• 제목/요약/키워드: High-Voltage Circuit Breaker

검색결과 136건 처리시간 0.031초

병렬아크의 고속 차단에 관한 연구 (A Study on the High Speed Breaking of Parallel Arcing)

  • 김일권;지홍근;김성욱;박대원;길경석
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2008년도 춘계학술대회 논문집
    • /
    • pp.327-331
    • /
    • 2008
  • This paper dealt with high speed breaking method to parallel arcing in low-voltage systems. The proposed high speed breaking circuit consists of a Rogowski coil and an integrator, and operates with an earth leakage circuit breaker (ELCB). A parallel arcing state was simulated by a short circuit using stripped wires. In this test, we analyzed tripping characteristics of the circuit breaker by the length of wires from 5m to 30m. From the experimental results, we confirmed that the proposed method can break the parallel arcing within a few millisecond.

  • PDF

고정밀 전류센서를 이용한 RCD 보조트립 장치 개발 (Development of RCD Auxiliary Trip Device by using High Precision Current Sensor)

  • 곽동걸
    • 전기학회논문지
    • /
    • 제58권8호
    • /
    • pp.1532-1537
    • /
    • 2009
  • Nowadays the diversity and large-capacity of electric appliances are strong effect on electrical fires augment in an alarming way. But, as the inactive response characteristics of the existing RCD (Residual Current protective Device) used on low voltage power distribution lines, so control of overload and electric short circuit faults, major causes of electrical fires, are not enough. Therefore this paper is confirmed the unreliability of the existing RCD by electrical faults simulation and is proposed a auxiliary trip device of RCD by using a high precision current sensor (namely, reed switch) for the prevention of electrical disasters in low voltage power distribution lines caused by overload or electric short circuit faults. The sensitive reed switch in the proposed ATD (auxiliary trip device) exactly detects the increased magnetic flux with the overload or the short current caused by a number of electrical faults, and then rapidly cuts off the existing RCD. The proposed auxiliary trip device of RCD is confirmed the excellent characteristics in response velocity and accuracy in comparison with the conventional circuit breaker through various operation performance analysis. The proposed ATD can also prevent electrical disaster, like as electrical fires, which resulted from the malfunction and inactive response characteristics of the existing RCD.

고압 차단기 동작특성 측정 및 분석용 시스템 개발 (The system development for measuring and analyzing operating characteristics of high-voltage circuit-breaker)

  • 윤지호;강윤식;김홍룡;박종화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.77-78
    • /
    • 2007
  • 국제규격에 따라 VCB(vacuum circuit breaker), ACB(air circuit breaker), 등과 같은 전력기기들의 기계적 동작 시험 시, 시험전후의 개폐시간, 개폐속도, 동작코일전류크기, 등과 같은 특성을 측정하고 이들의 변화정도를 평가하여 시험결과를 판단한다. 그러나 시험 중에는 이러한 동작특성들을 측정하지 않기 때문에, 시험 중에 실패하는 경우, 원인 규명에 많은 어려움이 따른다. 이러한 문제를 해결하기 위해, LS산전 PT&T(Power Testing & Technology Institutes)는 시험전후뿐만 아니라 전체시험횟수 동안 동작특성을 측정하고, 이들의 변화추이를 분석할 수 있는 시스템을 구축하고, 관련 소프트웨어를 개발하였다. 본 논문에서는 개발 내용과 결과를 소개하고자 한다.

  • PDF

고전압 가스 차단기용 전자석 조작기에 대한 해석 (Analysis of New Type of Switchgear for High Voltage Gas Circuit Breaker)

  • 이승민;강종호;김래은;정현교
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.872-873
    • /
    • 2008
  • In this paper, a new type of switchgear, electro magnetic force driving actuator (EMFA), is developed and analyzed, applicable to high voltage gas circuit breaker (HGCB). Transient analysis is performed in order to obtain the dynamic characteristics of the EMFA. The distribution of static magnetic flux is obtained using the finite element method (FEM). The governing electric and kinematical equations are solved using the time difference method (TDM). Fabrication and experiments were performed in order to prove the applicability of HGCB for overall class. In comparing the experiment with simulated data, it is confirmed that analysis of the dynamic characteristics of EMFA is appropriate for design.

  • PDF

Thyristor를 이용한 교류과전류 차단에 관한 연구 (A study on AC over-current breaker using thyristor)

  • 박민호;심재명
    • 전기의세계
    • /
    • 제28권7호
    • /
    • pp.49-55
    • /
    • 1979
  • 본논문은 Thyristor를 이용하여 교류회로의 고장전류를 차단하는 기구에 대한 것이다. 즉 Thyristor 한류차단회로를 설정하고 게이트제어회로 과전류검출기를 설계하고 동작과정을 확인하였다. 결과에 있어서 (1) 고속차단이 가능하다(60Hz 교류에서 4ms이내) (2) 이 방식에 의하면 차단용량을 감소시킬 수 있다. (3) 적은 신호로 지체없이 동작한다. (4) 기계적부분이 없으므로 반영구시 수명을 가진다.

  • PDF

$SF_6$ 파퍼차단기의 수학적 모델링 I : 대전류 영역 (Mathematical Modelling of $SF_6$ Puffer Circuit Breakers I : High Current Region)

  • 박경엽;박종화;신영준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1993년도 하계학술대회 논문집 B
    • /
    • pp.640-644
    • /
    • 1993
  • A mathematical arc model based on the integral method has been developed to study the arc behaviour of $SF_6$ Puffer circuit breakers during high current period. The interaction between the compression chamber and the arc interrupter plays a critical role in determining the arc behaviour. Computations have been carried out for the puffer circuit breaker of Noeske et al.[1]. The aerodynamic behaviour and electrical characteristics of the puffer circuit breaker have been investigated. In addition, the pressure rise in the compression chamber and arc voltage have been computed and the results compared with the available experimental results of Noeske et al.[1]. Special attention has been paid to the presence of the shock.

  • PDF

Re-ignition System using Vacuum Triggered Gap-switch for Synthetic Breaking Test

  • Park Seung-Jae;Suh Yoon-Taek;Kim Dae-Won;Kim Maeng-Hyun;Song Won-Pyo;Koh Hee-Seog
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제5C권4호
    • /
    • pp.145-151
    • /
    • 2005
  • The synthetic breaking test method was developed to evaluate the breaking performance of ultra high-voltage circuit breaker and made up of two independent circuits; current source circuit and voltage source circuit. In application of this test method, it is necessary to extend the arc of the test breaker. So, the new re-ignition system using VTGS (Vacuum Triggered Gap-Switch) was constructed to improve the efficiency and reliability of this test. In this re-ignition system, VTGS operates in high vacuum state of $5{\time}10^{17}$torr and control system consists of the triggering device and the air M-G (Motor-Generator). This re-ignition system showed the operating characteristics, such as delay time ($t_d$) and jitter time ($t_j$ not exceeding 5us and 1us respectively, and had the operating voltage of $25\~150kVdc$ at the gap distance of 24mm.

460V / 50KA / 100AF 급 배선용 차단기의 소호부 차단 성능 향상 방법 (Methods for Increasing the Interrupting Performance of Are Chamber in 460V / 50KA / 100AF Molded Case Circuit Breaker)

  • 조성훈;정의환;이한주;임기조;김길수
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.105-105
    • /
    • 2010
  • Voltage circuit breakers are widely used in power distribution systems to interrupt fault current rapidly and to assure the reliability of the power supply. Power distribution system requires the transformer with higher capacity than ever, but this ever, but this may be the cause. of the increasing of short circuit current in contrast to conventional one when short-circuit accident is occurred. Therefore molded case circuit breaker improved in aspects of interrupting capacity of short circuit current in this system is needed. By using the proposed methods in this paper, such as new arc quenching structure of grid would contribute to minimizing the MCCB, realization of high interrupting performance and reducing the design time and development cost.

  • PDF

단락시험 회로의 시정수 조정에 의한 투입전류 제한법 (Limiting method of short-circuit making current by controlling the time constant of dc component)

  • 박승재;류형기;강영식;고희석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.466-468
    • /
    • 2002
  • In order to newly define and specify the performance and the testing method of the high-voltage circuit breaker, IEC 62271-100 was published in May, 2001 and took place of IEC 60056 which had been used since 1987. This new standard intensifies the requirement and the test method of the circuit breaker and also domestic manufacturer makes progress the new product development. And, KERI also goes on the build-up project of short-circuit testing facilities for fulfilling the testing method requirements in new IEC 62271-100. This paper introduce the limiting method of short-circuit making current by controlling the time constant of dc component.

  • PDF

합성단락시험용 재점호장치 (Reignition system for synthetic short-circuit test)

  • 박승처;김맹현;강영식;신영준;고희석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1856-1858
    • /
    • 2000
  • This paper describes the principles of reignition system which has newly been developed and used as KERI's high power testing facilities. Synthetic short-circuit testing method is generally adopted to perform the short-circuit test of the ultra high-voltage circuit breakers, which consists of two separated sources such as the current source from short-circuit generator and the voltage source from charged energy in capacitor. And, in case of synthetic short-circuit test, it will be necessary to use the reignition system in order to extending the arcing time of the circuit breaker and provide the arc energy equivalent to the direct testing method.

  • PDF