• Title/Summary/Keyword: Generator Faults

Search Result 120, Processing Time 0.026 seconds

A Study on Implementation of Multi-Function Prototype IED H/W for Generator Protection (발전기 보호용 다기능 IED 시제품 H/W 구현에 관한 연구)

  • Kim, Yoon-Sang;An, Tae-Pung;Park, Chul-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.12
    • /
    • pp.74-80
    • /
    • 2013
  • Generator faults does not happen more often than the transmission and substation facility faults. However, impacts on the power system by generator faults are very large. In order to minimize the impact of generator faults, generator protection and control system with high reliability is required. Most of the generator relay in generator protection and control system of large power plant of Korea is operated by imports from abroad. Accordingly, in order to accumulate source technology and increase the import substitution effect, localization of multi-function generator protection IED is being developed. This paper deals with the implementation of a multi-function prototype IED H/W, which can be command and data exchange through communication for measuring, monitoring, protection and control. And the IED specification, various relay elements, measurement elements, communication functions, module function, and test system for the prototype IED H/W are described.

Fault Simulation and Analysis of Generator (발전기의 사고 시뮬레이션과 분석)

  • Park, Chul-Won;Oh, Yong-Taek
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.3
    • /
    • pp.151-158
    • /
    • 2013
  • Large generator of power plant is very important. In order to protect large generator from faults, digital protective relay or IED is required. However, all protective relays for generators of the domestic power plant are operated by foreign products. And now, for technological independence from foreign and improvement of import substitution effect, IEDs using domestic technology are being developed. To evaluate performance of developing next-generation power devices, the study of the dynamic characteristics of the power plant, generator system modeling, fault simulation and analysis, should be considered. Specially, To obtain IEEE Standards COMTRADE format for relay operation test, generator system modeling and fault simulation using PSCAD/EMTDC tools must be preceded. Until now, a complete modeling of generator internal windings and fault simulation techniques dose not exist. In this paper, for evaluation performance of relay elements of developing IED, the generator system modeling and various faults simulation using PSCAD/EMTDC tools were performed. And then, the various transient phenomena through obtained relaying signal of developed modeling were analyzed.

A Fast Automatic Test Pattern Generator Using Massive Parallelism (대량의 병렬성을 이용한 고속 자동 테스트 패턴 생성기)

  • 김영오;임인칠
    • Journal of the Korean Institute of Telematics and Electronics B
    • /
    • v.32B no.5
    • /
    • pp.661-670
    • /
    • 1995
  • This paper presents a fast massively parallel automatic test pattern generator for digital combinational logic circuits using neural networks. Automatic test pattern generation neural network(ATPGNN) evolves its state to a stable local minima by exchanging messages among neural network modules. In preprocessing phase, we calculate the essential assignments for the stuck-at faults in fault list by adopting dominator concept. It makes more neurons be fixed and the system speed up. Consequently. fast test pattern generation is achieved. Test patterns for stuck-open faults are generated through getting initialization patterns for the obtained stuck-at faults in the corresponding ATPGNN.

  • PDF

Digital Negative Sequence Relay Algorithm for Detection of Unbalanced State in a Generator (발전기의 불평형 검출을 위한 디지털 역상 계전 알고리즘)

  • Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.4
    • /
    • pp.198-203
    • /
    • 2013
  • There are conditions that can be unbalanced three phase currents in a large generator by untransposed lines, unbalanced loads, unsymmetrical faults, and open phases. The unbalanced conditions can producing negative sequence components of current that induce two times frequence current in the surface of the rotor, the retaining rings, the slot wedges in the field windings. These rotor currents make the rotor rapidly overheat, so the rotor can cause substantial damage in a very short time. This paper presents the digital negative sequence relay algorithm for unbalanced protection in a generator. The proposed algorithm was tested by using collected current signals on PSCAD/EMTDC considering a hydro turbine based generator control system. It can be seen that the proposed relaying by negative sequence current is useful for detection of unbalanced state of large generator.

Process and instrument faults detection based on steam generator model (증기발생기 모델을 이용한 계통 및 계측기 고장검출에 관한 연구)

  • Kim, Jung-Soo;Lyou, Joon;Na, Nan-Ju;Kwon, Kee-Choon
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1993.10a
    • /
    • pp.250-255
    • /
    • 1993
  • In this paper, for detection and isolation of instrument and process faults related with steam generator(S/G) in nuclear power plant, two types of observers are designed based on the linearized dynamic model of S/G : a bank of Dedicated Observers (DOS) for instrument faults detection and a bank of Unknown Input Observers(UIO) for process faults detection. And then, they are combined to decide which one between the above two faults occurs. In principle, the failure in ith instrument(process) can be isolated by monitoring the error between the ith output and its estimation obtained from the ith DOS(UIO). It is shown via computer simulations that the present scheme is feasible in finding out the source of a fault.

  • PDF

A Protection Algorithm Discriminating Between Internal and External Faults for Wind Farms (풍력발전단지 보호를 위한 내외부 고장 판별 알고리즘)

  • Kwon, Young-Jin;Kang, Sang-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.5
    • /
    • pp.854-859
    • /
    • 2007
  • A wind farm consists of many wind generator(WG)s therefore, it is generally a complex power system. A wind farm as a distributed generation(DG) affects utility power system. If a conventional protection schemes are applied, it is difficult to detect faults correctly and the schemes can't provide proper coordination in some cases. This paper presents a protection algorithm for a wind farm which consists of a looped collection circuit. Because the proposed algorithm can distinguish between an internal fault and an external fault in a wind farm, The proposed algorithm can disconnect the faulted section in a wind farm. This algorithm is based on an overcurrent protection technique with the change of the ratio of the output current of a generator to the current of the looped line connected to each generator to collect the each generator's power. In addition, operating time of the algorithm is shortened by using the voltage drop at a generator collection point. The performance of the proposed algorithm was verified under various fault conditions using PSCAD/EMTDC simulations.

Generator Protection Relaying System in Power Plant (발전소의 발전기 보호계전시스템)

  • Kwan, Sung-Kyun;Park, Chul-Won;Lee, Jong-Soo;Lee, Sang-Seung;Shin, Myong-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.151-152
    • /
    • 2006
  • Because power plant faults have severe effects on the power system and on mechanical maintenance of the generator, reliable protection systems are needed. In this paper, we compared and analyzed methods of the generator protection relaying system, which can defect internal faults of the generator, and surveyed the trends in generator protection using digital computing.

  • PDF

Fault Detection and lsolation System for centrifugal-Pump Systems: Parity Relation Approach (원심펌프 계통의 고장검출진단시스템 : 등가관계 접근법)

  • Park, Tae-Geon;Lee, Kee-Sang
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.1
    • /
    • pp.52-60
    • /
    • 1999
  • This paper deals with a fault detection and isolation scheme for a DC motor driven centrifugal pump system. The emphasis is placed on the design and implementation of the residual generatorm, based on parity relation, that provides decision logic unit with residuals that will be further processed to detect and isolate three important faults in the system;brush fault, impeller fault, and the speed sensor fault. Two process faults are modelled as multiplicative type faults, while the sensor fault as an additive one. With multiplicative fault, the implementation of the residual generator needs the time varying transformation matrix that must be computed on-line. Typical implementation methods lack in generality because only a numerical approximation around the assumed fault levels is employed. In this paper, a new implementation method using well tranined neural network is proposed to improve the generality of the residual generator. Application results show that the fault detection and isolation scheme with the proposed residual generator effectively isolates three major faults in the centrifugal pump system even with a wide range of fault magnitude.

  • PDF

Analysis on Air-Gap Magnetic Flux of Synchronous Generator According to Short-Circuit Types in Winding (권선단락 유형별 동기발전기의 공극자속 파형 분석)

  • Bae, Duck-Kweon;Kim, Dong-Hun;Park, Jung-Shin;Lee, Dong-Young;Lee, Sung-Ill
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.5
    • /
    • pp.929-935
    • /
    • 2009
  • As modem industrialized society progresses, the demand for electric power is increasing rapidly. The electric power system is getting amazingly bigger and complicated, which can easily induce serious troubles from the potential of large fault problems and/or system failure. The monitoring and diagnosis of the electric machine for the fault detection and protection has been important part in the electric power system. Most faults in the generator appear in the winding. This paper presents the air-gap magnetic flux characteristic of a small-scale 2-pole synchronous generator according to the faults in the field winding to protect the generator from the fault. The magnetic flux patterns in air-gap of a generator under various fault conditions as well as a normal state are simulated by using finite element method. These results are successfully applied to the detection and diagnosis of the short-circuit condition in rotor windings of a high capacitor generator.

Methodology for Determining of Generator Operation Point for Ensuring Voltage Stability Against Generator Faults in Jeju-Haenam HVDC System

  • Kang, Sang-Gyun;Seo, Sang-Soo;Lee, Byong-Jun;Joo, Joon-Young
    • Journal of Electrical Engineering and Technology
    • /
    • v.5 no.1
    • /
    • pp.54-60
    • /
    • 2010
  • This paper presents a new algorithm for determining generator operation point for maintaining stability considering generator faults in Jeju-Haenam HVDC system. As the HVDC system consumes reactive power for the transmission of active power substantially, compensation of reactive power is essential. And the HVDC system is operated on frequency control mode. That is to say, the HVDC system almost manages system frequency. Therefore, we recognized that the Jeju system could be unstable if the reactive power consumed by the HVDC is insufficient when out-of-step occurs with large generators. When the solution of power flow analysis does not converge due to the unstable system phenomenon, we have difficulty in establishing countermeasures as the post-fault information is not available. In this paper, for the purpose of overcoming this difficulty in establishing countermeasures, we introduce the CPF(Continuation Power Flow) algorithm. This paper suggests an algorithm for calculating the output limitation of the generator to maintain the stability in case of generator fault in the Jeju system.