• Title/Summary/Keyword: Grounding method

Search Result 293, Processing Time 0.029 seconds

Evaluation of the potential reduction and energy dispersion caused by ionization phenomena at the submerged ground rod (수중에 잠긴 접지전극주변에서 이온화에 의한 전위저감 및 에너지 방출의 평가)

  • An, Sang-Duk;Choi, Jong-Hyuk;Park, Geon-Hun;Yang, Soon-Man;Lee, Bok-Hee;Ahn, Chang-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.337-340
    • /
    • 2008
  • When high surge voltage invaded into the ground rod contacted with ground water, the ionization phenomena are happened in the water. Although some researchers have surveyed the ionization phenomena in soil, they have just analyzed the variation of the ground resistance. The most important role of the ground rod is to elect human beings from potential rise and to dissipate energy to the earth safely. In this wort we presented the method evaluating the potential reduction and energy dispersion. Also we analyzed theses factors as a function of charging voltages at the water resistivity of $50\;{\Omega}{\cdot}m$ using the Matlab Program. As a result the ground rod potential was reduced to 38 kV by ionization just below breakdown voltage. The energy more than half of the total injected energy was dispersed through the grounding electrode caused due to ionization.

  • PDF

A Study on SVL Transient Characteristics by Switching Overvoltage at Single Point Bonding Section in Underground Transmission Cables (개폐과전압 발생시 지중송전선로 편단접지 구간에서 SVL에 미치는 과도특성에 관한 연구)

  • Jung, Chae-Kyun;Kang, Ji-Won
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.6
    • /
    • pp.764-769
    • /
    • 2014
  • This paper describes sheath voltage limiter(SVL) transient characteristics by switching overvoltage considering single point bonding in underground transmission cables. The crossbonding system is generally used for grounding methods of underground transmission system. However, the single point bonding system is used in selective area which is difficult to consist of crossbonding major section. The sheath voltage limiters are connected between joints in the single point bonding. Specially, the high overvoltage might be generated in that section as well as the aging of sheath voltage limiter might be progressed by various electrical stress including lightning overvoltage, switching overvoltage and power frequency overvoltage. Therefore, in this paper, the switching overvoltage characteristics in underground cables are firstly analysed using EMTP simulation. Then, the switching overvoltage of sheath voltage limiter is also studied in single point bonding. Finally, the reduction method of sheath voltage limiter switching overvoltage is proposed by various simulation studies including circuit breaker operating order.

Performance Evaluation of Early Streamer Emission Lightning Air Terminal

  • Choi, Sang-Won;Her, Yong
    • International Journal of Safety
    • /
    • v.5 no.2
    • /
    • pp.18-23
    • /
    • 2006
  • Studies have claimed that ESE (Early Streamer Emission) air terminals offer a vastly increased zone of protection over that of traditional lightning rods (Franklin rods) by causing the emission of an upward streamer/leader: The upward streamer/leader will propagate towards the tip of the downward leader at an early stage in the attachment process.. This paper shows the results of a performance evaluation test of a particular type of the ESE air terminal (called "ElecHippo") with a simple rod tested at the Korea Electrotechnology Research Institute (KERI). The corona emission current of the ElecHippo made by Yong-Jin Enterprise Corp. has also been measured at the Occupational Safety & Health Research Institute (OSHRI). The results show that the ElecHippo meets the French standard of NFC 17-102-1995. The results also verify the ESE performance by measuring the ion emission current generated in the discharge electrode gap as a function of the capacitance and inductance of the equipped devices. Finally, we propose a new method for grounding the system to reduce the lightning damage by combining the ESE air terminal, the early discharge earth plate, the lightning strike recorder and the surge protection device.

A Study on Grounding Technology for the Reduction of Electric Surge in IBS Building (IBS 빌딩에서의 서어지 저감을 위한 접지방안 연구)

  • 박중양;김학련;최규형
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.87-92
    • /
    • 2003
  • According to the realization of highly information dependent society, the recent building system is developed into the concept of suitable for management of intellegent work, which is demanded to unify of IBS(Intelligent Building System), IC(information communication), OA(office automation), BA(building automation) system and computer technology. However inspite of the presence arrester, cable shielding, insulated TR, filter, earth etc., in the IBS building for the cope with several surge and noise has several problems from the wrong operation of the equipment which caused from several surge, damage of equipment, and noise etc. And the miss operation caused by wrong earth works, which must be considered at first during the building construction. In order to minimize these problems, it's necessary that various earth project are performed effectively, and bonding methods between the mutual wiring of earth system and the equipments in the building should be improved sucessively. So in this paper, we analyze present domestic conditions of the earth technology in IBS building, and propose minimization method for the various surge and noise problem, and examine and analyze through the applied works.

  • PDF

Characteristics and Measurement Method of the Underwater Electromagnetic Signature Emitted from a Naval Ship (함정 발생 수중 전자기장 신호의 특성 및 측정 기법)

  • Yang, Chang-Seob;Chung, Hyun-Ju;Shin, Seung-Je
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.9 no.2 s.25
    • /
    • pp.11-19
    • /
    • 2006
  • The underwater electromagnetic signatures of a naval ship are mainly generated from three sources which are the permanent and induced magnetic field in the ship's hull and other ferrous components, the cathodic current electromagnetic field established by the Impressed Current Cathodic Protection(ICCP) system or the Sacrificial Anode and the stray electromagnetic fields generated by onboard equipment. These signatures can be minimized by certain design methods or installation of signature reduction equipment. In this paper, we represented the characteristic of the underwater electromagnetic signature and the signature reduction techniques for a naval ship. Also, we measured the electromagnetic field changes emitted from the real ship using the Electric and Magnetic field Measurement System(EMMS). We found that the underwater electromagnetic signature for a naval ship can be used as input or trigger signal in a surveillance system and an influence mine.

Optimization of the Earthing Resistance and Research on the Electrical Characteristics of New Catalyst for the Quality Earthing (접지품질 개선을 위한 접지저항 최적화 및 접지충진제의 전기적 특성 연구)

  • Park, C.G.;Ahn, S.J.;Woo, J.W.;Ahn, S.J.;Yu, Y.J.;Ahn, S.J.
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.7 no.6
    • /
    • pp.1078-1085
    • /
    • 2006
  • In earthing technologies, the intrusion of the surge wave can be protected when the earthing resistance is as low as several ohms. However, the cost fer realizing such a low resistance is quite high. Therefore it is important to determine appropriate target value of the earthing resistance to install cost-effective grounding system. In this work, we have proposed an optimization method of the earthing resistance according to the various environmental parameters by using a numerical simulator We have also developed new catalyst composed of water-soluble alkaline elements and activated carbon and investigated its electrical characteristics for enhancement of the earthing qualities.

  • PDF

Southeast Asia and Southeast Asian Studies: Issues in Multidisciplinary Studies and Methodology

  • King, Victor T.
    • SUVANNABHUMI
    • /
    • v.7 no.1
    • /
    • pp.13-57
    • /
    • 2015
  • The paper brings together several strands of debate and deliberation in which I have been involved since the early 2000s on the definition of Southeast Asia and the rationale of Southeast Asian Studies. I refer to the relationship between area studies and methodologies as a conundrum (or puzzle), though I should state from the outset that I think it is much more of a conundrum for others than for me. I have not felt the need to pose the question of whether or not area studies generates a distinctive method or set of methods and research practices, because I operate from a disciplinary perspective; though that it is not to say that the question should not be posed. Indeed, as I have earned a reputation for "revisionism" and championing disciplinary approaches rather than regional ones, it might be anticipated already the position that I take in an examination of the relationships between methodologies and the practice of "area studies" (and in this case Southeast Asian [or Asian] Studies). Nevertheless, given the recent resurgence of interest in the possibilities provided by the adoption of regional perspectives and the grounding of data gathering and analysis within specified locations in the context of globalization, the issues raised for researchers working in Southeast Asia and within the field of Southeast Asian Studies require revisiting.

  • PDF

Characteristics for Ground Impedance according to Distance of Current Probe and Frequency (전류보조전극 거리 및 주파수에 따른 접지임피던스 특성)

  • Gil, Hyoung-Jun;Lee, Ki-Yeon;Moon, Hyun-Wook
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.5
    • /
    • pp.122-128
    • /
    • 2010
  • This paper presents the characteristics for ground impedance of combined three rods according to distance of current probe and frequency using the fall-of-potential method and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of auxiliary probes. In order to analyze the effects of ground impedance due to the distance of the current probe and frequency, ground impedances were measured in case that the distance of current probe was located from 5[m] to 20[m] and the measuring frequency was ranged in 55~513[Hz]. The results could be help to determine the position of current probe and the measuring frequency when the ground impedance was measured at grounding system.

Determination of Optimal Ship Route in Coastal Sea Considering Sea State and Under Keel Clearance (해상 상태 및 선저여유수심을 고려한 연안 내 선박의 최적 항로 결정)

  • Lee, Wonhee;Yoo, Wonchul;Choi, Gwang-Hyeok;Ham, Seung-Ho;Kim, Tae-wan
    • Journal of the Society of Naval Architects of Korea
    • /
    • v.56 no.6
    • /
    • pp.480-487
    • /
    • 2019
  • Ship route planning is to find a route to minimize voyage time and/or fuel consumption in a given sea state. Unlike previous studies, this study proposes an optimization method for the route planning to avoid the grounding risk near the coast. The route waypoints were searched using A* algorithm, and the route simplification was performed to remove redundant waypoints using Douglas-Peucker algorithm. The optimization was performed to minimize fuel consumption by setting the optimization design parameters to the engine rpm. The sea state factors such as wind, wave, and current are also considered for route planning. We propose the constraint to avoid ground risk by using under keel clearance obtained from electoronic navigational chart. The proposed method was applied to find the optimal route between Mokpo and Jeju. The result showed that the proposed method suggests the optimal route that minimizes fuel consumption.

Ontology-Based Dynamic Context Management and Spatio-Temporal Reasoning for Intelligent Service Robots (지능형 서비스 로봇을 위한 온톨로지 기반의 동적 상황 관리 및 시-공간 추론)

  • Kim, Jonghoon;Lee, Seokjun;Kim, Dongha;Kim, Incheol
    • Journal of KIISE
    • /
    • v.43 no.12
    • /
    • pp.1365-1375
    • /
    • 2016
  • One of the most important capabilities for autonomous service robots working in living environments is to recognize and understand the correct context in dynamically changing environment. To generate high-level context knowledge for decision-making from multiple sensory data streams, many technical problems such as multi-modal sensory data fusion, uncertainty handling, symbolic knowledge grounding, time dependency, dynamics, and time-constrained spatio-temporal reasoning should be solved. Considering these problems, this paper proposes an effective dynamic context management and spatio-temporal reasoning method for intelligent service robots. In order to guarantee efficient context management and reasoning, our algorithm was designed to generate low-level context knowledge reactively for every input sensory or perception data, while postponing high-level context knowledge generation until it was demanded by the decision-making module. When high-level context knowledge is demanded, it is derived through backward spatio-temporal reasoning. In experiments with Turtlebot using Kinect visual sensor, the dynamic context management and spatio-temporal reasoning system based on the proposed method showed high performance.