Greenhouse Heating Technology Development by using Riverbank Filtration Water (강변여과수를 이용한 온실난방기술 개발)

  • Moon, Jong-Pil;Lee, Sung-Hyoun;Kwon, Jin-Kyung;Kang, Youn-Ku;Ryou, Young-Sun;Lee, Su-Jang
    • Journal of The Korean Society of Agricultural Engineers
    • /
    • v.53 no.6
    • /
    • pp.145-152
    • /
    • 2011
  • In order to heat greenhouse nearby river channel, riverbank filtration water source heat pump was developed for getting plenty of heat flux from geothermal energy. Recharging well, thermal storage tank with separating insulation plate and filtering tank for eliminating iron, manganese were mainly developed for making the coefficient of performance (COP) of heat pump higher. Heating system using riverbank filtration water source heat pump was installed at a paprika greenhouse in the Jinju region where a single fold of vinyl cover and 2 layers of horizontal thermal curtain were installed as a part of temperature keeping and heat insulation with a greenhouse area of 3,185 $m^2$. 320,000 kcal/h was supplied for performing a site application tests. A greenhouse heating test was performed from Feb. 1, 2011 to Apr. 30, 2011. As the result of that, COPh of the heat pump was measured in the range of 4.0~4.5, while COPS of the system was represented as 2.9~3.3. COP measured of the heat pump was very good and well responded to indoor heating temperature of the environment control system of a greenhouse.

Cooling Performance of Cooling Tower-Assisted Ground-Coupled Heat Pump (GCHP) System Applied in Hospital Building (병원 건물에 설치된 냉각탑 병용 지열 히트펌프 시스템의 냉방 성능)

  • Sohn, Byonghu;Lee, Doo-Young;Min, Kyung-Chon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.12 no.1
    • /
    • pp.7-16
    • /
    • 2016
  • This paper presents the measurement and analysis results for the cooling performance of ground-coupled heat pump (GCHP) system using a cooling tower as a supplemental heat rejector. In order to demonstrate the performance of the hybrid approach, we installed the monitoring equipments including sensors for measuring temperature and power consumption, and measured operation parameters from May 1 to October 30, 2014. The results showed that the entering source temperature of brine returning from the ground heat exchanger was in a range of design target temperature. Leaving load temperatures to building showed an average value of $11.4^{\circ}C$ for cooling season. From the analysis, the daily performance factor (PF) of geothermal heat pumps ranged from 4.4 to 5.2, while the daily PF of hybrid GCHP system varied from 3.0 to 4.0 over the entire cooling season.

Study on the Operation of the Solar Heating System with Ground Source Heat Pump as a Back-up Device (지열히트펌프 보조열원식 태양열 난방급탕 시스템 작동에 관한 연구)

  • Kim, Hwidong;Baek, Namchoon;Lee, Jinkook;Shin, Uchul
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2010.06a
    • /
    • pp.197.2-197.2
    • /
    • 2010
  • The study on the operation characteristics of solar space and water heating system with ground source heat pump (GSHP) as a back-up device was carried out. This system, called solar thermal and geothermal hybrid system (ST/G), was installed at Zero Energy Solar House II (KIER ZeSH-II) in Korea Institute of Energy Research. This ST/G hybrid system was developed to supply all thermal load in a house by renewable energy. The purpose of this study is to find out that this system is optimized and operated normally for the heating load of ZeSH-II. Experiment was continued for seven months, from October to April. The analysis was conducted as followings ; - the contribution of solar thermal system. - the appropriateness of GSHP as a back-up device. - the performance of solar thermal and ground source heat pump system respectively. - the adaptation of thermal peak load - the operation characteristics of hybrid system under different weather conditions. Finally the complementary measures for the system simplification was referred for the commercialization of this hybrid system.

  • PDF

Effect of the Geothermal Heat-pump on alleviation of the Urban Heat Island (지열히트펌프의 도심 열섬 저감 효과의 검토)

  • Son, Won-Tug
    • Journal of the Korean Solar Energy Society
    • /
    • v.36 no.3
    • /
    • pp.45-52
    • /
    • 2016
  • Remarkable air temperature increases in urban areas are known as heat island phenomenon. In this study, we analyzed the effects of renewable energy on the heat island phenomenon in urban area by numerical method. The results showed that the use of renewable energy reduces the building energy use in urban area and contributes the alleviation of the Urban Heat Island Effects.

Design of Ground-Coupled Heat Pump (GCHP) System and Analysis of Ground Source Temperature Variation for School Building (학교 건물용 지열 히트펌프 시스템 설계와 지중 순환수 온도 변화 분석)

  • Sohn, Byonghu
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.16 no.1
    • /
    • pp.17-25
    • /
    • 2020
  • Ground-coupled heat pump (GCHP) systems have become an efficient alternative to conventional cooling and heating methods due to their higher energy using efficiency. Although some experimental and simulation works related to performance analysis of GCHP systems for commercial buildings have been done, relatively little has been reported on the performance evaluation of GCHP systems for school buildings. The purpose of this simulation study is to evaluate the performance of a hypothetical GCHP system for a school building in Seoul. We collected various data of building specifications and construction materials for the building and then modeled to calculate hourly building loads with SketchuUp and TRNSYS V17. In addition, we used GLD (Ground Loop Design) V2016, a GCHP system design and simulation software, to design the GCHP system for the building and to simulate temperature of circulating water in ground heat exchanger. The variation of entering source temperature (EST) into the system was calculated with different prediction time and then each result was compared. For 20 years of prediction time, EST for baseline design (Case A) based on the hourly simulation results were outranged from the design criteria.

RETScreen(R) Ground Source Heat Pump(GSHP) Application for Korea (RETScreen(R) 지중열 히트펌프 모듈 한국 적용에 관한 연구)

  • Naveed Ahmed T;Park Sanghyun;Lee Euijoon;Kim Byungseon
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2005.06a
    • /
    • pp.678-683
    • /
    • 2005
  • Korea is utilizing geothermal resources mainly in the bathing and swimming facilities with very few applications for industrial processes or space heating. It is estimated that geothermal capacity and annual utilization are 36.2MWt and 761TJ/year as compared to global capacity and annual utilization of 15,145MWt and 190,699 TJ/year. RETScreen software is a user's friendly tool for analyzing the technical and financial pre-feasibility of potential Renewable Energy (RE) projects that promotes the use of RE applications through the capacity building of planners, decision-makers and industries for successful implementation of RE projects. Strong ties between Canada and Korean organizations such as Korean Solar Energy Society (KSES) and the Korea Institute of Energy Research (KIER) exist for knowledge transfer about RETScreen. In this paper, an overview of RETScreen and its ground source heat pump (GSHP) model with a practical example of an existing project of a community hall in Canada are described to illustrate effectiveness of RETScreenin the implementation of RE technologies. The same community hall project is then evaluated hypothetically considering its location at Kangnyng, Korea. The main objective is to demonstrate how RETScreen GSHP model can also be utilized effectively for GSHP applications in Korea.

  • PDF

Verification experiment of a ground source multi-heat pump at cooling mode (지열원 시스템 히트펌프의 냉방 성능 특성에 관한 실증 연구)

  • Lim, Hyo-Jae;Kang, Shin-Hyung;Choi, Jae-Ho;Choi, Jong-Min;Moon, Je-Myung;Kwon, Young-Seok;Kwon, Hyung-Jin;Kim, Rock-Hee
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.21-26
    • /
    • 2008
  • Recently, small and medium-sized buildings have employed a multi-heat pump. The major benefits of the multi-heat pump over a conventional system are that it is easier system to maintain along with a diversification of facility use, and high comfortability. The performance of multi-heat pump systems can be enhanced by using geothermal energy instead of air source energy. This paper describes the multi-heat pumps applied in an ground source heat pump system for an actual building. The performance of a ground source multi-heat pump installed in the field was investigated in cooling mode. The maximum COP of the systems with single U-tube and double tube ground loop heat exchangers were 6.6 and 6.0, respectively. It is suggested that the new algorithms to control the flow rate of secondary fluid for ground loop heat exchanger have to be developed in order to enhance the performance of the system.

  • PDF

The Field Test of Heat Pump Cooling & Heating System using the water-purifying device (수도시설을 이용한 지열냉난방시스템의 실증연구)

  • Hwang, Ki-Sup;Jung, Woo-Sung;Ahn, Young-Sub
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.629-634
    • /
    • 2007
  • The Alternative energy has lately attracted considerable attention due to the high oil price and environment problem. In this study, field test of facility for using the geothermal energy source from water-purifying device was constructed and monitoring devices are installed to estimate the efficiency of this system. Initial installation cost can be saved efficiently by connecting a heat pump system into the existing pumping well in site of water-purifying in Cheongju. One set of monitoring results during summer was presented and analyzed.

  • PDF

An Experimental Study on the Effects of Operating Variables on the Cooling and Heating Performance of Geothermal Heat Pump (지열 히트펌프에서 운전변수가 냉난방 성능에 미치는 영향에 대한 실험연구)

  • Chang, Keun-Sun;Kang, Hee-Jeong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.8
    • /
    • pp.562-570
    • /
    • 2011
  • In this research, an experimental study is performed to investigate the effects of system operating variables on the cooling and heating characteristics of heat pump system using geothermal heat source and carbon dioxide as a refrigerant. System variables analyzed include compressor frequency, electronic expansion valve opening, refrigerant charge, secondary fluid temperature and flow rate. Results show that optimum refrigerant charge and electronic expansion valve opening position exist at the maximum point of COP curve, and both cooling and heating capacity increase but COPs decrease with the increase of compressor frequency. The change of a secondary fluid temperature leads to variation of overheat area and enthalpy difference in the evaporator and gas cooler. which again results in considerable variations of cooling and heating capacity and COP. In the case of effects of secondary water fluid flow rate, both cooling capacity and COP increase with the increase of secondary flow in evaporator or gas cooler, whereas heating capacity and COP decrease with the increase of flow rate in gas cooler.

Numerical Analysis on the Heat Transfer Characteristics of HDPE Pipe with the Variation of Geometries for Ground Loop Heat Exchangers (지중열교환기의 고밀도폴리에틸렌 배관 형상에 따른 열전달 성능 특성에 대한 수치해석적 연구)

  • Mensah, Kwesi;Choi, Jong Min
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.12 no.4
    • /
    • pp.33-39
    • /
    • 2016
  • A ground source heat pump (GSHP) system is recommended as a heating and cooling system to solve the pending energy problem in the field of air conditioning, because it has the highest efficiency. However, higher initial construction cost works as a barrier to the promotion and dissemination of GSHP system. In this study, numerical analysis on the characteristics of high density polyethylene (HDPE) pipe with spiral inside was executed. The heat transfer and flow characteristics of it were compared with those of a conventional smooth HDPE pipe. The heat transfer coefficient and pressure drop of the spiral HDPE pipe were higher than those of the smooth HDPE pipes at the same fluid flow rate. By decreasing the flow rate, the spiral HDPE pipe represented similar values of heat transfer coefficient and pressure drop to the smooth HDPE pipe. The lower flow rate of the spiral HDPE pipe comparing with it of the smooth HDPE pipe is estimated to reduce the length of the ground loop heat exchanger.