Abstract
This paper presents the experimental results of evaporation heat transfer coefficients of HC(e.g. R290 and R600a), R-22 as a HCFCs refrigerant in horizontal double pipe heat exchangers, having four different inner diameters of 10.07 mm and 6.54 mm respectively. The experiments of the evaporation process were conducted at mass flux of $35.5{\sim}210.4\;kg/m^2s$ and cooling capacity of $0.95{\sim}10.1\;kW$. The main results were summarized as follows : The average evaporation heat transfer coefficient of R-290 and R-600a was higher value than that of R-22. In comparison with R-22, the evaporation heat transfer coefficient of R-290 and 600a is approximately $56.7{\sim}70.1$ and $46.6{\sim}59.7%$ higher, respectively. In comparison with experimental data and some correlations, the evaporation heat transfer coefficients are well matched with the Kandlikar's correlation regardless of a type of refrigerants and tube diameters.
본 논문은 수평 이중관식 열교환기 내 프레온계 냉매의 대체냉매인 탄화수소계 냉매(R-290과 R-600a)의 증발 열전달 계수에 대한 실험적 결과를 나타내었다. 증발기의 내관 내경은 각각 10.07 mm와 6.54 mm의 2가지를 사용하였다. 증발실험은 질량유속 $35.5{\sim}210.4\;kg/m^2s$이고, 냉각용량 $0.95{\sim}10.1\;kW$인 조건에서 수행하였다. 실험결과를 요약하면, 탄화수소계 냉매 R-290과 R-600a의 증발 열전달 계수가 프레온계 냉매 R-22보다 높았다. 즉, R-22의 증발 열전달 계수에 비해, R-290와 R600a는 각각 $56.7{\sim}70.1%$와 $46.9{\sim}59.7%$ 정도 높았다. 실험데이터와 종래의 상관식을 비교한 결과, 모든 냉매와 관경에 대해서 Kandlikar상관식이 가장 좋은 일치를 보였다.