Browse > Article
http://dx.doi.org/10.5370/KIEE.2014.63.6.764

A Study on SVL Transient Characteristics by Switching Overvoltage at Single Point Bonding Section in Underground Transmission Cables  

Jung, Chae-Kyun (KEPCO Research Institute)
Kang, Ji-Won (KEPCO Research Institute)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.63, no.6, 2014 , pp. 764-769 More about this Journal
Abstract
This paper describes sheath voltage limiter(SVL) transient characteristics by switching overvoltage considering single point bonding in underground transmission cables. The crossbonding system is generally used for grounding methods of underground transmission system. However, the single point bonding system is used in selective area which is difficult to consist of crossbonding major section. The sheath voltage limiters are connected between joints in the single point bonding. Specially, the high overvoltage might be generated in that section as well as the aging of sheath voltage limiter might be progressed by various electrical stress including lightning overvoltage, switching overvoltage and power frequency overvoltage. Therefore, in this paper, the switching overvoltage characteristics in underground cables are firstly analysed using EMTP simulation. Then, the switching overvoltage of sheath voltage limiter is also studied in single point bonding. Finally, the reduction method of sheath voltage limiter switching overvoltage is proposed by various simulation studies including circuit breaker operating order.
Keywords
Sheath voltage limiter; Single point bonding; Switching overvoltage; Underground power cables;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 KEPCO, "Underground Transmission Cable System", 2002. 12.
2 KEPRI, "A study on the composition scheme establishment of optimum system in Underground Transmission Systems(Final report), 2009. 9
3 Chae-Kyun Jung, Ji-Won Kang, Hung-Sok Park, Jin Kim "A Study on Overvoltage Reduction Method of Single Point Bonded Section on Combined Transmission Lines", The Transactions of the Korean Institute of Electrical Engineers, Vol. 58, No. 10, 2009. 10   과학기술학회마을
4 Chae-Kyun Jung, Hung-Sok Park, Tai-In Jang, Ji-Won Kang, Jong-Keon yoon, "A Study on Transient Characteristics of Single Point Bonded Grounding in Underground Power Cable Systems", 2013 KIEE Summer Annual Conference Proceedings, 2013. 07
5 IEEE, "IEEE Guide for the Application of Sheath Bonding Methods for Single-conductor Cables and Calculation of induced Voltage and Current in Cable Sheaths, ANSI/IEEE Std. 575-1998
6 CIGRE WG B1.18, "Special Bonding of High Voltage Power Cables, Oct. 2005
7 Chae-Kyun Jung,.Hung-Sok Park, Ji-Won Kang, Jong-Beom Lee, "A Study on Reclosing Decision on 154kV Combined Transmission Lines", The Transactions of the Korean Institute of Electrical Engineers, Vol. 59, No. 10, 2010. 10   과학기술학회마을
8 Jong-Beom Lee, Chae-Kyun Jung, .Kwang-Sik Lim, Ji-Won Kang, "Effects of Reclosing for Insulation Coordination in 345kV Combined Transmission Lines", The Transactions of the Korean Institute of Electrical Engineers, Vol. 59, No. 8, 2010. 8   과학기술학회마을
9 KEPRI "A Study on Theory and Application of Power System Transient Anlysis Program(Final Report), 1991. 1