• 제목/요약/키워드: Generator-Stator Core

검색결과 32건 처리시간 0.025초

EL-CID를 이용한 발전기 고정자 철심의 건전성 평가 (Healthy Assessment of Generator Stator Cores using EL-CID (ELectromagnetic Core Imperfection Detector))

  • 김병래;김희동
    • 전기학회논문지
    • /
    • 제58권2호
    • /
    • pp.356-362
    • /
    • 2009
  • The ELectromagnetic Core Imperfection Detector (EL-CID) test was performed on a small generator in the laboratory and a gas turbine generator in the field to assess the fault condition of generator stator core. Artificial defects with six different sizes were introduced in the small generator. The scan results on six defects show a very large increase in the magnitude of fault current compared to that obtained with a healthy core. After the stator core heats up, a thermal imaging camera was used to detect hot spot on the inner surface of the core for comparison. Several faults were found during inspection of the gas turbine generator with the EL-CID. It has been shown that the existence of a fault can be determined by monitoring the magnitude of fault current.

전자기력에 의한 발전기 고정자 코어의 진동 해석 (Vibration Analysis of a Generator-Stator Core Under Electromagnetic Excitation)

  • 김철홍;주영호;박종포
    • 소음진동
    • /
    • 제9권4호
    • /
    • pp.747-753
    • /
    • 1999
  • This paper presents results of vibration analysis of a generator-stator core for 500 MW fossil power plant. A finite element analysis using a commercial S/W is performed to estimate alternating electromagnetic forces, mainly of 120 Hz in 60 Hz machines, acting on the core, and then to calculate forced response of the core. Results are compared with design requirements.

  • PDF

The Influence of Stator Pole Shape and Its Arrangements on Cogging Torque for Double-sided AFPM Generator

  • Kim, Chang-Eob;Jang, Joong-Keun;Joo, Sung-Jun
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • 제3권4호
    • /
    • pp.379-382
    • /
    • 2014
  • In this paper, the cogging torques were calculated for 1kw double-sided axial flux permanent magnet (AFPM) generator with different stator core pole arrangements. The generator is composed of 18 stator pole and 24 rotating field magnets on each side. The cogging torques of the generator with three types of arrangements of stator poles were calculated using 3D finite element method and the optimum core shape was determined to minimize the cogging torque.

전동/발전기 코어에 의한 초전도 플라이휠 에너지 저장장치의 회전손실 특성 평가 (Rotational loss assessment of flywheel energy storage system by Motor/Generator core)

  • 이정필;한영희;정세용;한상철;정년호;성태현
    • 전기학회논문지
    • /
    • 제56권10호
    • /
    • pp.1775-1781
    • /
    • 2007
  • In this paper, the rotational loss of the superconductor flywheel energy storage system (SFES) by motor/generator stator core was assessed. To do this, the vertical axial type SFES with journal type superconductor bearing was manufactured. To quantitatively assess the rotational loss by the stator core, the rotational losses by superconductor bearing and the degree of a vacuum were measured. In case of variation of the inner radius and outer radius of the stator core, the rotational losses were measured. From the experimental results, It is confirmed that the rotational loss can be reduced by means of the optimal stator core design.

Electromagnetic Structural Design Analysis and Performance Improvement of AFPM Generator for Small Wind Turbine

  • Jung, Tae-Uk;Cho, Jun-Seok
    • Journal of Magnetics
    • /
    • 제16권4호
    • /
    • pp.374-378
    • /
    • 2011
  • Axial Field Permanent Magnet (AFPM) generators are widely applied for the small wind turbine because of the higher power density per unit weight than that of the conventional radial field generator. It is caused by the disc shaped rotor and the stator structures. The generally used AFPM generator, AFER-NS generator, is composed of the two side's external rotors and non-slotted stator without stator core. However, the output voltage and the output power are limited by the large reluctance by the long air-gap flux paths. In this paper, the design study of AFIR-S generator having double side's slotted stator core is accomplished to improve the output generation characteristics. The electromagnetic design analysis and the design improvement of the suggested AFIR-S generator are studied. Firstly, the electromagnetic design analysis was done to increase the power density. Secondly, the design optimizations of the rotor pole-arc ratio of permanent magnet are accomplished to increase the output power and to reduce the cogging torque. Finally, the output performances of AFER-NS and AFIR-S generator are compared with each other. For this study, 3D FEA is applied for the design analysis because of three dimensional electromagnetic structures.

소형 풍력용 슬롯리스 영구자석형 발전기에 관한 연구 (A Study of Slotless Permanent Magnet Generator for Small Wind Turbine)

  • 김형길;공정식;오진훈
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.981-982
    • /
    • 2011
  • This paper discusses design aspects of slotless permanent magnet generator for high performance and low speed applications. The airgap flux density in was obtained from finite element analysis and the design of a PM generator. The relatively large diameter stator laminations of such machines tend, therefore, to have a very thin back of core and narrow teeth, which make them expensive and difficult to manufacture. this thesis proposes an alternative PM generator topology featuring a slotless stator whose laminations are manufactured from a split core. The test results with a resistive load confirm the satisfactory operation of generator.

  • PDF

Research about the Evaporative Cooling Sleeve of 3.6 MW Wind Generator Stator

  • Yu, Shunzhou;Yang, Jie;Yuan, Jiayi;Tian, Xindong
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • 제3권1호
    • /
    • pp.61-66
    • /
    • 2014
  • The evaporative cooling technology used in Wind generator stator has unique advantages. Combined with the structure of motor stator and operating conditions, this report based on the research project for the evaporative cooling sleeve of the 3.6MW wind generator, introduces the material requirements and structural characteristics of the sleeve, simulates on the stress, displacement and stability by finite analysis method, and tests the products experimentally. The research results show that the epoxy resin-glass materials have a higher strength and better insulation properties, but the evaporative cooling of the wind generator stator sleeve, because of its thin-walled, and the external pressure, so it's the less rigid. Should make full use of the motor stator core structure, increase its stiffness and improve the stability of the epoxy resin-glass sleeve, which for thin-walled the epoxy resinglass sleeve on the successful application of wind turbines has played an important role.

수력발전기 고정자권선의 절연열화 분석 (A study on the Analysis of Insulation Aging for Generator stator windings)

  • 변두균;오봉근;강동식;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2072-2074
    • /
    • 2005
  • This test was performed to assess the insulation condition of the stator winding of 3.45kV hydro generator in insulation deterioration condition which was due to long service period(30years) since installed We extracted 12 stator wingdings from the hydro generator core, cut the stator windings into three parts(Middle winding part, slot winding part, end wingding part), and evaluated the insulation condition to know the deterioration condition of each parts. This insulation diagnostic tests include AC current, dissipation factor, and partial discharg test.

  • PDF

이중 고정자 구조의 소형풍력터빈용 AFPM 발전기의 코깅토크 저감에 관한 연구 (Study on Cogging Torque Reduction for Small Wind Turbine AFPM Generator of Double Stator Structure)

  • 정태욱;배병덕
    • 조명전기설비학회논문지
    • /
    • 제26권2호
    • /
    • pp.71-77
    • /
    • 2012
  • The cogging torque is important to the cut-in wind speed. And, it causes the acoustic noise and the vibration on the machine. This paper presents a 3D FEA(Finite Element Analysis) to evaluate the effect of magnet skew and stator displacement on cogging torque reduction, for double core AFPM(Axial Flux Permanent Magnet) generator. As a result, the magnet skew and the stator side displacement are proved excellent techniques to reduce the cogging torque.

발전기 고정자 이완에 의한 소음발생 고찰 (The Case Study of The Generator Noise generated by Stator Looseness)

  • 유무상;한승우;노철우;류길수;오승태
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2014년도 추계학술대회 논문집
    • /
    • pp.527-532
    • /
    • 2014
  • Generator is the main equipment of a power plant that generates electric power. The line frequency is 60Hz, since that is operated at 3600rpm in fossil power plant. Therefore, the specific frequency 120Hz by the electromagnetic excitation force is generated inherently. If the looseness of stator at generator happens, abnormal sound that has 120Hz and the harmonic frequency is emitted from generator frame. In that case, binding of end-winding or re-wedging is needed for the reduction of sound level. In case of severe level of sound, belly band can be additionally installed at core. In this paper, the characteristics of generator sound is described and modal data is analyzed after installation of belly band.

  • PDF