공동주택 공기열 멀티 히트펌프의 바닥난방 성능 평가 (Performance Evaluation of Air Source Multi Heat Pump Floor Heating System in Apartment)

  • 이철희;나환선;정훈;김강식
    • 한국기계기술학회지
    • /
    • 제13권3호
    • /
    • pp.93-98
    • /
    • 2011
  • To analyze and evaluate the performance of developing air to water multi heat pump, the heat pump was installed and tested at low energy house in Daejeon, korea. Heating capacity of heat pump is 16.5KW and cooling capacity is 14.0KW. Space heating/cooling, floor heating and hot water is available. The results performance evaluation of heat pump in lab test showed that the coefficient of performance (cop) was 3.75, and heating capacity was 16.0KW in ambient temperature $7^{\circ}C$. Also at ambient temperature $-15^{\circ}C$, the COP was 1.69. At a low energy house, floor heating is controled by a floor heating water temperature and a room temperature. The COP of heat pump is decreased with frequent on/off operation for controlling of floor heating water temperature.

열원 및 부하조건에 따른 물-공기 히트펌프 시스템의 성능분석 (Performance Analysis of Water-to-Air Heat Pump System under Water Temperature and Load Ratio)

  • 조용;이동근
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2011년도 춘계학술대회 초록집
    • /
    • pp.194.2-194.2
    • /
    • 2011
  • Heating and cooling performance has been analyzed for the water-source heat pump system using raw water from Daechung reservoir. During heating operation from March to May, water temperature is not good condition for a heat source due to the higher atmospheric temperature. Avearged heating load ratio is only 14.3%, and the averaged unit COP and system COP are estimated to be 2.46 and 2.15 respectively. The COP is affected considerably by the water temperature, and the unit COP is increased from 2.16 at $5^{\circ}C$ to 2.95 at $11^{\circ}C$. Cooling performance is analyzed with the measured data from June to August. During cooling operation, raw water has lower temperature by 4. $5^{\circ}C{\sim}4.7^{\circ}C$ than the atmosphere. The load ratio is 39.2%, and the averaged unit COP and system COP are estimated to be 7.25 and 6.13 respectively. The heating COP is affected by the load ratio rather than water temperature. The COP is increased for 20%~40% load ratio, while is decreased for 40%~60% load ratio. It is estimated that the compressor operation combination for 3 (two constant speed and one inverter) compressors is changed for the load ratio.

  • PDF

건축물 용도별 내부 발열부하에 따른 수열원, 지열원 및 하이브리드 히트펌프 시스템의 에너지 성능 비교 분석 (Comparative Analysis of Energy Performance of Hydrothermal, Geothermal Source and Hybrid Heat Pump System According to Internal Heat Load for Office, School and Smart Farm)

  • 박시훈;민준기
    • 한국지열·수열에너지학회논문집
    • /
    • 제18권3호
    • /
    • pp.19-30
    • /
    • 2022
  • In this study, comparative analysis of energy performance in Taebaek city, a test area, by applying hydrothermal, geothermal source and hybrid heat pump system to office, school and smart farms with different internal heat loads. The conclusion is as follows. In the load characteristics by use of buildings, it was found that office had a large cooling load compared to heating load, school had a large heating load compared to cooling load, and smart farm had only cooling load year-round. Performance analysis of the heat pump system in office shows that the cooling COP of the hydrothermal source is 5.12% and the heating COP is 3.22% lower based on the geothermal source, the cooling COP of the hybrid is 0.41% higher, and the heating COP is the difference in performance appeared sparsely. The performance analysis of the heat pump system in school showed that the cooling COP of the hydrothermal source was 10.44% and the heating COP 3.22% lower based on the geothermal source, and the performance difference between the hybrid cooling and heating COP was insignificant. Heat pump system performance analysis in smart farm only occurred with cooling load. Based on geothermal sources, the cooling COP of the hydrothermal source was 46% and the cooling COP of the hybrid was 19.65%, respectively.

냉.온열 동시 제조시스템의 성능분석(I)-Simulation (Performance Analysis of Simultaneous Heating & Cooling Water Making System(I)-Simulation)

  • 박성룡;박준택;안영훈
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집D
    • /
    • pp.266-271
    • /
    • 2001
  • In this study, the performance of the simultaneous heating & cooling water making system using R134a was investigated by simulation. The most important effect upon heating COP was intermediate pressure depending on input water temperature. With the input water temperature of $10^{\circ}C\;and\;20^{\circ}C$, optimum intermediate pressure were 923 and 1040kPa, respectively. At that optimum intermediate pressure, the maximum heating COP of the system operated between $0^{\circ}C$ evaporating temperature and $70^{\circ}C$ condensing temperature were 4.15 and 3.83. With installation of the subcoolers in high or low pressure section, the system COP was increased by reducing the refrigerant mass flow rate. Under the optimum pressure and $10^{\circ}C$ input water temperature, it was found that heating COP was maximized when the low-subcooler and high-subcooler capacity rate were taken by 14% and 13%, respectively.

  • PDF

물-물 수온차 히트펌프 시스템의 원수온도에 따른 성능 특성 분석 (Analysis on Cooling and Heating Performance of Water-to-Water Heat Pump System for Water Source Temperature)

  • 박태진;조용;박진훈
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.169.2-169.2
    • /
    • 2010
  • The research assesses the performance of the water-to-water heat pump system installed in Cheongju water treatment plant for cooling and heating ventilation. In summer season monthly averaged COP is ranged from 3.85 to 4.56 according to the water source temperature, and the performance is increased as the raw water temperature is dropped. While, heating performance is increased for the high temperature water source, and the monthly averaged COP is changed from 2.92 to 3.82. The correlation of the water source temperature and the heat pump performance shows a linear tendency by the simple regression of average data. In heating, the COP of heat pump system linearly rises according to the water source temperature. In comparison, the COP in cooling linearly reduces as the raw water temperature is raised. The goodness of fit at the simple regression shows the coefficient of determination 82% in cooling, 46% in heating. The electric cost of water-to-water heat pump is reduced by 40% compared to that of air source heat pump.

  • PDF

지열 히트펌프에서 운전변수가 냉난방 성능에 미치는 영향에 대한 실험연구 (An Experimental Study on the Effects of Operating Variables on the Cooling and Heating Performance of Geothermal Heat Pump)

  • 장근선;강희정
    • 설비공학논문집
    • /
    • 제23권8호
    • /
    • pp.562-570
    • /
    • 2011
  • In this research, an experimental study is performed to investigate the effects of system operating variables on the cooling and heating characteristics of heat pump system using geothermal heat source and carbon dioxide as a refrigerant. System variables analyzed include compressor frequency, electronic expansion valve opening, refrigerant charge, secondary fluid temperature and flow rate. Results show that optimum refrigerant charge and electronic expansion valve opening position exist at the maximum point of COP curve, and both cooling and heating capacity increase but COPs decrease with the increase of compressor frequency. The change of a secondary fluid temperature leads to variation of overheat area and enthalpy difference in the evaporator and gas cooler. which again results in considerable variations of cooling and heating capacity and COP. In the case of effects of secondary water fluid flow rate, both cooling capacity and COP increase with the increase of secondary flow in evaporator or gas cooler, whereas heating capacity and COP decrease with the increase of flow rate in gas cooler.

3실 열펌프의 운전조합에 대한 난방성능 실험연구 (Experimental Study on Heating Performance by Operation Combination of Heat Pump with 3 Indoor-Units)

  • 김주형;김기영;권영철;박승철
    • 한국산학기술학회논문지
    • /
    • 제14권9호
    • /
    • pp.4197-4203
    • /
    • 2013
  • 본 실험연구는 인버터 압축기를 적용한 실내기 3실을 가진 멀티형 열펌프 시스템의 난방운전 시 열펌프의 난방성능을 연구하였다. 멀티형 열펌프의 운전특성은 항온항습 기능을 가진 공기엔탈피방식의 멀티형 칼로리미터를 이용하여 측정되었다. 난방표준 및 난방저온 온도조건에서 실내기 운전조합에 따른 실험을 수행하여 난방성능 변화를 관찰하였다. 실내기 3실을 가진 열펌프의 실내기 운전조합에 따른 난방표준 및 난방저온 운전에서 난방능력, 난방 COP, P-h선도로부터, 3실을 가진 열펌프의 운전특성과 냉매 사이클의 거동을 조사하였다. 열펌프의 운전부하와 성능은 실내기 조합에 의한 부분부하에 의존하므로 열펌프의 난방능력과 사이클의 거동은 다르게 관찰되었다. 표준온도 시험조건 대비 저온 시험조건의 난방능력과 난방 COP는 감소하였다. 또한 실내기 조합에 대한 냉매사이클은 P-h 선도를 사용하여 분석되었다.

강변여과수 열원 히트펌프 온실난방 성능시험 (Estimation of Greenhouse Heating performance for Ground Filtration Water Source Heat Pump)

  • 문종필;이성현;권진경;강연구;이수장
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2011년도 춘계학술대회 초록집
    • /
    • pp.200.2-200.2
    • /
    • 2011
  • This study was carried out in order to estimate the greenhouse performance for Ground filtration water source heat pump which was installed for supplying the heat to the paprika greenhouse in Jinju city. Experimental area of Greenhouse was $3,300m^2$, For keeping the heat from greenhouse, single plastic covering and double thermal screen was installed. With considering all of greenhouse insulation condition and designed heatng temperature, heating capacity for experimental greenhouse was calculated as 320,000kcal/hr. Coefficient of performance(COP) of Ground filtration water source heat pump was gauged and greenhouse heating performance was tested from Febuary 1 to Febuary 28 in 2011. The result showed that COP of heat pump was in the range of 3.7~4.7 and COP of heating system was in the range of 3.0~3.5. The vaule of COP was very high and the temperature inside greenhouse was well corresponded to the setting temperature of greenhouse environment controlling system. lots of Ground filtration water made the the number of well fewer and the expense for installing heating system cheaper than that of geothermal system used custmarily. and this system went beyond the limitation of intaking amount of groundwater in normal Groundwater source heat pump.

  • PDF

지열히트펌프의 작동시간 경과에 따른 COP 변화에 대한 연구 (Study on COP Variations with the duration of Ground Source Heat Pump Systems Operation)

  • 이용규;백남춘;윤응상
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.198.2-198.2
    • /
    • 2010
  • In this study, the COP variation with the duration of Ground Source Heat Pump (GSHP) systems operation was analyzed by experiment. This experimental facility was installed in residential house as a back-up device of solar thermal heating system. The capacity of heat pump is 2.5 kW with a vertical bore hole of 150m depth. The COP of GSHP is varied, depending on the ground temperature which is used as a heat source. The ground heat source temperature influencing heating COP is the soil or rock temperature which adjoin with geo-source heat exchanger. This temperature is decreased rapidly according to the operation duration of heat pump. As a result, COP of GSHP is decreased to 3 in one hour of continuous operation time.

  • PDF

지열원 물대공기 멀티 히트펌프의 일일 난방 운전 특성에 관한 실증 연구 (Daily Heating Performance of a Ground Source Multi-heat Pump at Heating Mode)

  • 최종민;임효재;강신형;문제명;김록희
    • 설비공학논문집
    • /
    • 제21권9호
    • /
    • pp.527-535
    • /
    • 2009
  • The aim of this study is to investigate the daily heating performance of ground source multi-heat pump system with vertical single U-tube type GLHXs, which were installed in a school building located in Cheonan. Daily average COP of heat pump unit on Jan. 12th, 2009 at heating mode was lower than it on Nov. 10th, 2008 and Dec. 15th, 2008, because of lower EWT of the outdoor heat exchanger and relatively smaller size of condenser and evaporator. But, the system COP on the former was higher than it on the latter because ground loop circulating pump was operated in rated speed. It is suggested that the new algorithms to control the flow rate of secondary fluid for GLHX according to load change have to be developed in order to enhance the performance of the system COP.