A Study on the Improvement of Heat Transfer Performance in Low Temperature Closed Thermosyphon

  • Han, Kyu-Il;Yee, Seok-Su;Park, Sung-Hyun;Lee, Suk-Ho;Cho, Dong-Hyun
    • Journal of Mechanical Science and Technology
    • /
    • 제16권9호
    • /
    • pp.1102-1111
    • /
    • 2002
  • The study focuses on the heat transfer performance of two-phase closed thermosyphons with plain copper tube and tubes having 50, 60, 70, 80, 90 internal grooves. Three different working fluids(distilled water, methanol, ethanol) are used with various volumetric liquid fill charge ratio from 10 to 40%. Additional experimental parameters such as operating temperature and inclination angle of zero to 90 degrees are used for the comparison of heat transfer performance of the thermosyphon. Condensation and boiling heat transfer coefficients, heat flux are obtained using experimental data for each case of specific parameter. The experimental results are assessed and compared with existing correlations. The results show that working fluids, liquid fill charge ratio, number of grooves and inclination angle are very important factors for the operation of thermosyphons. The relatively high rate of heat transfer is achieved when the thermosyphon with internal grooves is used compared to that with plain tube. The optimum liquid fill charge ratio for the best heat transfer performance lies between 25% and 30%. The range of the optimum inclination angle for this study is 20$^{\circ}$~30$^{\circ}$ from the horizontal position.

Experimental Investigation of Heat Transfer in Absorber with Small Diameter Tube

  • Phan Thanh Tong;Moon Choon-Geun;Kim Jae-Dol;Yoon Jung-In
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2006년도 전기학술대회논문집
    • /
    • pp.261-262
    • /
    • 2006
  • The effect of tube diameter on heat transfer characteristics of absorber in absorption chiller/heater using LiBr solution as a working fluid has been investigated by experimental study to develop a high performance and compact absorber. A system Includes a tube absorber, a generator, solution distribution system and cooling water system was set up. The diameter of the heat exchanger tube inside absorber was changed from 15.88mm to 12.7mm and 9.52mm. The experimental results show that the heat transfer coefficient, Nusselt number and heat flux increase as solution flow rate and cooling water flow rate increase. The heat transfer performance increases as tube diameter decreases. Among three different tube diameters, the smallest tube diameter 9.52mm has highest heat transfer performance. A comparison of the heat transfer coefficient obtained by the present study with those of previous experimental results showed good overall agreement.

  • PDF

CFD 해석을 통한 냉장고용 응축기 전열성능 연구 (CFD ANALYSIS OF HEAT TRANSFER PERFORMANCE OF A REFRIGERATOR CONDENSER)

  • 유성수;황도연;이명수;한병윤;박형구
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2009년 춘계학술대회논문집
    • /
    • pp.303-309
    • /
    • 2009
  • In this study, the heat transfer and flow field of condenser used on Kim-chi refrigerator is analysed with numerical method. Main objective is to present the base data for designing new condenser model with improvement of heat transfer performance. For CFD analysis, a commercial code, STAR-CCM+ was used. The water was used for the inner working fluid and the air was used for the outer fluid. The condenser type used in this study is a flat plate fin-and-tube heat exchanger. As factors for performance analysis, the effect of condenser geometry and air velocity was investigated. As a result, it has been observed that there is a suitable fin pitch with which heat transfer performance of condenser is maximized.

  • PDF

CFD를 활용한 태양열 공기가열기 내 사각저항체 설치 조건에 따른 열전달 및 압력강하에 관한 연구 (Research on the Heat Transfer and Pressure Drop by Installation Conditions of Rectangular Obstacle in a Solar Air Heater Based on CFD)

  • 최휘웅;김영복;손창효;윤정인;최광환
    • 한국태양에너지학회 논문집
    • /
    • 제39권1호
    • /
    • pp.77-89
    • /
    • 2019
  • The solar air heater has various performances according to an obstacle installed in the air duct. Many studies on thermal performance have been conducted. But many of these studies were using a kind of rib type obstacle attached at the bottom of absorbing plate, but they are so hard to be manufactured. In this study, characteristics of the heat transfer and pressure drop in the solar air heater with various horizontal rectangular obstacles was investigated by CFD (Computational Fluid Dynamics) analysis. As a result, the heat transfer performance was improved from 1.2 to 3.32 times depending on installation conditions of rectangular obstacle. The pressure drop, however, also increased with increment of heat transfer performance from 2.8 to 180 times only by changing installation conditions of rectangular obstacle. Thus, the performance factor presenting the thermal performance enhancement on the same pressure drop was also confirmed. As a result, the highest value of 0.828 as better performance factor was obtained at the lower height of rectangular obstacle and this value has started to decrease with increment of heat transfer performance. In the end, it could be confirmed that the pressure drop was carried higher than the quantity of improvement of the heat transfer performance when the heat transfer performance was increased by change of installation conditions of rectangular obstacle. Both heat transfer enhancement and pressure drop to be required for system need to be considered before the rectangular obstacles are applied to the solar air heater.

건식온돌시스템의 전열특성 및 방열성능에 관한 이론적 분석 (Theoretical Analysis on Heat Transfer Characteristics and Heat Flux Performance in Ondol Systems of Dried Type)

  • 장용성;유기형;조동우
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.176-181
    • /
    • 2007
  • This study aims to evaluate theoretically heat transfer characteristics and heat flux performance in ondol system of dried type is composed of panel of ceramics to improve of thermal conductivity and fin to expand heat. To this end, we analyzed effect of design factors(temperature of hot water, set temperature of room and thermal conductivity of finishing materials) in ondol system of dried type by heat transfer analysis. The main results of this study are summarized as follows; The deviation of heat flux and temperature was reduced by heat expansion from fin decreasing heat loss generated in air layer. The temperature and heat flux in upper finishing materials surface linearly increased according to temperature increment of hot water, but the temperature distribution in upper surface was assessed uneven. The greater heat resistance value of upper finishing materials, the deviation of maximum temperature and minimum temperature was decreased. Also, we suggested a basic design data about ondol system of dried type through an analysis of simulation results on heat transfer characteristics and heat flux performance.

  • PDF

R410A 냉매를 사용한 열펌프용 열교환기의 형상에 따른 성능특성 연구 (A Study on Performance Characteristics of Heat Exchanger for Heat Pump with R410A Refrigerant)

  • 정규하;박윤철;오상경
    • 설비공학논문집
    • /
    • 제16권4호
    • /
    • pp.340-348
    • /
    • 2004
  • The air and refrigerant side heat transfer performances are key parameters to improve heat transfer efficiency of the heat exchanger including the fan performance. Design of the fins, treatment of the tube inside, tube diameter and tube array effect heat transfer performance of the heat exchanger. The heat exchanger is used as a condenser at cooling mode and used as an evaporator at heating mode in the heat pump system. The heat pump system uses R410A as the refrigerant. The heat exchangers are consisted with 7 mm diameter tubes with slit-type fins. The study was conducted with variation of arrangement of the refrigerant path and air flow rate and refrigerant pressure drop and heat transfer rate were measured with a code tester. The capacity of the 3 path heat exchanger is more efficient than 2 or 4 path heat exchangers in heating or cooling modes.

Experimental Investigation of the Thermal Hydraulics in Lead Bismuth Eutectic-Helium Experimental Loop of an Accelerator-Driven System

  • Xi, Wenxuan;Wang, Yongwei;Li, Xunfeng;Huai, Xiulan;Cai, Jun
    • Nuclear Engineering and Technology
    • /
    • 제48권5호
    • /
    • pp.1154-1161
    • /
    • 2016
  • The heat transfer characteristics between liquid lead bismuth eutectic (LBE) and helium are of great significance for the two-loop cooling system based on an accelerator-driven system (ADS). This paper presents an experimental study on the resistance characteristics and heat transfer performance in a LBE-helium experimental loop of ADS. Pressure drops in the LBE loop, the main heat transfer, and the coupled heat transfer characteristics between LBE and helium are investigated experimentally. The temperature of LBE has a significant effect on the LBE thermo-physical properties, and is therefore considered in the prediction of pressure drops. The results show that the overall heat transfer coefficient increases with the increasing helium flow rate and the decreasing inlet temperature of helium. Increasing the LBE Reynolds number and LBE inlet temperature promotes the heat transfer performance of main heat transfer and thus the overall heat transfer coefficient. The experimental results give an insight into the flow and heat transfer properties in a LBE-helium heat exchanger and are helpful for the optimization of an ADS system design.

탄화수소 냉매를 사용한 냉방시스템의 성능 및 열전달 특성 (Performance and heat transfer of an air conditioning system filled with hydrocarbon refrigerants)

  • 장영수;김민수;노승탁
    • 대한기계학회논문집B
    • /
    • 제21권5호
    • /
    • pp.713-723
    • /
    • 1997
  • Performance and heat transfer characteristics of an air conditioning system filled with hydro- carbon refrigerants are experimentally investigated. Single component hydrocarbon refrigerants (propane, isobutane, butane and propylene) and binary mixtures of propane/isobutane and propane/butane are considered as working fluids in the air conditioning system. Performances of each refrigerant are obtained at several compressor speeds and temperature levels of secondary heat transfer fluids. The cooling capacity and the coefficient of performance are obtained as test results. Heat transfer data of selected refrigerants are achieved from overall conductance measurement. Average heat transfer coefficients at different mass fluxes are shown and they are also displayed for different heat capacities of the system. Experimental results show that some hydrocarbon refrigerants have better characteristics than R22.

루버핀-관 열교환기의 습조건에서의 열전달 및 마찰특성에 대한 실험 연구 (Heat Transfer and Friction Characteristics of Louver Fin and Tube Heat Exchangers under Wet Conditions)

  • 권영철;장근선
    • 공업화학
    • /
    • 제19권1호
    • /
    • pp.73-79
    • /
    • 2008
  • 본 연구에서는 핀-관 열교환기의 공기측 열전달, 마찰 그리고 물질특성을 조사하기 위하여 6종의 열교환기에 대하여 습조건에서 실험을 수행하였다. 실험에 사용된 핀은 루버형으로 핀피치, 관 열수 그리고 입구상대습도를 변화하였다. 루버핀-관 열교환기의 열전달계수와 마찰계수는 레이놀즈 수가 증가할수록 감소하였으며, 핀피치가 줄어들수록 열전달계수는 감소하였고 마찰계수는 증가하였다. 3열 열교환기의 열전달계수와 마찰계수의 핀피치 변화에 따른 영향은 2열 열교환기의 경우보다 덜 민감하였다. 그리고 유입공기의 상대습도에 대한 열전달계수와 마찰계수의 변화폭은 크지 않았다. 또한, 루버핀-관 열교환기의 물질전달계수는 핀피치가 감소할수록 줄어들었으나, 레이놀즈 수 변화에 따른 물질전달계수는 열전달계수와는 달리 관 열수에 따라 서로 다른 경향을 보였다. 유입공기의 상대습도가 높아질수록, 물질전달계수는 다소 줄어 들었다.

착상에 의한 휜관형 열교환기의 성능변화에 관한 실험적 연구 (Experimental Study on the Performance Change of the Fin and Tube Type Heat Exchanger by the Frosting)

  • 김정국;소산번;상원헌;박병덕;김동휘;사용철
    • 설비공학논문집
    • /
    • 제21권2호
    • /
    • pp.79-86
    • /
    • 2009
  • The present study was investigates the effect of the parameters on the frost formation and heat transfer performance such as fin shape, air temperature and air velocity. Heat transfer rate and pressure drop by frost were experimentally investigated. Effect of the wet blub temperature and air velocity on the heat transfer performance has been also investigated. The heat transfer performance of the louver fin and tube type heat exchanger was higher by maximum of 0.85% than the corrugate fin type at the air temperature of $2.0/1.5^{\circ}C$. As the wet blub temperature of air were increased, the heat transfer rate, pressure drop and mass of frost of three test models were increased. Especially, the maximum heat transfer rate and maximum pressure drop were shown for the Type B louver fin heat exchanger. As an experimental result, the enhancement factor(EF) of louver fin and tube type heat exchanger was only $0.2{\sim}0.4$ due to the high pressure drop.