• Title/Summary/Keyword: Grounding rods

Search Result 52, Processing Time 0.032 seconds

Ground ing Impedance Characteristics of Ground Rods in frequency Domain (주파수 영역에서 봉상전극의 접지임피던스 특성)

  • Lee, Hyung-Soo;Shim, Keon-Bo;Kim, Kyung-Chul;Choi, Jong-Kee;Park, Sang-Man
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.248-253
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance of various rod-type ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

Lightning Protection of Signalling Equipments at Subway Car Depot by Equi-potential Bonding (지하철 차량기지에서의 등전위 본딩에 의한 신호시스템 낙뢰보호대책)

  • Seo, Seog-Chul;Choi, Kyu-Hyoung
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.1
    • /
    • pp.100-105
    • /
    • 2007
  • Signalling equipments at railroad sites are widely exposed to high voltage lightning surges. This paper presents a lightning protection system for the signalling equipments at subway car depots. The main features of the system are as follows : (1)the common grounding system between power system grounds and the signaling system grounds, (2)physical and chemical methods to reduce grounding resistivity, (3)rearrangement of lightning rods based on the rolling bal1 theory, (4)equi-potential bonding networks to minimize the potential differences between the equipments grounds. The system has been constructed at six subway car depots in Seoul metropolitan area and it is measured that the grounding resistivity are reduced to 0.266 ohms and the potential differences between devices are reduced to a negligible quantity. After the construction of the systems, it has not been reported the break-down of the signalling equipments caused by lighting surges.

Ground impedance of deeply driven rod in high frequency domain (고주파수 영역에서 심매설 접지전극의 접지임피던스)

  • Lee, Bok-Hee;Lee, Tae-Hyung;Lee, Su-Bong;Jeong, Hyun-Wook;Jeong, Dong-Cheol
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.247-250
    • /
    • 2004
  • A ground resistance is a good index of performance in a grounding system, but it does not reflect the performance in transient states. Recently long vertical ground rods in urban areas are often installed. But because of the inductance of long ground rods the ground impedance at high frequency might be greater than its resistance at low frequency. In this paper, a ground impedance of deeply driven ground rod has been measured in the frequency range from 10 kHz to 50 MHz. As a result, the ground impedances of a deeply driven ground rods are almost constant at the frequency range less than 100 kHz. However at high frequency the ground impedance showed the strong frequency dependance.

  • PDF

Lightning impulse characteristics of large-scale ground rods with different length (대형 봉상 접지전극의 길이에 따른 뇌 임펄스 특성)

  • Lee, B.H.;Chang, K.C.;Eom, J.H.;Kim, B.K.;Jeong, D.C.;Kil, H.J.
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.233-235
    • /
    • 2003
  • To obtain a low ground resistance in high resistivity soil or in insufficient place such as downtown, long vertical ground rods are often used. However, if the lightning current or fault current with high frequency flows into the grounding system, the ground impedance is significantly increased. This paper presents how the impulse current works on the long vertical ground rods with a different length. As a result, it can be estimated what the waveform is composed of and how the GPR is affected by the rate of current change.

  • PDF

Lightning impulse characteristics of large-scale ground rods (대형 봉상 접지전극의 뇌 임펄스 특성)

  • Lee, B.H.;Chang, K.C.;Lee, D.M.;Jeong, D.C.;Lee, S.C.;Ahn, C.H.;Jeong, Y.K.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1849-1851
    • /
    • 2003
  • To obtain a low ground resistance in high resistivity soil, long vertical ground rods are often used. However, if the lightning current or fault current with high frequency flow into the grounding system, the ground impedance is significantly increased because of the inductive behavior. This paper presents how the impulse current works on the long vertical ground electrodes. The different shape of current was impressed between ground rods and auxiliary electrode by using impulse generator and the ground impedance was calculated from the ground potential rise.

  • PDF

A Study on the Effect of Concrete Pole Foundation on Ground Resistance Measurement (전주의 구조체접지효과가 접지저항 측정에 미치는 영향 연구)

  • Choi, J.K.;Ryu, H.Y.;Kang, M.H.;Hwang, G.C.;Shim, K.B.;Lee, H.S.;Kim, K.C.
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.464-465
    • /
    • 2008
  • Concrete poles(CP) are popular supports for distribution lines. Various types of grounding electrode, such as copper-clad rods, have been used to maintain CP's ground resistance under the required value. The buried part of CP can also have structural grounding effect because of its iron reinforcing rods inside CPs. In this paper, we measured the total ground current injected into CP ground while measuring the ground current splitting to the metal electrode as well as the total injecting current. By this, it was able to measure the ground current splitting to CP structure. Based on the measured results, interrelationship between ground resistance of metal electrodes and current split factor to CP structure was analyzed.

  • PDF

Review about the Lightning Protection System for Ground Facilities of Anti-aircraft Weapons System (뇌 보호시스템의 대공무기체계 지상시설 적용에 대한 고찰)

  • Jung, Kyoungwook;Shim, Donghyouk;Son, Donghyeop
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.24 no.3
    • /
    • pp.339-347
    • /
    • 2021
  • Recently, the incidence of lightning in Korea has been increasing more and more. The damage caused by lightning is also getting worse. Lightning protection system is a prerequisite, not a sufficient condition. Considering the characteristics of lightning, there is a high frequency of lightning strikes in highlands. So, high grades of LPS should be applied to ground facilities of anti-aircraft weapons systems. 4-Level LPS was applied on groung facilities of anti-aircraft weapons system based on lightning incidence rate in past. There are some possibilities of damage from lightning in anti-aircraft weapons system. So, we have to readjust the LPS level with grounding, lightning rods and surge protect device based on lightning incidence rate in now days. Propose 2-level LPS and design with lightning rods, surge protector, separated grounding in this paper.

Behaviors of Impulse Ground Impedances Associated with the Current Injection Point in a Ground Rod (봉상 접지전극에시 전류유입위치에 따른 임펄스 접지임피던스의 특성)

  • Lee, Bok-Hee;Jeong, Dong-Cheol;Lee, Su-Bong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.1
    • /
    • pp.94-100
    • /
    • 2005
  • This paper presents the behaviors of transient and effective impulse impedances of a long ground rod associated with the current injection points. The laboratory test for the time domain performance of actual-sized model ground rod subjected to a lightning stroke current has been carried out The transient ground impedances of long ground rods under impulse currents were higher than the ground resistance. Both of the ground resistance and the effective impulse ground impedance decrease with increasing the length of the ground rods. Also, the effective impulse ground impedances are significantly increased in fast rise time ranges. The reduction of the ground resistance is decisive to improve the impulse impedance characteristics of grounding systems. When the test current is injected at the bottom of ground rod, the oscillating pulses with high frequency are included on the wave front of ground rod potential and the effective impulse impedances are higher than any other cases.

Research for the Substitutional Grounding Electrode in the Foundation of the House (주택기초의 대용 접지극에 관한 연구)

  • Kim, Sung-Sam;Lee, Chung-Sik;Choi, Jong-Kyu;Kim, Ju-Chan;Koh, Hee-Seog
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.355-358
    • /
    • 2005
  • The electrical characteristics for applying the foundation of the house to the substitutional earth electrode was reviewed fundamentally. In order to measure the earth resistance in the foundation of the house, it was performed to investigate the effect of the electrode arrangements and configurations concerning to grounding methods, and tried to the adequate simulation for comparing those experimental data. The number of steel rods and the ground resistivity were affected to change the earth resistance, but the latter caused the large variation in its resistance compared to the former in this experiment. Since the large surface area in the foundation of the house have contacted the ground usually, it is possible to use the earth electrode substitutionally.

  • PDF

Ground Impedance Characteristics Analysis of a Copper Rod-type Grounding Electrode used for Electric Distribution Systems (배전계통에 사용되는 동봉 접지전극의 접지 임피던스 특성 분석)

  • Kim, Kyung-Chul;Lee, Joo-Hong;Jin, Seong-Eun;Oh, Jung-Suk;Park, Sang-Young;Choi, Jong-Ki;Kim, You-June
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.6
    • /
    • pp.46-51
    • /
    • 2005
  • Grounding insures a reference potential point for electric devices and also provides a low resistance path for fault currents in the earth. The ground impedance as a function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. A cower rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the ground impedance of cower rods has been measured in frequency ranging from 60[Hz] up to 100[kHz] and an equivalent circuit model, transfer function model of the ground impedance are identified from the measured values.