• 제목/요약/키워드: Ground heat

검색결과 892건 처리시간 0.025초

국내의 주요 지역에서 밀폐형 열교환기의 열전도도 측정 (Measurements of In-situ Thermal Conductivity of Closed Type Ground Heat Exchanger in Korea)

  • 임효재;정계훈;한지원;박경우
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.3401-3406
    • /
    • 2007
  • This study was performed to acquire the reliable in-situ thermal conductivity of closed type ground heat exchanger used in ground source heat pump. We selected four sites(Cheonan, Daejeon, Daegu, Gwangju) which are central area of South Korea. Test results show that the effective thermal conductivities are 2.33 W/m$^{\circ}C$, 2.50 W/m$^{\circ}C$, 2.75 W/m$^{\circ}C$ and 2.86 W/m$^{\circ}C$. From this data, we can see that thermal conductivity varies about the range of 23% with the sites. Also, thermal conductivity increases up to 20% by changing grouting material from low salica sand to high one.

  • PDF

CFD 모델을 이용한 열미로의 지중열원 활용에 관한 사례 연구 (Case Study on Application of Ground Heat Source in Thermal Labyrinth by CFD Model)

  • 민준기;남선영
    • 한국지열·수열에너지학회논문집
    • /
    • 제10권1호
    • /
    • pp.1-6
    • /
    • 2014
  • In order to evaluate the performance of ground heat source in thermal labyrinth on pre-heating in winter season and pre-cooling in summer season, the followings are made as a conclusion through case study of H project by using the weather data from Korea meteorological administration and CFD model. By making outdoor air inlet via ground heat source in thermal labyrinth for conduction, convection and etc., the temperature rise is $13.4^{\circ}C$as the effect of pre-heating in winter season. On the other hand, as the effect of pre-cooling in summer season, the temperature decrease is $7.2^{\circ}C$. The energy saving rate by the application of ground heat source in thermal labyrinth is 9.1%.

지중열원 열펌프 시스템의 난방성능 해석 (A Study on the Heating Performance of Ground Source Heat Pump System)

  • 우정선;김대기;이세균
    • 설비공학논문집
    • /
    • 제16권12호
    • /
    • pp.1175-1182
    • /
    • 2004
  • Installations of vertical boreholes for the ground source heat pump system are expensive to install. One way to reduce the initial cost is to increase the specific heat extraction rate of borehole system. However, as the specific heat extraction rate increases the temperature of borehole fluid decreases with the resultant lower Coefficient Of Performance in Heating(COPH) of heat pump system. The purpose of this study is to provide the basic informations about the performance of heat pump system with the specific heat extraction rate and soil thermal properties such as thermal conductivity and temperature. It is shown that the specific heat extraction rate is the most important parameter for the ground source heat pump system. To obtain the reasonable COPH value (COPH > 3) the heat extraction rate should be about 25 W/m or less. Accurate measurements of soil thermal properties are also very important to design the system properly. The effects of borehole thermal resistances are also examined in this study.

충적대수층을 이용한 지열히트펌프시스템의 냉방성능 (Cooling Performance of Geothermal Heat Pump using Alluvium Aquifer)

  • 강병찬;박준언;이철우;송윤호
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2009년도 추계학술대회 논문집
    • /
    • pp.561-566
    • /
    • 2009
  • Alluvium is sedimentary stratum and composed of gravel, sand, silt, clay. Permeability of alluvium is the higher. If alluvium have lots of aquifer, will be of great use heat source and heat sink of heat pump. Alluvium aquifer contain the thermal energy of surrounding ground. Also geothermal heat pump using alluvium aquifer reduce expenses than general geothermal heat pump, because geothermal heat pump using alluvium aquifer make use of single well. In this study geothermal heat pump using alluvium aquifer was installed and tested for a building. The heat pump capacity is 30USRT. Temperature of ground water is in $12{\sim}17^{\circ}C$ annually and the quality of the water is as good as living water. The heat pump cooling COP is 4.4 ~ 4.7. The system cooling COP is 3.25 ~ 3.6. This performance is as good as BHE type ground source heat pump.

  • PDF

단독주택 적용 지열 히트펌프 시스템의 성능 분석 (Performance Simulation of Ground-Coupled Heat Pump(GCHP) System for a Detached House)

  • 손병후;최종민;최항석
    • 설비공학논문집
    • /
    • 제23권6호
    • /
    • pp.392-399
    • /
    • 2011
  • Ground-coupled heat pump(GCHP) systems have been shown to be an environmentally-friendly, efficient alternative to traditional cooling and heating systems in both residential and commercial applications. Although some work related to performance evaluation of GCHP systems for commercial buildings has been done, relatively little has been reported on the residential applications. The aim of this study is to evaluate the cooling and heating performances of a vertical GCHP system applied to an artificial detached house($117\;m^2$) in Seoul. For this purpose, a typical design procedure was involved with a combination of design parameters such as building loads, heat pump capacity, borehole diameter, and ground thermal properties, etc. The cooling and heating performance simulation of the system was conducted with different prediction times of 8760 hours and 240 months. The performance characteristics including seasonal system COP, average annual power consumption, and temperature variations related to ground heat exchanger were calculated and compared.

수평형 지중 열교환기 시스템의 시공비 및 영향인자 분석 (Analysis of Construction Cost and Influence Factors on Horizontal Ground Heat Exchangers)

  • 윤석;이승래
    • 신재생에너지
    • /
    • 제10권3호
    • /
    • pp.6-13
    • /
    • 2014
  • This paper presents a computational study of thermal performance and construction cost of horizontal ground heat exchangers (GHEs). GLD (ground loop design) simulations of various type of GHEs were carried out. Construction costs were also calculated based on standard estimating, and compared with vertical type GHE system. Besides that, dummy regression analysis was conducted to study the influence of design parameters on the simulation results in horizontal ground heat exchanger system.

히트펌프용 수직형 지중열교환기의 성능에 관한 연구 (A Study on Performance of Vertical Ground Heat Exchanger for Heat Pump)

  • 장기창;정민호;윤형기;나호상;유성연
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2007년도 춘계학술대회
    • /
    • pp.466-469
    • /
    • 2007
  • Heat pumps are used for air-conditioning systems in commercial buildings, schools, and factories because of low operating and maintenance costs. These systems use the earth as a heat source in heating mode and a heat sink in cooling mode. Ground heat exchangers are classified by a horizontal type and vertical type according to the installation method. A horizontal type means that a heat exchanger is laid in the trench bored in 1.2 to 1.8 m depth. And a vertical type is usually constructed by placing small diameter high density polyethylene tube in a vertical borehole. Vertical tube sizes range from 20 to 40 mm nominal diameter. Borehole depth range between 100 and 200 m depending on local drilling conditions and available equipment. In this study, to evaluate the performance of single u-tube with bentonite grouting, single u-tube with broken stone grouting and double n-tube bentonite grouting of vertical ground heat exchangers, test sections are buried on the earth and experimental apparatus is installed. Therefore the heat transfer performance and pressure loss of these are estimated.

  • PDF

태양열 및 지중열원을 이용한 히트펌프 시스템의 최적이용법에 관한 연구 (Study on the Optimum Design of a Heat Pump System Using Solar and Ground Heat)

  • 남유진
    • 설비공학논문집
    • /
    • 제24권6호
    • /
    • pp.509-514
    • /
    • 2012
  • In this research, a heat pump system with a heat source network is suggested which utilizes solar heat and ground heat as heat source for cooling and heating. This paper describes the summary of the suggested system and the results of the annual energy simulation. The heating and cooling loads, the electric consumption and the COP were calculated by TRNSYS 16 and evaluated in the cases of different local conditions and different system compositions. In the results, the superiority of the suggested system has been quantitatively evaluated comparing with the conventional heat pump system using one heat source. Furthermore, it was more significant in cold climate, in which the heating COP was 146% increased compared the air source heat pump system, than it in subtropical climate, 119% increased.

학교 건물용 지열 히트펌프 시스템 설계와 지중 순환수 온도 변화 분석 (Design of Ground-Coupled Heat Pump (GCHP) System and Analysis of Ground Source Temperature Variation for School Building)

  • 손병후
    • 한국지열·수열에너지학회논문집
    • /
    • 제16권1호
    • /
    • pp.17-25
    • /
    • 2020
  • Ground-coupled heat pump (GCHP) systems have become an efficient alternative to conventional cooling and heating methods due to their higher energy using efficiency. Although some experimental and simulation works related to performance analysis of GCHP systems for commercial buildings have been done, relatively little has been reported on the performance evaluation of GCHP systems for school buildings. The purpose of this simulation study is to evaluate the performance of a hypothetical GCHP system for a school building in Seoul. We collected various data of building specifications and construction materials for the building and then modeled to calculate hourly building loads with SketchuUp and TRNSYS V17. In addition, we used GLD (Ground Loop Design) V2016, a GCHP system design and simulation software, to design the GCHP system for the building and to simulate temperature of circulating water in ground heat exchanger. The variation of entering source temperature (EST) into the system was calculated with different prediction time and then each result was compared. For 20 years of prediction time, EST for baseline design (Case A) based on the hourly simulation results were outranged from the design criteria.

파이프 순환수의 수치해석 모사를 통한 수직 밀폐형 지중열교환기 단면의 열전달 효율 평가 (Numerical Evaluation of Heat Transfer un Ground Heat Exchanger Considering Flow through U-loop)

  • 길후정;이강자;이철호;최항석
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2009년도 춘계학술대회 논문집
    • /
    • pp.583-587
    • /
    • 2009
  • This paper presents a series of numerical simulations on the thermal performance and sectional efficiency of a closed-loop vertical ground heat exchanger (U-loop) equipped in a geothermal heat pump system (GHP). A 3-D finite volume analysis (Fluent) was used to simulate the operating process of the closed-loop vertical ground heat exchanger by considering the effect of the thickness of HDPE pipe and grout thermal properties, distance between the inflow and outflow pipes, and the effectiveness of the latticed HDPE pipe system. It was observed that the thermal interference between the two strands of U-loop is of importance in determining the efficiency of the ground heat exchanger, and thus it is highly recommendable to modify the cross section configuration of the conventional U-loop system by including a thermally insulating latice between the two strands.

  • PDF