Analysis on Heating Effects of the Vertical Type Geothermal Heat Pump System

  • Kang, Youn Ku (Dept. of Agricultural Engineering, National Academy of Agriultural science, RDA) ;
  • Ryou, Young Sun (Dept. of Agricultural Engineering, National Academy of Agriultural science, RDA) ;
  • Jang, Jae Kyung (Dept. of Agricultural Engineering, National Academy of Agriultural science, RDA) ;
  • Kim, Young Hwa (Dept. of Agricultural Engineering, National Academy of Agriultural science, RDA)
  • Received : 2013.11.19
  • Accepted : 2014.05.28
  • Published : 2014.06.01

Abstract

Purpose: This paper is aimed at analyzing the heating performance of the vertical closed loop type Geothermal Heat Pump System (GHPS) distributing the farm site and providing basic data of the GHPS. Method: Seedling greenhouse heating was made from October 2012 to May 2013. The seedling greenhouse was divided into 4 sectors (A, B, C and D zone, total $3,300m^2$) with different temperatures. It was heated from 5PM to 8AM, and during the night the greenhouse was covered by non-woven fabric thermal curtains along the upper 2m of the greenhouse for temperature maintenance. In order to analyze the heating performance of the GHPS, power consumption and operating time of the GHPS, inlet and outlet water temperature of the condenser, temperatures of each zone of the greenhouse, and ambient temperature were measured. Results: When operating only one heat pump unit, heat generated in the condenser decreased as the experiment progressed and power consumption increased correspondingly. However, the heating coefficient of performance decreased from 3.3 to 2.0 rapidly. Also, when operating two heat pump units, heat generated in the condenser decreased and power consumption increased. Heating coefficient of performance decreased from 4.5 to 3.7 rapidly. When the set temperature of the greenhouse was $13.7{\sim}20.1^{\circ}C$ and minimum ambient temperature was $-20.8{\sim}4.8^{\circ}C$, the annually accumulated heat and power consumption were 520,623 kW, 142,304 kW, respectively. Conclusion: When the set temperature of the greenhouse was $13.7{\sim}20.1^{\circ}C$ and the minimum ambient temperature was $20.8{\sim}4.8^{\circ}C$, the annually accumulated heat and power consumption were 520,623 kW, 142,304 kW, respectively. When operating only one heat pump unit, the heating COP was 2.0~3.3, and when operating 2 heat pump units, it was 3.7~4.5. If several heat pumps are installed in one GHPS, it is suggested that all heat pumps be operated except in special cases. Because the scale of the water pumps are set to the scale of when all heat pump units are operating, if even one unit is not operating, the power consumption will increase. That becomes the cause of COP decrease.

Keywords

References

  1. Ball, D. A., Fisher, R. D and D. L. Hodgett. 1983. Design methods for ground-source heat pump. ASHRAE Trans. 89(2B):416-440.
  2. Bose, J. E. 1988. Closed-loop ground-coupled heat pump design manual. Stillwater, OK : Oklahoma state university, Engineering Technology Extension.
  3. Cane, D., Morrison, A and K. Christopher, 1998. Operating experiences with commercial ground-source heat pump systems. ASHRAE.
  4. Doherty, P. S., Al-Huthaili, S., Riffat, S. B and N. Abodahab. 2004. Ground source heat pump-description and preliminary results of the Eco House system. Applied thermal engineering 24:2627-2641. https://doi.org/10.1016/j.applthermaleng.2004.04.007
  5. Esen, H and M. Inalli. 2006. Technoecomic appraisal of a ground source heat pump system for a heating season in eastern Turkey. Energy Conversion and Management 47:1281-1297. https://doi.org/10.1016/j.enconman.2005.06.024
  6. Hepbasli, A and O. Akdemir. 2003. Energy and exergy analysis of a ground source (geothermal) heat pump system. Energy conversion and management 45:737-753.
  7. Inalli, M and H. Esen. 2004. Experimental thermal performance evaluation of a horizontal ground-source heat pump system. Applied thermal Engineering 24:2219-2232. https://doi.org/10.1016/j.applthermaleng.2004.01.005
  8. Kavanaugh, S. P. 1998. Development of design tools for ground-source heat pump piping. ASHRAE Trans. 104(1):932-937.
  9. Kavanaugh, S. P and K. Rafferty. 1997. Ground-source heat pumps: Design of geothermal systems for commercial and institutional buildings. ASHRAE.
  10. Lund, J. W and D. H. Freeston. 2001. World-wide direct use of geothermal energy 2000. Geothermics 30:29-68. https://doi.org/10.1016/S0375-6505(00)00044-4
  11. Lund, J. W. 2003. Direct-use of geothermal energy in the USA. Applied Energy 74:33-42. https://doi.org/10.1016/S0306-2619(02)00129-0
  12. Lund, J. W., Freeston, D. H and T. L. Boyd. 2005. Direct application of geothermal energy:2005 Worldwide review. Geothermics 34:691-727. https://doi.org/10.1016/j.geothermics.2005.09.003
  13. Mei, V. C and V. D. Baxter. 1990. Experimental study of direct-expansion ground coil heat exchanger. ASHRAE Trans. 96(1):450-459.
  14. Ministry for Food, Agriculture, Forestry and Fisheries. 2012. Vegetable production performance and flower cultivation status. 11-1541000-000017-10. Gwacheon. Gyounggi.: Ministry for Food, Agriculture, Forestry and Fisheries.