pressure of refrigeration system is increased from 15bar to 16bar and degree of superheat is increased from 0 to $10^{\circ}C$ at each condensing pressure. As the result of experiment, when comparing the each COP, we knew the $NH_3$ is suitable as the alternative refrigerant of the R22.

  • PDF

수평관내 R-290과 R-600a의 증발 열전달 특성 (Evaporation kent transfer characteristics of R-290 and R-600a in the horizontal tubes)

  • 손창효
    • 한국산학기술학회논문지
    • /
    • 제9권2호
    • /
    • pp.264-269
    • /
    • 2008
  • 본 논문은 수평 이중관식 열교환기 내 프레온계 냉매의 대체냉매인 탄화수소계 냉매(R-290과 R-600a)의 증발 열전달 계수에 대한 실험적 결과를 나타내었다. 증발기의 내관 내경은 각각 10.07 mm와 6.54 mm의 2가지를 사용하였다. 증발실험은 질량유속 $35.5{\sim}210.4\;kg/m^2s$이고, 냉각용량 $0.95{\sim}10.1\;kW$인 조건에서 수행하였다. 실험결과를 요약하면, 탄화수소계 냉매 R-290과 R-600a의 증발 열전달 계수가 프레온계 냉매 R-22보다 높았다. 즉, R-22의 증발 열전달 계수에 비해, R-290와 R600a는 각각 $56.7{\sim}70.1%$$46.9{\sim}59.7%$ 정도 높았다. 실험데이터와 종래의 상관식을 비교한 결과, 모든 냉매와 관경에 대해서 Kandlikar상관식이 가장 좋은 일치를 보였다.