Performance analysis of a R744 and R404A cascade refrigeration system with internal heat exchanger (내부 열교환기 부착 R744-R404A용 캐스케이드 냉동시스템의 성능 분석)

  • Oh, H.K.;Son, C.H.
    • Journal of Power System Engineering
    • /
    • v.16 no.1
    • /
    • pp.38-43
    • /
    • 2012
  • This paper describes an analysis on performance of R744-R404A cascade refrigeration system with internal heat exchanger to optimize the design for the operating parameters of the system. The operating parameters considered in this study include subcooling and superheating degree, internal heat exchanger and compression efficiency, evaporating and condensing temperature in the R744 low- and R404A high-temperature cycle and temperature difference of cascade heat exchanger. The main results are summarized as follows : COP of cascade refrigeration system increases with the increasing of compression efficiency, but decreases with the increasing temperature difference of cascade heat exchanger. Also, the COP increases with the increasing of internal heat exchanger efficiency in high-temperature cycle, but decreases with that in low-temperature cycle. Therefore, internal heat exchanger efficiency, compressor efficiency and temperature difference of cascade heat exchanger on R744-R404A cascade refrigeration system have an effect on the COP of this system.

Heat transfer analysis on the heat exchanger of a stirling cycle machine (스터링 사이클 기기 열교환기의 열전달 해석)

  • Lee, Dae-Yeong;Jo, Gwan-Sik;No, Seung-Tak;Kim, Byeong-Ha
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.20 no.4
    • /
    • pp.1385-1394
    • /
    • 1996
  • A theoretical analysis was performed on the heat transfer by laminar oscillating flow in a simplified heat exchanger of a Stirling cycle machine and the results were compared with the experiment of Hwang. In the analysis the general solution to the temperature field obtained by Lee et. al was applied and extended to a more realistic situation. The results show that the heat transfer is influenced by the ratio of the swept distance of the fluid to the length of the heat exchanger as well as the oscillation frequency. This is well consistent with the result of Hwang's experiment. It is also revealed that there exist three distinct regimes having different heat transfer mechanisms. Through the scale analysis the main parameters governing the heat transfer in each regime are reduced and the dependency of the heat transfer on the parameters are examined.

The operational condition of the refrigeration cycle taking into account of heat transfer processes and heat loss of the cold heat source (熱傳達 및 熱損失을 考慮한 冷凍사이클의 運轉條件)

  • 김수연;정평석;정인기
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.12 no.1
    • /
    • pp.48-52
    • /
    • 1988
  • For the refrigeration system using the reversed Carnot cycle, maximum conditions of effectiveness and available energy output are studied with taking into account of the heat transfer between heat sources and the cycle, and of the heat loss due to heat leakage into the cold heat source. The extremum of the effectiveness exists for variables T$_{l}$ and T$_{L}$. Therefore the desirable results in engineering applications that available energy output is not zero under maximum condition of the effectiveness are obtained. In addition, the extremum of the available energy output does not exist for the variable T$_{l}$ but does for the variable T$_{L}$. As the heat loss increases, the available energy output and the effectiveness decrease, the regions of T$_{l}$ and T$_{L}$ where the refrigeration system is possible to operate become smaller.aller.

Performance Characteristics and Economic Assessment of a River Water: Source Heat Pump System (하천수 열원 열펌프 시스템의 성능 특성 및 경제성 평가)

  • Park, Cha-Sik;Jung, Tae-Hun;Park, Hong-Hee;Kim, Yong-Chan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.11
    • /
    • pp.621-628
    • /
    • 2009
  • The objectives of this study are to analyze the performance of a river water-source heat pump and to carry out economic assessment for the heat pump. The COP of the river water-source heat pump was 3-21% higher than that of the air-source heat pump because river water provides stable operating temperature compared with air temperature throughout the year. The economic analysis was carried out by comparing the initial and operating cost of the river water-source heat pump with those of the conventional air-source heat pump. The ratio of the life cycle operating cost to the life cycle cost increased with the increase of building capacity. The payback period was found to be less than 3.5 years when the capacity of the river water-source heat pump was larger than 10 RT.

Experimental Study on the Cooling Performance Improvement of a Two-stage Compression $CO_2$ Cycle (2단압축 이산화탄소 사이클의 냉방성능 향상 특성에 대한 실험적 연구)

  • Cho Hong-Hyun;Lee Ho-Seong;Kim Yong-Chan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.10
    • /
    • pp.835-841
    • /
    • 2006
  • A $CO_2$ system using the two-stage compression cycle was tested by varying $1^{st}-2^{nd}$ compressor frequencies in the cooling mode. To improve the cooling performance of the two-stage compression $CO_2$ cycle, the following cycle options were applied: a basic cycle, a cycle with an intercooler, a cycle with an IHX (internal heat exchanger), and a cycle with an intercooler and IHX. The cycle with the intercooler-IHX showed the highest cooling capacity improvement among the cycle options at all compressor frequencies. The cycle with the intercooler, the cycle with the IHX, and the cycle with the intercooler-IHX improved the cooling COP by 7, 12, and 15%, respectively, over the basic $CO_2$ cycle when the compressor frequencies for the first and second compressors were 50 Hz and 30 Hz, respectively. In addition, the applications of the selected cycle options enhanced system reliability.

Study on the Performance of Heat Pump Using Non-azeotropic Refrigerant Mixtures R-22+R-114 (비공비혼합냉매 R-22+R-114를 이용한 열펌프의 성능에 관한 연구)

  • 박기원;구학근;오후규
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.17 no.9
    • /
    • pp.2131-2137
    • /
    • 1993
  • This study, examines the performance and the heat pump cycle systematizing characteristics for non-azeotropic refrigerant systems. In order to conduct such an examination, the cycle characteristics of heat pumps for pure R-22, R-114, and their mixtures were experimentally investigated. The results show that cooling/heating capacities for the mixtures was more suited at the evaporating temperature of $5^{\circ}C$ than that of $0^{\circ}C$, $-5^{\circ}C$, and $-10^{\circ}C$. The C.O.P of the 50 wt% mixtures was considerably higher than for pure R-22, and the compression power of the 25 wt% was as much as 60% lower than that of pure R-22. Even small fractional mixture variations can lead to significant changes in the characteristics of the heat pump cycle. This experiment verified the importance of accurate weight fractions of refrigerant mixtures.

Changes of Low Cycle Fatigue Behavior of AI-Mg-Si Alloy with Severe Plastic Deformation and Heat Treatment (강소성 가공 및 열처리에 의한 Al-Mg-Si합금의 저주기 피로특성변화)

  • Kim, W.H.;Kwun, S.I.
    • Journal of the Korean Society for Heat Treatment
    • /
    • v.22 no.4
    • /
    • pp.217-222
    • /
    • 2009
  • The effects of severe plastic deformation by equal channel angular pressing (ECAP) and subsequent heat treatment on the low cycle fatigue behaviors of Al-Mg-Si alloy were investigated. The specimens which were peak aged at $175^{\circ}C$ after solution treatment showed cyclic hardening at all strain amplitudes, while the specimens ECAPed after solution treatment showed cyclic softening at all strain amplitudes during fatigue. The specimens aged at $100^{\circ}C$ after ECAP showed slight cyclic hardening. Various changes of cyclic fatigue behavior after severe plastic deformation and/or heat treatment were discussed in terms of the microstructural changes and precipitation conditions.

Oplimum Design Conditions for a Basic Refrigeration Cycle (냉동사이클의 최적 설계조건)

  • Cho, Sung-Whan
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.15 no.4
    • /
    • pp.356-361
    • /
    • 1986
  • An optimum design condition for a basic refrigeration cycle is defined as the condition which minimizes the total cost of heat exchanges (condenser and evaporator) and compressor for the refrigeration effect. Thermodynamic properties of ammonia (R717) are approximated by rational functions in order to obtain the optimum condition for a basic refrigeration cycle. Optimum condition depends on the heat capacity rates (mass flow rate times specific heat) of cooling water and brine used in condenser and evaporator. The difference between the cooling water temperature and condensation temperature at the optimum condition increases as the heat capacity rates and the coat of heat exchangers relative to the cost of compressor increase. Numerical examples of optimum conditions are obtained when the condensation temperature is $30^{\circ}C$ and the evaporator temperature is $-10^{\circ}C$.

  • PDF

A dual Pressure, Steam Injection Combined cycle Power Plant Performance Analysis (2압, 증기분사 복합발전 사이클에 대한 성능해석)

  • Kim, Su-Yong;Son, Ho-Jae;Park, Mu-Ryong;Yun, Ui-Su
    • 연구논문집
    • /
    • s.27
    • /
    • pp.75-86
    • /
    • 1997
  • Combined cycle power plant is a system where a gas turbine or steam turbine is used to produce shaft power to drive a generator for producing electrical power and the steam from the HRSG is expanded in a steam turbine for additional shaft power. Combined cycle plant is a one from of cogeneration. The temperature of the exhaust gases from a gas turbine ranges from $400^\circC$ to $600^\circC$, and can be used effectively in a heat recovery steam generator to produce steam. Combined cycle can be classed as a "topping(gas turbine)" and a "bottoming(steam turbine)" cycle. The first cycle, to which most of the heat is supplied, is called the topping cycle. The wasted heat it produces is then utilized in a second process which operates at a lower temperature level and is therefore referred to as a "bottoming cycle". The combination of gas/steam turbine power plant managed to be accepted widely because, first, each individual system has already proven themselves in power plants with a single cycle, therefore, the development costs are low. Secondly, the air as a working medium is relatively non-problematic and inexpensive and can be used in gas turbines at an elevated temperature level over $1000^\circC$. The steam process uses water, which is likewise inexpensive and widely available, but better suited for the medium and low temperature ranges. It, therefore, is quite reasonable to use the steam process for the bottoming cycle. Only recently gas turbines attained inlet temperature that make it possible to design a highly efficient combined cycle. In the present study, performance analysis of a dual pressure combined-cycle power plant is carried out to investigate the influence of topping cycle to combined cycle performance.

  • PDF

Performance Analysis of a Combined Cycle of Kalina and Absorption Refrigeration for Recovery of Low-Temperature Heat Source (저온 열원의 활용을 위한 칼리나/흡수냉동 복합사이클의 성능 해석)

  • KIM, KYOUNG HOON;KO, HYUNG JONG;JUNG, YOUNG GUAN
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.29 no.5
    • /
    • pp.490-496
    • /
    • 2018
  • Recently, the power and refrigeration cogeneration based on Kalina cycle has attracted much attention for more efficient utilization of low-grade energy. This study presents a thermodynamic performance analysis of a cogeneration cycle of power and absorption refrigeration based on Kalina cycle. The cycle combines Kalina cycle (KCS-11) and absorption cycles by adding a condenser and an evaporator between turbine and absorber. The effects of ammonia mass fraction and separation pressure were investigated on the system performance of the system. Results showed that the energy utilization of the system could be greatly improved compared to the basic Kalina cycle.