• Title/Summary/Keyword: Ground surface potential gradient

Search Result 7, Processing Time 0.029 seconds

Characteristics of Potential Gradient for the Type of Structure Grounding Electrode (구조체 접지전극의 유형에 따른 전위경도 특성)

  • Gil Hyung-Jun;Choi Chun-Seog;Kim Hyang-Kon;Lee Bok-Hee
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.8
    • /
    • pp.371-377
    • /
    • 2005
  • This paper Presents the Potential gradient characteristics of structure grounding electrode when a test current flows through grounding electrode. In order to analyze the potential gradient of ground surface on structure grounding electrode, the reduced scale model has been used. The potential gradient has been measured and analyzed for types of structure using the hemispherical grounding simulation system in real time. The structures were designed through reducing real buildings and fabricated with four types on a scale of one-one hundred sixty. The supporter was made to put up with weight of structure and could move into vertical, horizontal, rotary direction. When a test current flowed through structure grounding electrodes, ground potential rise was the lowest value at electric cage type(type B). According to resistivity and absorption percentage In concrete attached to structure, the potential distribution of ground surface appeared differently.

Reduction of the the Ground Surface Potential Gradients by Installing Auxiliary Grounding Grids (보조접지그리드의 시설에 의한 대지표면전위경도의 저감)

  • 이승칠;엄주홍;이복희;김효진
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.2
    • /
    • pp.121-129
    • /
    • 2002
  • The present paper describes a technique for installing an effective grounding grids, the major objective is forced on the experimental evaluation of the performance and characteristics with the arrangement and installation method for grounding grids consisting of the means to protect electric shock, electronics and computerized facilities against lightning, switching and ground fault surges. The study is oriented on two major areas: (1) the analysis of the ground surface potential gradient with the arrangement of grounding grids, (2) the control of the dangerous ground surface potential rise. The experiments wee carried out with the impulse currents as a function of the installation method or arrangement of grounding grids. An installation method of the inclined auxiliary grounding grid was proposed to overcome the drawbacks of equally spared grounding grids, i.e. an appropriate design concept far the installation of grounding grids was found out, It has been shown that the installation of the intwined auxiliary grounding grid can also result in a mere than 50% decrease in the maximum potential gradient on the ground surface and enhance the level of safety for persons and electronic equipments..

Surface Potential Distribution according to Grounding Electrode Shapes (접지전극 형상에 따른 대지표면전위분포)

  • Baek, Young-Hwan;Lee, Bok-Hee;Li, Feng;Yang, Soon-Man;Lee, Kyu-Sun
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1360-1361
    • /
    • 2008
  • This paper presents the surface potential rise distribution near grounding electrodes produced by ground fault currents. The small-scale model with the foundation pedestal in hemispherical tank was used to simulate the ground fault condition of the electrical installations for street lamps. When entering the fault current through the test ground electrode, surface potential rise, potential gradient, touch and step voltages for different grounding electrode shapes were measured, and the results obtained were discussed.

  • PDF

The Analysis of Structure Grounding Using Reduced Scale Model (축소모델을 이용한 구조체 접지 분석)

  • Gil, Hyoung-Jun;Kim, Hyang-Kon;Han, Woon-Ki;Lee, Ki-Yeon;Choi, Chung-Seog
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2046-2048
    • /
    • 2005
  • This paper deals with ground potential rise of structure grounding electrode when a test current flows through grounding electrode. In order to analyze the potential gradient of ground surface on structure grounding electrode, the reduced scale model has been used. The structures were designed through reducing real buildings and fabricated with four types on a scale of one-one hundred sixty. The supporter was made to put up with weight of structure and could move into vertical, horizontal, rotary direction. When a test current flowed through structure grounding electrodes, ground potential rise was the lowest value at electric cage type(type B). According to resistivity and absorption percentage in concrete attached to structure, the potential distribution of ground surface appeared differently.

  • PDF

An Experimental Study on Ground Resistivity and Grounding Resistance of Water Environment (수상환경의 대지저항률 및 접지저항 측정의 실험적 연구)

  • Choi, Young-Kwan
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.15 no.4
    • /
    • pp.2343-2348
    • /
    • 2014
  • Main ground net of power plant is formed to protect human body from increase in potential gradient caused by grounding current during ground fault. Calculations during ground design are generally performed according to IEEE Std-80-2000 (Kepco Design Standard 2602). However, it is difficult to apply this Standard to water environment, and a grounding technology is required to secure grounding resistance of floating photovoltaic system. Therefore the aim of this paper is to investigate and analyze ground resistivity on the water surface and underwater of reservoir using Wenner 4-pin method, a general method of measuring ground resistivity. Also, grounding resistance of floating photovoltaic systems currently in operation was measured and analyzed using the voltage drop method suggested in the international standard (IEEE Std-81) to propose a grounding method for stable grounding of floating photovoltaic system. The resistivity at 1m below the surface of water ($126.3969[{\Omega}{\cdot}m]$) is mostly higher than resistivity at the river bed ($97.5713[{\Omega}{\cdot}m]$). Also the proposed grounding anchor method was determined as the most effective method of securing stable grounding resistance in floating photovoltaic systems and is expected to be utilized as a ground method for future floating photovoltaic generation systems.

Comparison of the Activity of Cortical Neurons According to Muscle Contraction Type between Post Stroke Hemiplegic Subjects and Healthy Subjects (뇌졸중 환자와 정상인의 근 수축 유형에 따른 피질 신경원의 활성도 비교)

  • Yang, Ga-Ae;Kim, Su-Hyon;Lim, Yong-Eun;Lee, Dong-Geol;Kim, Tae-Youl
    • The Journal of Korean Physical Therapy
    • /
    • v.21 no.1
    • /
    • pp.73-80
    • /
    • 2009
  • Purpose: In order to examine difference in the activity of potential of spinal neurons and cortical neurons according to muscle contraction type in post stroke hemiplegic subjects and healthy subjects, the present study conducted an experiment as follows. Methods: The subjects in the experimental group were 17 left-side hemiplegic subjects (9 female, 8 male; mean age, 63.41$\pm$9.86 years) with the right hand as the dominant hand selected among post stroke hemiplegic subjects, and 17 age matched healthy control subjects (10 female, 7 male; mean age, 64.12$\pm$12.07 years). Movement-related cortical potentials (MRCPs) were measured using surface electromyography and electroencephalography while concentric and eccentric movements were made alternately. Results: As to the pattern of the activity of MRCP, which indicates the activity of motor cortical neurons, we found that the amplitude is high (p<0.01), the length of excitement is short (p<0.01) and the ascending gradient of amplitude to the peak increases (p<0.05) in post stroke hemiplegic subjects' lesion sites different from healthy subjects. Conclusion: The activity of cortical neurons was no difference in activity according to contraction type was observed in post stroke hemiplegic subjects' lesion sites. This suggests that there is no distinction in the activity of cortical neurons between concentric contraction and eccentric contraction. Accordingly, if post stroke hemiplegic subjects' activity of motor cortex is analyzed by measuring MRCPs, it is considered useful in research on neural plasticity or as a ground of clinical effects in the area of physical therapy for the central nervous system.

  • PDF

Stability and Damage Evaluation of the Buddha Triad and 16 Rock-Carved Arhat Statues at Seongbulsa Temple in Cheonan, Korea (천안 성불사 마애석가삼존과 16나한상의 손상도 및 안정성 평가)

  • Yang, Hyeri;Lee, Chan Hee;Jo, Young Hoon
    • Korean Journal of Heritage: History & Science
    • /
    • v.53 no.4
    • /
    • pp.78-99
    • /
    • 2020
  • The Buddha triad and 16 Arhat statues carved on the rock surface at Seongbulsa temple is the only domestic remaining example of all 16 Arhats, so its academic value is very high. However, it is severely damaged and so required a stability evaluation through study of digital documentation and precise diagnosis for the purpose of comprehensive conservation. This process established that the Buddha statues were of similar scale, while the Arhats showed a wide variety of sizes, and the two kith and kin in the volume were larger than the Arhats. It was estimated that the statues of food for Buddha are similar to the Arhat statues, and most of the statues are well-formed. The rock used to carve the Buddha statues is banded gneiss with distinct foliation, alternating between white bands of quartz and feldspar and black bands composed of biotite. The Buddha statues have been damaged by physical weathering, discoloration, and biological contamination. In damage evaluations, joint (3.6 crack index), peeling (5.2%), exfoliation (1.7%), and falling off (0.1%) were observed on the rock surface of the Buddha statues. In particular, due to severe biological weathering, stage 9 and 10 biological coverage of the rock surface accounted for 57.5% of the total area, and stages 5 to 8 also accounted for a high share at 22.3%. The discoloration factors were shown to be dark brown and white with Fe, Ca, and S, and a large amount of C detected in the blackened contaminants, and the damage weight high in all areas. Discontinuities in different directions were identified in the rock surface. Analysis of potential rock failure types indicated that there is a possibility of plane and toppling failure, but wedge failure is unlikely to occur. The mean ultrasonic velocity of the main rock surface was 2,463m/sec, the lower part of the left side with a large number of joints was relatively low, and the highly weathered (HW) type to the completely weathered (CW) type concentrated distribution, showing weak properties. For the Buddha statues, conservation treatment is required for about 14.9% of micro cracks and 58.9% of exfoliation cracks. In addition, in order to improve the conservation environment of the Buddha statues, maintenance of drainage and ground preparations for the rock surface gradient and plants are necessary, and protection facilities should be reviewed for long-term conservation and management purposes.