Browse > Article
http://dx.doi.org/10.17664/ksghe.2022.18.3.0019

Comparative Analysis of Energy Performance of Hydrothermal, Geothermal Source and Hybrid Heat Pump System According to Internal Heat Load for Office, School and Smart Farm  

Park, Sihun (Department of Mechanical Engineering, KyungHee University)
Min, Joonki (Department of Mechanical Engineering, KyungHee University)
Publication Information
Journal of the Korean Society for Geothermal and Hydrothermal Energy / v.18, no.3, 2022 , pp. 19-30 More about this Journal
Abstract
In this study, comparative analysis of energy performance in Taebaek city, a test area, by applying hydrothermal, geothermal source and hybrid heat pump system to office, school and smart farms with different internal heat loads. The conclusion is as follows. In the load characteristics by use of buildings, it was found that office had a large cooling load compared to heating load, school had a large heating load compared to cooling load, and smart farm had only cooling load year-round. Performance analysis of the heat pump system in office shows that the cooling COP of the hydrothermal source is 5.12% and the heating COP is 3.22% lower based on the geothermal source, the cooling COP of the hybrid is 0.41% higher, and the heating COP is the difference in performance appeared sparsely. The performance analysis of the heat pump system in school showed that the cooling COP of the hydrothermal source was 10.44% and the heating COP 3.22% lower based on the geothermal source, and the performance difference between the hybrid cooling and heating COP was insignificant. Heat pump system performance analysis in smart farm only occurred with cooling load. Based on geothermal sources, the cooling COP of the hydrothermal source was 46% and the cooling COP of the hybrid was 19.65%, respectively.
Keywords
Geothermal heat pump; Hydrothermal heat pump; Hybrid heat pump; Office; School; Smart Farm;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Park, S., Han, H., Hong, H., and Min, J., 2021, A Study on Energy Performance Evaluation of Combined Heat Source Heat Pump System Consisting of Ground and Water Sources in Smart Farm, Korean Journal of AirConditioning and Refrigeration Engineering, Vol. 33, No.11, pp. 608-618.   DOI
2 Ko, Y., Park, S., and Min, J., 2020, Comparison of Heat Pump Performance and Energy Consumption Patterns according to Heat Sources for Optimal Control of Multi-Source Heat Pumps, Korea Society for Geothermal and Hydrothermal Energy, Vol. 16, No. 4, pp. 31-38.
3 Park, S., Ko, Y., and Min, J., 2021, A Study on the Performance Evaluation of Combined Heat Pump System according to the Ratio of Ground Heat Source and Water Heat Source, Korea Society for Geothermal and Hydrothermal Energy, Vol. 17, No. 2, pp. 11-19.
4 Passive House Institude Korea, 2017, Standard of Weather Data in Korea.
5 Ministry of Land, Infrastructure and Transport, 2017, Standard of Building Saving, MLIT criteria 2017-881.
6 Yang, C. H., Kim, Y., and Chung, K. S., 2012, Economical Analysis of a Small Capacity Heat Pump utilizing Heat Sources of Air, Geothermal and Underground Water Tank using Dynamic Simulation, Korea Society for Geothermal and Hydrothermal Energy, Vol. 8, No. 4, pp. 17-33.
7 Park, S., Kim, J., and Min, J., 2021, A Study on Comparative Analysis of Energy Performance of Hybrid Heat Pump System Using Ground Heat Source and Water Heat Source, Korea Society for Geothermal and Hydrothermal Energy, Vol. 17, No. 4, pp. 59-67.
8 Oh, J., Bae, S., Kwon, Y., and Nam, Y., 2022, Performance and Economic Analysis of Water Source Heat Pump System According to Water Intake Distance and Capacity, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 34, No. 5, pp. 244-251.   DOI
9 Kwon, Y., and Nam, Y., 2022, Annual Performance Analysis of River Water Source Heat Pump System According to Building Type and Condition, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 34, No. 4, pp. 163-171.   DOI
10 Kwon, Y., Bae, S., Nam, Y., Park, C. Y., and Lee, H., 2021, Comparative Analysis of System Performance for Water, Ground and Air Source Heat Pump System Using the Dynamic Energy Simulation, Journal of the Korean Solar Energy Society, Vol. 41, No. 4, pp. 1-12.
11 Yang, W. S., Kim, Y. I., and Park, S. T., 2020, Performance Comparison of Electric Heater, Air Source and Geothermal Source Heat Pump type Agricultural Hot Air Dryer with Cycle Analysis, Vol. 32, No. 3, pp. 135-145.
12 Klein, S. A., 2019, TRNSYS18 Base Manual, KESTech, Kocaeli, Turkey.
13 Ministry of Trade, Industry and Energy, 2022, Energy Use Rationalization Method's Indoor Temperature.
14 Korea Institute of Civil Engineering and Building Technology, 2015, Development of Installation Method of a Removal Heat Exchanger on the Ground for the Use of Geothermal Energy.
15 National Academy of Environmental Sciences, 2020, Bonghwa Measurement Station Water Temperature Data.
16 ASHRAE Handbook, 2013, Internal Heat Load.
17 T. City, 2022, T-Eco Job City Smart Farm project's HVAC criteria.