• 제목/요약/키워드: High-Tc superconducting fault current limiter( HTSC-FCL )

검색결과 4건 처리시간 0.018초

자속구속형 고온초전도 전류제한기 사고전류제한 특성 (Fault Current Limiting Characteristic of Flux-Lock Type HTSC Fault Current Limiter)

  • 임성훈;최명호;박복기;송재주;박대희;한병성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 제4회 영호남학술대회 논문집
    • /
    • pp.105-108
    • /
    • 2002
  • In this paper, we investigated the fault current limiting characteristic of flux-lock type High-Tc superconducting fault current limiter(HTSC-FCL), which is comprised of a flux-lock reactor and an external magnetic field coil covering the HTSC element In this HTSC-FCL, the initial limiting current level can be controlled by adjusting the inductance of the each coil. Furthermore, the fault current limiting characteristics of HTSC-FCL can be improved by applying 'the external magnetic field into the HTSC element We performed the computer simulation by numerical analysis about the flux-lock type HTSC-FCL and compared the results of experiment with simulation ones. We can obtain the same results from both the computer simulation and the experiment except for the time immediately after fault occurs.

  • PDF

사고각에 따른 자속구속형 전류제한기의 전류제한특성 (Current Limiting Characteristics of Flux-Lock Type High-TC Superconducting Fault Current Limiter According to Fault Angles)

  • 박형민;임성훈;조용선;박충렬;한병성;최효상;현옥배
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.12-14
    • /
    • 2004
  • We investigated current limiting characteristics of the flux-lock type high-Tc superconcting fault current limiter(HTSC-FCL) according to fault angles. The Flux-lock type HTSC-FCL consists of primary and the secondary copper coils that are wound in parallel each other through the iron core and YBCO thin flim. In this paper, the current limiting characteristics of the flux-lock type HTSC-FCL according to fault angles in case of the subtractive and additive polarity windings were compared and analyzed. From the results, the flux-lock type HTSC-FCL could limit more quickly fault current as the fault angles increased irrespective of the fault angles. On the other hand, the initial power burden of HTSC element after a fault happened increased as the fault angles increased. In addition, it was confirmed that the resistance of flux-lock type HTSC-FCL in case of subtractive polarity winding was more increased than that of additive polarity winding and that the peak current of fault current in case of subtractive polarity winding was larger than that of the additive polarity winding case.

  • PDF

저항형 고온초전도 소자의 스위칭동작을 이용한 브리지타입 고온초전도 전류제한기의 동작 특성 (Operational Characteristics of Bride Type SFCL Using Switching Operation of Resistive Type HTSC Element)

  • 임성훈;박충렬;이종화;고석철;박형민;최효상;한병성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.83-85
    • /
    • 2004
  • We proposed the bridge type fault current limiter(FCL) using switching operation of high-Tc superconducting(HTSC) thin film. The proposed bridge type FCL consists of HTSC thin film, a diode bridge and a dc reactor. The controller for the operation of an interrupter is required in the conventional bridge type FCL to prevent the continuous increase of fault current after a fault happens. On the other hand, the proposed bridge type FCL can limit the fault current without the interrupter and the controller for its operation by the resistance generated when the gradually increased fault current exceeds HTSC thin film's critical current. We calculated the time when the gradually increased fault current started to be limited by the resistance generated in HTSC thin film after a fault happened and confirmed that it could be dependent on the amplitude of source voltage. The experimental results well agreed with the calculated ones from simulation.

  • PDF