The Design Flowchart of Earthing System for Building Electrical Installations in Accordance with International Standards (국제표준에 따른 건축전기설비의 접지시스템 설계순서)

  • Lee, Ju-Cheol;Yeom, Jin-Geun;Jeong, Seung-Hyun;Byeon, Cheol-Gyun;Kim, Jae-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.8
    • /
    • pp.113-120
    • /
    • 2014
  • In this paper, designing of an earthing system in accordance with international standards with regard to 22.9kV-y multi-grounded neutral system is discussed and confirmed that the consumer's earthing system can be a part of a global earthing system by interconnecting its earthing system with the neutral conductor of 22.9kV-y multi-grounded system. Further, it is proposed that some modification of the earthing system design flowchart given in the international standards are necessary when considering the equipotential bonding, lightning protection, and telecommunications facilities as well as the basic safety requirements.

A Study on the Optimal Divergence Spacing of the Connecting Grounding Rod to the Dangerous Voltage in the Global Earthing Network of Urban Rail Transit (도시철도 통합접지망에서의 위험전압에 따른 연접접지봉의 최적 분기간격에 관한 연구)

  • Jung, Ho-Sung;Park, Young;Kim, Hyeng-Chul;Kim, Jin-Hee;Kim, Jae-Moon;Cho, Dae-Hoon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.9
    • /
    • pp.1374-1379
    • /
    • 2012
  • Urban rail transit tends to global grounding system in order to control ground potential rise and potential differences between electric equipments. In addition, global grounding system can discharge the large capacity surge current to the ground safely. Since some railway electric equipments are installed all section of line, the global grounding system connected with the connecting grounding wire is more effectively. However, if the fault occurred in the connecting grounding wire area, some dangerous voltage is generated. So, the installation of additional grounding rod will be required. In this study, the global grounding system is simulated using CDEGS program to analyze the divergence spacing of additional ground rod depending on dangerous electric potential characteristics. Grounding net of the each station is modelled in depending on the size of the platform, and the spacing of the connecting grounding rod are compared 50m, 100m, 250m and 400m. Simulation results considering of earth resistivity and underground condition of the connecting grounding wire, spacing of the connecting grounding rod is that less than 250m to spacing of the ground rod was appropriately confirmed.