• 제목/요약/키워드: Geothermal heat pump

검색결과 339건 처리시간 0.027초

지열 히트펌프에서 운전변수가 냉난방 성능에 미치는 영향에 대한 실험연구 (An Experimental Study on the Effects of Operating Variables on the Cooling and Heating Performance of Geothermal Heat Pump)

  • 장근선;강희정
    • 설비공학논문집
    • /
    • 제23권8호
    • /
    • pp.562-570
    • /
    • 2011
  • In this research, an experimental study is performed to investigate the effects of system operating variables on the cooling and heating characteristics of heat pump system using geothermal heat source and carbon dioxide as a refrigerant. System variables analyzed include compressor frequency, electronic expansion valve opening, refrigerant charge, secondary fluid temperature and flow rate. Results show that optimum refrigerant charge and electronic expansion valve opening position exist at the maximum point of COP curve, and both cooling and heating capacity increase but COPs decrease with the increase of compressor frequency. The change of a secondary fluid temperature leads to variation of overheat area and enthalpy difference in the evaporator and gas cooler. which again results in considerable variations of cooling and heating capacity and COP. In the case of effects of secondary water fluid flow rate, both cooling capacity and COP increase with the increase of secondary flow in evaporator or gas cooler, whereas heating capacity and COP decrease with the increase of flow rate in gas cooler.

R410A 대체냉매 적용 지열히트펌프 개발 (The development of a ground source heat pump using R410A)

  • 김지동;정봉철;정일권
    • 한국지열·수열에너지학회논문집
    • /
    • 제3권1호
    • /
    • pp.17-22
    • /
    • 2007
  • The growth of domestic energy demand is rapidly increased for the industrialization and the improvement of the living standards. It is also recognised that the importance of the use of environmentally friendly energy and high efficient equipment. Ground Source heat pumps (GSHP) using earth as heat source or sink are outstanding environmentally friendly energy systems which have high thermal efficiency when compared to conventional heating and cooling system. So government employs a policy and increase investment for expanding renewable energy market volume. Especially is established a system for obligatory usage of renewable energy to achieve 5% renewable energy diffusion rate by 2011. And the market demand for the ground source heat pump is rapidly growing due to its strong advantages. However domestic situation usually have been depended on the import of ground source heat pumps. In this paper, the results of development of a ground source heat pump using refrigerant R410A are reported.

  • PDF

폐열이용 열펌프시스템의 성능에 관한 연구 (Performance Analysis on a Heat Pump System using Waste Heat)

  • 박윤철;송뢰;고광수
    • 한국지열·수열에너지학회논문집
    • /
    • 제14권4호
    • /
    • pp.53-60
    • /
    • 2018
  • This study was conducted for analysis of a heat pump system using waste heat in an enclosed space such as a green house. The model was developed with mathematical equations in literature and Engineering Equation Solver (EES) was used to get the solution of the developed equations. The simulation results have 5% of reliability comparing the results with actual test data of heat pump system's dynamic operation. The operating performance of the system was calculated with variation of working fluid temperature in the thermal storage tank such as $25^{\circ}C$, $35^{\circ}C$, $45^{\circ}C$ and $55^{\circ}C$. As a result, the system's the highest total heating capacity shows 280 kWh and the storage tank's operating time decreased as the starting storage tank's temperature was high.

지중열교환기의 고밀도폴리에틸렌 배관 형상에 따른 열전달 성능 특성에 대한 수치해석적 연구 (Numerical Analysis on the Heat Transfer Characteristics of HDPE Pipe with the Variation of Geometries for Ground Loop Heat Exchangers)

  • ;최종민
    • 한국지열·수열에너지학회논문집
    • /
    • 제12권4호
    • /
    • pp.33-39
    • /
    • 2016
  • A ground source heat pump (GSHP) system is recommended as a heating and cooling system to solve the pending energy problem in the field of air conditioning, because it has the highest efficiency. However, higher initial construction cost works as a barrier to the promotion and dissemination of GSHP system. In this study, numerical analysis on the characteristics of high density polyethylene (HDPE) pipe with spiral inside was executed. The heat transfer and flow characteristics of it were compared with those of a conventional smooth HDPE pipe. The heat transfer coefficient and pressure drop of the spiral HDPE pipe were higher than those of the smooth HDPE pipes at the same fluid flow rate. By decreasing the flow rate, the spiral HDPE pipe represented similar values of heat transfer coefficient and pressure drop to the smooth HDPE pipe. The lower flow rate of the spiral HDPE pipe comparing with it of the smooth HDPE pipe is estimated to reduce the length of the ground loop heat exchanger.

지열발전을 위한 HFC 유기랭킨 사이클의 시뮬레이션 (Simulation of HFC organic Rankine cycles for geothermal power generation)

  • 백영진;김민성;장기창;윤형기;이영수;나호상
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2009년도 춘계학술대회 논문집
    • /
    • pp.569-572
    • /
    • 2009
  • In this study, HFC ORCs (Organic Rankine Cycles) are investigated for a low-temperature geothermal power generation by a simulation method. A steady-state simulation model is developed to analyze and optimize cycle's performance. The model contains a turbine, a pump, an expansion valve and heat exchangers. The turbine and pump are modelled by an isentropic efficiency. Simulations were carried out for the given heat source and sink inlet temperatures, and given flow rate that is based on the typical power plant thermal-capacitance-rate ratio. 3 HFC fluids are considered as a candidate for a working fluid of low-temperature ORCs. In this study, all optimized HFC ORCs are shown to yield almost the same performance in terms of power for a low-temperature heat source of about $100^{\circ}C$.

  • PDF

스탠딩컬럼웰(SCW)을 적용한 지열히트펌프의 성능에 대한 매개변수 연구 (A parametric study on the performance of heat pump using standing column well(SCW))

  • 장재훈;박두희
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2010년도 춘계 학술발표회
    • /
    • pp.625-630
    • /
    • 2010
  • Parametric study was performed using the SCW numerical model for evaluating the performance of the SCW. The five ground related parameters, which are porosity, hydraulic conductivity, thermal conductivity, specific heat, geothermal gradient, and five SCW design parameters, which are pumping rate, well depth well diameter, dip tube diameter, bleeding rate, were used in the study. Numerical simulations were performed for short-term (24-hour) simulation. The study results indicate that the parameters that have important influence on the performance of SCW were hydraulic conductivity, thermal conductivity, geothermal gradient, pumping rate, and bleeding rate. Overall, this study showed that various factors had a cumulative influence on the performance of the SCW, and a numerical simulation can be used to accurately predict the performance of the SCW.

  • PDF

투자비회수기간법을 이용한 공공청사 적용 축열식 지열히트펌프 시스템의 경제성 평가 (Economic Estimation of Heat Storage Type Geothermal source Heat Pump System Adopted in Government office Building by a Payback Period Method)

  • 고명진;오중근;김용인;김용식
    • 한국태양에너지학회 논문집
    • /
    • 제27권4호
    • /
    • pp.175-182
    • /
    • 2007
  • Geothermal-energy has been getting popular as a natural energy source for green buildings these days. As a result Geothermal Source Heat Pump System (GSHPs) was being recognized effective alternative systems to conventional heating and cooling systems owing to their higher energy utilization efficiency. But GSHPs has not been popularized thereby the large amount of initial cost of the system and insufficiency of studies for economic estimation. Therefore GSHPs are being developed to make up for the weak points that are the large amount of initial cost of the system and much annual electricity consumption. In this paper, economic estimation was conducted by payback period method and it shows that the pay back period of Heat Storage Type GSHPs was calculated 6.8 years compared with the absorption Chiller-Heater system and 8.2 years compared with the Ice storage-Boiler system. Heat Storage Type GSHPs also has the lower annual source energy consumption than the conventional heating and cooling systems because of using nighttime electricity.

지중 유효 열물성 산정 및 지중열교환기 성능에 대한 보어홀 열저항의 영향 (Evaluation of Ground Effective Thermal Properties and Effect of Borehole Thermal Resistance on Performance of Ground Heat Exchanger)

  • 손병후
    • 한국지열·수열에너지학회논문집
    • /
    • 제8권4호
    • /
    • pp.32-40
    • /
    • 2012
  • Geothermal heat pump(GHP) systems use vertical borehole heat exchangers to transfer heat to and from the surrounding ground via a heat carrier fluid that circulates between the borehole and the heat pump. An Important feature associated with design parameters and system performance is the local thermal resistances between the heat carrier flow channels in the borehole and the surrounding ground. This paper deals with the in-situ experimental determination of the effective thermal properties of the ground. The recorded thermal responses together with the line-source theory are used to determine the thermal conductivity and thermal diffusivity, and the steady-state borehole thermal resistance. In addition, this paper compares the experimental borehole resistance with the results from the different empirical and theoretical relations to evaluate this resistance. Further, the performance simulation of a GHP system with vertical borehole heat exchangers was conducted to analyze the effect of the borehole thermal resistance on the system performance.

시설원예를 위한 수평형 지열 히트펌프의 냉방성능 해석 (Cooling Performance of Horizontal Type Geothermal Heat Pump System for Protected Horticulture)

  • 유영선;강연구;강금춘;김영중;백이
    • 생물환경조절학회지
    • /
    • 제17권2호
    • /
    • pp.90-95
    • /
    • 2008
  • 수직형에 비해 비교적 가격이 저렴하고 냉난방을 동시에 할 수 있는 농업시설에 적합한 10RT 규모의 수평형 지열히트펌프 시스템을 $240m^2$ 면적의 온실에 설치하고, 이 시스템의 냉방성능을 분석하였다. 응축기 출구온도가 $40^{\circ}C$에서 $58^{\circ}C$로 상승함에 따라 소비전력은 11.5kW에서 15kw로 상승하였으며, 고압이 1,617kpa에서 2,450kPa로 변화하였다. 냉방성능계수는 지중온도 $25.5^{\circ}C$에서 2.7 수준이었으며 지온이 상승함에 따라 하강하여 $33.5^{\circ}C$에서 2.0 수준이었다. 또한 온실 내부로부터 흡수하는 열량(냉방열량)은 같은 지중온도 수준에서 각각 28.8kW, 26.5kW이었다. 가동 8시간 후 지열교환기가 설치된 60cm깊이의 지온은 $14.3^{\circ}C$가 상승하였으며 150cm는 $15.3^{\circ}C$가 상승하였다. 반면 지열교환기가 매설되지 않은 60cm 깊이는 2.4, 150cm 깊이는 $4.3^{\circ}C$의 지온상승을 보였다. 열매 체유가 지열교환기를 통과한 후 평균 $7.5^{\circ}C$의 온포가 하강하였으며, 토양온도가 평균 $27.5^{\circ}C$ 수준에서 토양으로 방출하는 열량은 평균 46kw로 지중열교환기의 단위 길이 당 약 36.8W의 열량을 방출하는 것으로 분석되었다. 팬코일 유닛이 온실로부터 흡수하는 냉방 열량은 평균 28.2kW이었으며, 열매체유의 온도는 $4.2^{\circ}C$ 상승하였다. 축열조내 열전달매체유의 온도가 $26.0^{\circ}C$에서 $2.0^{\circ}C$까지 하강하는데 3시간이 소요되었으며, 평균 축열율은 29.7kW, 총 축열량은 321MJ이었다. 또한 $2.0^{\circ}C$까지 냉열을 축열한 후 $25.4^{\circ}C$까지 방열되는 시간은 외기온이 평균 $28.5^{\circ}C$일 때 4시간이었고, 총 313.0MJ의 에너지가 방열되었으며, 이때 평균 방열율은 21.7kW인 것으로 분석되었다.

Analysis on Heating Effects of the Vertical Type Geothermal Heat Pump System

  • Kang, Youn Ku;Ryou, Young Sun;Jang, Jae Kyung;Kim, Young Hwa
    • Journal of Biosystems Engineering
    • /
    • 제39권2호
    • /
    • pp.69-75
    • /
    • 2014
  • Purpose: This paper is aimed at analyzing the heating performance of the vertical closed loop type Geothermal Heat Pump System (GHPS) distributing the farm site and providing basic data of the GHPS. Method: Seedling greenhouse heating was made from October 2012 to May 2013. The seedling greenhouse was divided into 4 sectors (A, B, C and D zone, total $3,300m^2$) with different temperatures. It was heated from 5PM to 8AM, and during the night the greenhouse was covered by non-woven fabric thermal curtains along the upper 2m of the greenhouse for temperature maintenance. In order to analyze the heating performance of the GHPS, power consumption and operating time of the GHPS, inlet and outlet water temperature of the condenser, temperatures of each zone of the greenhouse, and ambient temperature were measured. Results: When operating only one heat pump unit, heat generated in the condenser decreased as the experiment progressed and power consumption increased correspondingly. However, the heating coefficient of performance decreased from 3.3 to 2.0 rapidly. Also, when operating two heat pump units, heat generated in the condenser decreased and power consumption increased. Heating coefficient of performance decreased from 4.5 to 3.7 rapidly. When the set temperature of the greenhouse was $13.7{\sim}20.1^{\circ}C$ and minimum ambient temperature was $-20.8{\sim}4.8^{\circ}C$, the annually accumulated heat and power consumption were 520,623 kW, 142,304 kW, respectively. Conclusion: When the set temperature of the greenhouse was $13.7{\sim}20.1^{\circ}C$ and the minimum ambient temperature was $20.8{\sim}4.8^{\circ}C$, the annually accumulated heat and power consumption were 520,623 kW, 142,304 kW, respectively. When operating only one heat pump unit, the heating COP was 2.0~3.3, and when operating 2 heat pump units, it was 3.7~4.5. If several heat pumps are installed in one GHPS, it is suggested that all heat pumps be operated except in special cases. Because the scale of the water pumps are set to the scale of when all heat pump units are operating, if even one unit is not operating, the power consumption will increase. That becomes the cause of COP decrease.