• 제목/요약/키워드: Heating cycle

검색결과 437건 처리시간 0.035초

재열기를 사용한 고성능 VI 사이클 열펌프의 난방 성능 특성에 관한 연구 (A Study on the Characteristics of Heating Performance of High-Performance Heat Pump with VI cycle using Re-Heater)

  • 이진국;최광환
    • 동력기계공학회지
    • /
    • 제19권4호
    • /
    • pp.69-75
    • /
    • 2015
  • In this study, the characteristics of heating performance of a high-performance air-cooled heat pump with vapor-injection(VI) cycle using re-heater was investigated experimentally. Devices used in the experiment is consist of a VI compressor, condenser, oil separator, refrigerant (economizer outlet refrigerant) re-heater, economizer, evaporator. And R410A was used as a working fluid. The experiment was conducted with two cycles(cycles A and B) for investigating heating performance. In case of cycle B, heat exchange was conducted by re-heater between outlet refrigerant of compressor and suction refrigerant of the VI system(Fig.1, re-heater). But the re-heater was not used in case of cycle A. As a result of this experiment, discharge temperature of refrigerator in compressor was shown higher value, when the cycle B was conducted, because of the heat exchange between suction refrigerant of VI cycle and outlet refrigerant of compressor in the re-heater than cycle A that was not use re-heater. it means that liquid hammer and the decrement of heating performance can be decreased by using re-heater. Also, Heating coefficient of performance(COPh) was shown about 2.98 in Cycle B which was 4% higher than Cycle A and from these results, It was confirmed that the improvement of the heating performance of heat pump with VI cycle can be achieved by applying re-heater.

가변속 이산화탄소 열펌프의 난방성능 특성에 관한 실험적 연구 (Experimental Study on the Heating Performance of a Variable Speed CO2 Heat Pump with a Variation of Operating Conditions)

  • 조홍현;이호성;장용희;김용찬
    • 대한기계학회논문집B
    • /
    • 제31권8호
    • /
    • pp.694-701
    • /
    • 2007
  • The applications of a transcritical $CO_2$ cycle into water heaters show advantages over conventional systems in the respect of power consumption and heating efficiency because the $CO_2$ cycle has a high compressor discharge temperature. Besides, the heating performance of the transcritical $CO_2$ cycle can be improved by optimizing operating conditions. In this study, the heating performance of a variable speed $CO_2$ heat pump was measured and analyzed by varying refrigerant charge amount, EEV opening, compressor frequency and outdoor temperature. As a result, the optimum normalized charge for heating was 0.226. The COPs at the compressor frequencies of 40, 50 and 60 Hz were 2.94, 2.75 and 2.25, respectively. The heating performance of the $CO_2$ cycle with charge amount was more sensitive than the cooling performance. Moreover, the heating performance was improved significantly by optimizing of compressor frequency and EEV opening.

저온수2단흡수냉난방기의 개발 (Development of Single effect/Double lift Absorption Chiller & Heater for a District Heating Net work)

  • 구기동;김상호;류진상;이재영;서종철;장훈
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.668-672
    • /
    • 2009
  • This is to report the result of Development of Single effect/Double lift absorption chiller & heater which is used in the district heating net work. The heating cycle was newly developed to make the secondary hot water from evaporator and the cycle change-over function was added for the heating to the cooling mode and the cooling to the heating mode. Finally, it was assured through the site trial operation that the outlet temperature of primary hot water can be produced lower than $68^{\circ}C$ when the outlet temperature of secondary hot water is $60^{\circ}C$.

  • PDF

냉각공기 예냉각과 연료예열에 의한 복합발전 시스템의 성능변화 (Performance Variation of a Combined Cycle Power Plant by Coolant Pre-cooling and Fuel Pre-heating)

  • 권익환;강도원;김동섭;김재환
    • 한국유체기계학회 논문집
    • /
    • 제15권3호
    • /
    • pp.57-63
    • /
    • 2012
  • Effects of coolant pre-cooling and fuel pre-heating on the performance of a combined cycle using a F-class gas turbine were investigated. Coolant pre-cooling results in an increase of power output but a decrease in efficiency. Performance variation due to the fuel pre-heating depends on the location of the heat source for the pre-heating in the bottoming cycle (heat recovery steam generator). It was demonstrated that a careful selection of the heat source location would enhance efficiency with a minimal power penalty. The effect of combining the coolant pre-cooling and fuel pre-heating was also investigated. It was found that a favorable combination would yield power augmentation, while efficiency remains close to the reference value.

AC Cycles 가변을 이용한 PTC 발열체의 전력제어 (Power control of PTC heating element using variable AC Cycles)

  • 공재웅;이영주;김두영
    • 융합신호처리학회논문지
    • /
    • 제12권4호
    • /
    • pp.355-361
    • /
    • 2011
  • 기존 발열체의 전력제어는 On-Off 제어, 위상제어, PWM 제어를 사용해왔다. 최근 개발된 PTC 발열체를 기존의 방법으로 전력제어를 하였을 경우, 온도를 정밀하게 제어하지 못하고 인체에 유해한 전자파가 발생한다. 본 논문은 AC Cycles 가변을 이용한 PTC 열선의 전력 제어를 제안한다. 이것은 N개의 교류 cycle을 전력 제어의 단위로 간주하여, 각 cycle 마다 On-Off 여부를 결정하여 N cycles 내의 on-cycle 을 랜덤하게 배치하여 지속적으로 AC전력제어방법이다. 이 때 최소 전력량은 1/N이 되고 최대 전력량은 1이 되며 설정 값에 따라 on cycle의 수를 설정하여 N개의 단계로 일정하게 전력을 제어할 수 있다. PTC 열선과 온도센서를 사용한 발열 시스템에서 제안한 전력제어 방식이 전자파 발생과 온도제어 특성에서 우수함을 MATLAB simulation과 실험 및 측정을 통하여 확인하였다.

LCC 기법을 이용한 영구임대아파트 난방방식 리모델링에 대한 경제성분석 -유지관리비용을 중심으로- (The Economic Analysis on the Heating System Remodeling by the Life Cycle Costing in Permanent Rental Apartment)

  • 박민용;장승재
    • 한국주거학회논문집
    • /
    • 제15권1호
    • /
    • pp.33-40
    • /
    • 2004
  • Considering the present development situation of rental apartment since 1982, the supply of rental housing for low-income dwellers has contributed a amount of quantities, but has been deficient qualities in housing policy. To propose the device of remodeling for low-income dwellers in deteriorated apartment, this study investigated the energy consumption of central heating system and the characteristics of maintenance cost in permanent rental apartment. The results of evaluation of alternative heating systems by Life Cycle Costing in permanent rental apartment were as follows; From Life Cycle 15∼20 years by Present Worth Method, the economic heating system of remodeling is central heating system (heat source: B-C oil), unit heating system(natural gas), central heating system(natural gas) in order.

태양열과 재열기를 사용한 VI heat pump의 성능 특성에 관한 연구 (Heating Performance Characteristics of Heat Pump with VI cycle using Re-Heater and Solar-Assisted)

  • 이진국;최광환
    • 한국태양에너지학회 논문집
    • /
    • 제35권6호
    • /
    • pp.25-33
    • /
    • 2015
  • In this study, heating performance of the air-cooled heat pump with vapor-injection (VI) cycles, re-heater and solar heat storage tank was investigated experimentally. Devices used in the experiment were comprised of a VI compressor, re-heater, economizer, variable evaporator, flat-plate solar collector for hot water, thermal storage tank, etc. As working fluid, refrigerant R410A for heat pump and propylene glycol (PG) for solar collector were used. In this experiment, heating performance was compared by three cycles, A, B and C. In case of Cycle B, heat exchange was conducted between VI suction refrigerant and inlet refrigerant of condenser by re-heater (Re-heater in Fig. 3, No. 3) (Cycle B), and Cycle A was not use re-heater on the same operating conditions. In case of Cycle C, outlet refrigerant from evaporator go to thermal storage tank for getting a thermal energy from solar thermal storage tank while re-heater also used. As a result, Cycle C reached the target temperature of water in a shorter time than Cycle B and Cycle A. In addition, it was founded that, as for the coefficient of heating performance($COP_h$), the performance in Cycle C was improved by 13.6% higher than the performance of Cycle B shown the average $COP_h$ of 3.0 and by 18.9% higher than the performance of Cycle A shown the average $COP_h$ of 2.86. From this results, It was confirmed that the performance of heat pump system with refrigerant re-heater and VI cycle can be improved by applying solar thermal energy as an auxiliary heat source.

저온 해수를 이용한 난방 및 담수화사이클 성능 해석 (Analysis of Heating and Desalination Cycle Using Low Temperature Seawater)

  • 이호생;이승원;정동호;문덕수;김현주
    • 한국해양환경ㆍ에너지학회지
    • /
    • 제14권4호
    • /
    • pp.301-306
    • /
    • 2011
  • 저온 해수에너지를 이용한 난방사이클 및 이와 연계할 수 있는 적정 담수화사이클에 대하여 제안 및 해석을 수행하였다. 난방사이클은 기본 증기압축식 사이클을 이용하여 1단 및 2단압축사이클에 대해 해석을 수행하였고, 담수화사이클은 난방사이클과 연계할 수 있도록 설계하여 해석을 수행하였다. 난방사이클의 증발기 열원으로 5이하의 저온 해수열을 이용하였고, 난방수 온도는 60 이상 공급될 수 있도록 해석하였으며, 사이클 작동유체는 R-134a, R-1234 yf, R-600a를 적용하였다. 사이클 해석 결과, 2단압축사이클을 적용할 경우 1단압축사이클에 비해 모든 냉매에서 압축기 소요동력은 약 15.6% 감소하였고, 성능계수는 약 17.6% 향상되었다. 냉동법 담수화 사이클의 경우 R-134a에 대해서 난방수 60 조건일 때, 1단압축 사이클에 비해 2단압축사이클을 적용할 경우 담수 1kg 생산당 에너지가 약 19.8% 감소하는 것으로 나타났다.

자동차용 고장력 강판의 열처리에 관한 연구 (A Study on the Annealing of High Tensile Strength Steel for Automobile)

  • 박범식
    • 한국공작기계학회:학술대회논문집
    • /
    • 한국공작기계학회 1999년도 추계학술대회 논문집 - 한국공작기계학회
    • /
    • pp.530-535
    • /
    • 1999
  • In recently, annealing process of cold rolled sheet tend to change to continuous annealing process for improving quality, saving yield. In the meantime as demand for various kind and small lot of products has been increasing, batch annealing has been appreciated for its small restriction for the operation. So, we tested on the effect for the proper heating temperatures, heating time of cycle, cooling time and total cycle time in this annealing process of hi tensile strength steel for automobile. As a result of several investigation. we confirmed for the following characteristics; In this process, we knew that 68$0^{\circ}C$ is suitable for this heating temp. cycle heating time of 38 Hr, cooling time of 31 Hr and total cycle time of 70 Hr. Still more, we could know that it is proper for cold rolling before annealing to be managed by 7 pass because of the act on high pressure.

  • PDF

가열금형을 사용하는 강철과 알루미늄 이종금속판재의 전기저항 이중스폿용접 (Electric Resistance Double Spot Welding Process of Dissimilar Metal Plates of Steel and Aluminum by Using Heating Dies)

  • 김태현;;진인태
    • 소성∙가공
    • /
    • 제27권1호
    • /
    • pp.37-47
    • /
    • 2018
  • In this paper, a double spot welding process, utilizing electric resistance heating dies, is suggested for the spot welding of dissimilar metal plates for drawing and concurrent spot welding. This double welding process has two heating methods for the fusion welding at the interfacial zone between steel and aluminum plates, such as heating method by thermal conduction of electric resistance by welding current induced to heating dies, and heating method by electric resistance between contacted surfaces of two plates by welding current induced to copper electrode. This double welding process has welding variables such as each current induced in heating dies and in copper electrode, outer diameters of heating dies, and edge shape of copper electrode. Experiments for current conditions in welding process should be demanded in order to get successful welding strength. It was known that the welding strength could be reached to the value demanded on industry fields under such welding conditions as heating dies of outer ring dia.12mm contacted on steel plate, as heating dies of outer ring dia. 14mm contacted on aluminum plate, and as copper electrode of dia. 6.0mm, and as 3 times continuous heating method by $1^{st}$ current of 11 kA(9cycle), $2^{nd}$ current 11 kA(60cycle), $3^{rd}$ current 7 kA(60cycle) applied in steel heating dies and copper electrodes, flat edge of copper electrode, for double spot welding process of dissimilar metal plates of steel and aluminum of 1.0 mm thickness.