• Title/Summary/Keyword: Grounding Resistance

Search Result 246, Processing Time 0.023 seconds

Nonchange of Grounding Current due to Equipment Measuring Insulation Resistance (절연저항 측정 장치에 의한 지락사고 전류의 비변화)

  • Um, Kee-Hong;Lee, Kwan-Woo
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.15 no.3
    • /
    • pp.175-180
    • /
    • 2015
  • With progress in industrialization, facilities for generating, delivering, and receiving high levels of electric power are in great demand. The scale of electric power equipment is increasing in both size and complexity. This has contributed to the development of our modern, high-tech and information-based society. However, if the generation of electric power is suspended due to unexpected accidents at power facilities or power stations, a range of equipment the operations of which are dependent on electric power can be damaged, causing substantial socioeconomic losses in an industrial society. A great deal of time and money would be expended to repair damaged facilities at a power station, causing enormous economic loss.In order to detect the deterioration processes of power cables, and to prevent the destruction of power cables, the operation status of power cables should be monitored on a regular basis. We have installed equipment at Korea Western Power Co., Ltd., located in Taean, in order to predict and prevent the destruction of power cables. This is an entirely new installation: a set of equipment invented specifically to measure the insulation resistance of power cables. Installation of the equipment does not cause the flow of earth fault current. This ensures accurate measurement of insulation resistance values by the equipment. We have been studying this equipment in order to develop preventive technology that would show the deterioration processes of power cables.

An Analysis of Influence Between the Power Feeding Line Insulation and Negative Rail Potential for the DC Ground Fault Protection in the Rubber Wheel System (고무차륜시스템에서의 지락보호를 위한 급전선로 절연과 부극전위와의 영향 분석)

  • Jung, Hosung;Shin, Seongkuen;Kim, Hyungchul;Park, Young;Cho, Sanghoon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.4
    • /
    • pp.577-583
    • /
    • 2013
  • We have analyzed influence of potential rise in negative bus, which caused by decrease of power feeding line insulation, upon protecting method of DC ground protection device which detecting potential rise between negative bus and ground in order to detect ground fault in the rubber wheel system. For this purpose, we proposed negative potential equation between negative bus and ground and calculated negative potential according to system condition changes by estimating power feeding line insulation changes in steel wheel system and rubber wheel system, and equalizing DC power feeding system when ground fault occurred. Also, in order to estimate negative potential of real system, we modeled the rubber wheel system, and simulated normal status, grounding fault occurrence and power feeding line insulation changes. In normal status, negative potential did not rise significantly regardless of vehicle operation. When ground fault occurred, negative potential rose up over 300V regardless of fault resistance. However, we also observed that negative potential rose when power feeding line insulation dropped down under $1M{\Omega}$. In conclusion, our result shows that in case of rubber wheel system unlike steel wheel system, relay will be prevented maloperation and insulation status observation can be ensured when ground over voltage relay will be set 200V ~ 300V.

Stability Evaluation of Series and Parallel Varistor Combination Using Thermal Image Analysis (열화상 분석을 통한 바리스터의 직렬과 병렬 조합의 안전성 평가)

  • Eom, Ju-Hong;Cho, Sung-Chul;Lee, Tae-Hyung;Han, Hoo-Sek
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.8
    • /
    • pp.22-29
    • /
    • 2006
  • According to the recent revision of KS on the basis of the IEC, equipotential grounding systems has been come into focus and the use of surge protective devices(SPD) has been increased radically in order to operate the power system stably. $Z_nO$ varistor with non-linear resistance, which has an outstanding voltage-current(V-I) characteristic, is mainly used in power system to limit surge voltage and divert surge current. $Z_nO$ varistors are packaged several types based on the circuit assembly to be connected to a.c. power line. When the user assemble the $Z_nO$ varistors into parallel or series circuit package, there are my things to be taken into consideration including functions and thermal stability because they are directly related to the safety. We compare stabilities of each assembly type by measuring residual voltage, discharge current, leakage current and surface temperature concerned to the protection performances between a single device with a 40[kA] of current capacity and parallel or series circuits type of varistor package.

A Study on the Supply and Stray Current Distribution of the DC Railway Power System (직류전기철도 급전시스템에서 공급 및 누설전류 분포에 관한 연구)

  • Cho, Woong-Ki;Choi, Kyu-Hyoung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.6
    • /
    • pp.160-168
    • /
    • 2010
  • This paper presents the analysis of the current as stray current and supplied current of the substation, on the DC railway power system. In DC railway power supply system, the running rails are usually used as the return conductor(negative-polarity) for traction load current. This condition mainly focuses on economic considerations, since it does not require the installation of an additional return conductor. But, problems of low resistance between the running rails for the return conductor and earth allows a significant part of the return load current to leak into the earth. This current is normally called to as leakage or stary current. This stary currents creates serious problems for any electrified matter in the underground. Therefore, reduction of stray current of the DC railway power supply system is also of direct benefit to the operational and safety aspects of the DC railway systems. In this paper, deal with the analysis of the current distribution on the DC railway power system applied the common grounding system, using SPLIT of CDEGS program.

Investigation of Ice Impacts on Aluminum Skin Structure (알루미늄 표피 구조의 Ice 충돌 특성에 관한 연구)

  • Park, Gyu Cheol;Myeong, No Sin
    • Journal of the Korean Society for Aeronautical & Space Sciences
    • /
    • v.31 no.5
    • /
    • pp.110-116
    • /
    • 2003
  • With the growth of aircraft performance and needs for light aircraft, the problems associated with hail impacts on aircraft during flights and grounding become and important issue. These hail encounters can cause severe damages to aircraft and result in major concerns in safety and cost. Since nearly all external components of the commercial and military aircraft-in particular, the nose section and the leading edge of the wing and tail-are subject to damages, much effort has been put into understanding of this problem. However, most of the previous studies have focused on the composite components and few results have been reported for the metallic components. In this paper, we study the ice impacts on the aluminum component with the finite element analysis method utilizing commercial non-linear dynamics solver LS-DYNA. The results are compared with the experimental data and a simple measure of the ice impact effects is proposed.

Development and Application of Pre/Post-processor to EMTP for Sequence Impedance Analysis of Underground Transmission Cables (지중 송전선로 대칭분 임피던스 해석을 위한 EMTP 전후처리기 개발과 활용)

  • Choi, Jong-Kee;Jang, Byung-Tae;An, Yong-Ho;Choi, Sang-Kyu;Lee, Myoung-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.10
    • /
    • pp.1364-1370
    • /
    • 2014
  • Power system fault analysis has been based on symmetrical component method, which describes power system elements by positive, negative and zero sequence impedance. Obtaining accurate line impedances as possible are very important for estimating fault current magnitude and setting distance relay accurately. Especially, accurate calculation of zero sequence impedance is important because most of transmission line faults are line-to-ground faults, not balanced three-phase fault. Since KEPCO has started measuring of transmission line impedance at 2005, it has been revealed that the measured and calculated line impedances are well agreed within reasonable accuracy. In case of underground transmission lines, however, large discrepancies in zero sequence impedance were observed occasionally. Since zero sequence impedance is an important input data for distance relay to locate faulted point correctly, it is urgently required to analyze, detect and consider countermeasures to the source of these discrepancies. In this paper, development of pre/post processor to ATP (Alternative Transient Program) version of EMTP (Electro-Magnetic Transient Program) for sequence impedance calculation was described. With the developed processor ATP-cable, effects of ground resistance and ECC (Earth Continuity Conductor) on sequence impedance were analyzed.