Browse > Article

Performance Characteristics and Economic Assessment of a River Water: Source Heat Pump System  

Park, Cha-Sik (Department of Automotive Engineering, Hoseo University)
Jung, Tae-Hun (Hyundai Kia Motor Company)
Park, Hong-Hee (Graduate School of Mechanical Engineering, Korea University)
Kim, Yong-Chan (Department of Mechanical Engineering, Korea University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.21, no.11, 2009 , pp. 621-628 More about this Journal
Abstract
The objectives of this study are to analyze the performance of a river water-source heat pump and to carry out economic assessment for the heat pump. The COP of the river water-source heat pump was 3-21% higher than that of the air-source heat pump because river water provides stable operating temperature compared with air temperature throughout the year. The economic analysis was carried out by comparing the initial and operating cost of the river water-source heat pump with those of the conventional air-source heat pump. The ratio of the life cycle operating cost to the life cycle cost increased with the increase of building capacity. The payback period was found to be less than 3.5 years when the capacity of the river water-source heat pump was larger than 10 RT.
Keywords
River water; Heat pump; Life cycle cost(LCC); Payback period; Economic assessment;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Okamoto, S., 2006, A heat pump system with a latent heat storage utilizing sea water installed in an aquarium, Energy and Building, Vol. 38, pp. 121-128   DOI   ScienceOn
2 Jung, T. H., Park, C. S. and Kim, Y. C., 2008, Simulation on the optimal performance and effective operating range of a 2-stage compression heat pump using river water, SAREK, Vol. 20, pp. 295-303
3 Lee, Y. S., 2008, Development of the optimization technology for network plant using unutilized energy resources, KIER Report, pp. 387-402
4 Lian, Z., Park, S. and Qi, H., 2005, Analysis on energy consumption of water loop heat pump system in china, Applied Thermal Engineering, Vol. 25, pp. 73-85   DOI   ScienceOn
5 Fisher, S. K. and Rice, C. K., 1983, The Oak Ridge heat pump models:A steady state computer design model for air to air heat pumps, ORNL/CON-80/RI, Energy Division
6 Mearig, T., Coffee, N. and Morgan, M., 1999, Life cycle cost analysis handbook, Alaska Department of Education and Early Development, 1st edition
7 Park, J. T. and Lee, J. H., 1999, The possibility of temperature difference energy utilization as the heat source of heat pump, Proceed -ings of SAREK 1999 Summer Conference, pp. 254-258
8 Park, C. S., Kim, B. H., Kim, Y. C., Lee, Y., S. and Bang, G. Y., 2005, Simulation on the heating performance of a 2-stage compression heat pump system using river water, SAREK, Vol. 11, pp. 1005-1013   과학기술학회마을   ScienceOn
9 Chen, C., Sun, F., Feng, L. and Liu, M., 2005, Underground water source loop heat pump air conditioning system applied in a residential building in Beijing, Applied Energy, Vol. 82, pp. 331-344   DOI   ScienceOn