• 제목/요약/키워드: GIS(Gas Insulated Substation)

검색결과 49건 처리시간 0.026초

EMTP/RV를 이용한 22.9kV GIS 모델링과 과도회복전압 해석 (22.9kV GIS Modeling and Transient Recovery Voltage Analysis Using EMTP/RV)

  • 정태영;백영식;정기석;박지호;서규석
    • 전기학회논문지
    • /
    • 제59권7호
    • /
    • pp.1199-1205
    • /
    • 2010
  • The recent power system is required to a large size of facilities and high power technology according to increasing power demand. However, it could lead to spoiling the beauty of city and environment problem. The miniaturized facilities with large capacity such as GIS have been required in recent power system. The GIS(Gas Insulated Substation) using the SF6 insulation gas enables to miniaturize facilities with large capacity with high insulation performance. However, the substation installed GIS has required to new design model which is different from the conventional substation. The TRV(Transient Recovery Voltage) analysis on simple circuit may applied by differential equation. However, in case of relatively complicated system, EMTP(Electro Magnetic Transients Program) mainly has been used to design and simulate for transient analysis. This paper mainly design the 22.9 kV GIS system and analyze the transient recovery voltage of main circuit breaker using EMTP/RV. It also enables to easily design the other substation installed GIS with same maker and voltage level because the proposed GIS model consists of separated modules such as busbar, circuit breaker, bushing, CT, PT etc. Eventually, it contributes to comfortably compare the interrupting performance of circuit breaker and system TRV corresponding to the substation system configuration.

Measurement of Transient Electric Field Emission from a 245 kV Gas Insulated Substation Model during Switching

  • Rao, M. Mohana;Thomas, M. Joy;Singh, B.P.
    • Journal of Electrical Engineering and Technology
    • /
    • 제2권3호
    • /
    • pp.306-311
    • /
    • 2007
  • The transient fields generated during switching operations in a Gas Insulated Substation (GIS) are associated with high frequency components in the order of few tens of MHz. These transient fields leak into the external environment of the gas-insulated equipment and can interfere with the nearby electronics. Measurements of the transient fields are thus required to characterise the interference caused by switching phenomena in such substations. In view of the above, E-field emission measurement during a switching operation has been carried out for a 245 kV GIS model, using a resonant dipole antenna and D-dot sensor. The characteristics of the E-fields i.e., frequency spectra and their levels have been analysed and are reported in the paper. Suitability of the measurements has been confirmed by comparing frequency spectra of the measured and computed transient fields.

345kV GIS 변전소 뇌써지 해석 (Analysis of lightning surge on the 345kV Gas Insulated Substation)

  • 김재관;이종범;조한구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.561-563
    • /
    • 2003
  • This paper deals with simulation of lightning overvoltage generated by back flashover entering 345[kV] Gas Insulated Substation. In order to protect the substation equipment against lightning surge, insulation coordination is performed with the lightning arrester. This paper suggests optimal location of lightning arrester using the EMTP/ATPDraw to mere economically and effectively reduce the lightning surge incoming overhead lines.

  • PDF

RF front-end Module for On-Line UHF Partial-discharge Monitoring System

  • Lee June Young;Kim Bok Ki
    • 대한전자공학회:학술대회논문집
    • /
    • 대한전자공학회 2004년도 학술대회지
    • /
    • pp.776-779
    • /
    • 2004
  • A RF front-end module is designed for GIS(Gas Insulated Substation) which is employed for effective and efficient very high voltage transmission. Major advantage of the unit is improved PO detection sensitivity through minimizing the effect of surrounding interference signals, which is achieved by controlling the gain and the selection of the frequency band, for the precise detection of any UHF PO (Partial Discharge) disturbance occurred in the GIS due to some unwanted problems. For the development of the module, various switches for providing selected signal paths, wideband LNA, 3 BPF for selecting detection frequency band, and video detector are designed, fabricated and measured on 1 mm FR4 substrate with various RF components. The detection sensitivity of the unit was <-60 dBm that is sufficient to detect UHF PO signals as low as 1 pC. It is believed that the value is enough to detect the signal occurred in GIS.

  • PDF

The Lightning Current Parameters that Impact on the Surge Analysis of the EHV Gas Insulated Substation by EMTP

  • Shim Eung-Bo;Han Sang-Ok
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제5C권1호
    • /
    • pp.1-7
    • /
    • 2005
  • This paper describes the lightning surge analysis model of extra high voltage GIS using EMTP. Various lightning current parameters were investigated in order to confirm the impact on the lightning surge analysis such as lightning current amplitude, waveform, size of GIS, tower footing resistance and surge arresters. The multi-story tower model and EMTP/TACS model were introduced for the simulation of dynamic arc characteristics. The margin between the maximum overvoltage and BIL of the GIS was about 10 percent and the margin between the maximum overvoltage and BIL of the transformer was 21 percent.

154KV 가스중 종단접속의 사고유형과 방지대책 (FAILURE ANALYSIS OF 154KV TERMINATION IN GAS INSULATED SWITCHGEAR)

  • 이천구;이민규;김병수;허근도
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1993년도 하계학술대회 논문집 B
    • /
    • pp.594-597
    • /
    • 1993
  • With the increase of electric power demand in the downtown area. many problems, such as the difficulty in security of substation site and interference of the electromagnetic wave or damage to person due to outdoor type substation facilities has been occured. Therefore, the compaction of substation facilities is required and the gas insulated switchgear(GIS) has been adopted accordingly. However, much care should be taken of the interface problem between cable and GIS. This paper describes the failure analysis and a countmeasure for prevent ion from failure in the interface.

  • PDF

변전소 형태 및 설비규모의 결정 (Application Standards for Substation Types and Facility Scales)

  • 민병욱;신명식;방선웅;김영달
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.438-439
    • /
    • 2011
  • Substations in Korea are classified into an outdoor steel structure type, an outdoor GIS(Gas Insulated Switchgear) type, an indoor GIS type, an underground GIS type, and a complex GIS type. Before 1970, substations were built in outdoor steel structure types only. In 1980, an 154kV indoor GIS type substation was built for the first time in Pusan. And the first 345kV indoor GIS type substation, the first 765kV full GIS substation were built in 1984 and in 2002 each. In 1998, 154kV indoor type substations were standardized into regular type and urban type which applied steel frames to structures. In 2002, this was re-standardized into five different types in detail. In 2007, hub substations which had high capacity were built in the region of industrial zone and heavy load areas. And 154kV compact substation was developed and standardized by compacting an indoor GIS type substation in 2009. This paper would present a series of substation type transition and application standards for substation types and facility scales.

  • PDF

UHF법 부분방전 진단기법에 의한 가스절연 개폐장치의 성능검증 (Performance Verification of Gas Insulated Switchgear using UHF Partial Discharge Diagnosis Method)

  • 김정배;박경수;송원표;김덕수;김종화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.37-39
    • /
    • 2002
  • UHF method is very effective to diagnosis for partial discharge of GIS. In generally, inner UHF sensor can be attached on sheath cover of GIS under construction for periodic inspection. However, there is no inner UHF sensor for GIS of the domestic substation. We used the outer UHF sensor attached on spacer for GIS of existing substation. In this paper, we report the diagnosis result of partial discharge on 800kV GIS in domestic substation. From these results, we can find the quantity, reason and location of PD and certificate the performance of UHF method for partial discharge diagnosis of GIS.

  • PDF

P.C.에 의한 GIS형 AC Substation의 접지계 설계 (Grounding System Design of GIS type AC Substation using Personal Computer)

  • 임한석;김왕
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제4권1호
    • /
    • pp.46-53
    • /
    • 1990
  • GIS(Gas-Insulated Switchgear)형 옥내변전소에 있어서 접지계의 구성은 접지도체를 포설할 수 있는 면적이 협소하기 때문에 특별한 설계방법이 요구된다. 본 논문에서는 접지망의 전위해석과 축소형 변전소의 접지계 설계기법을 제시하였고, 아울러 컴퓨터 시뮬레이션을 위한 프로그램을 작성하고 그 시뮬레이션 결과를 측정치와 비교하여 프로그램의 타당성을 입증하였다.

  • PDF

Detection Characteristics of a Novel Coupler for GIS PD Detection

  • Park, Jae-Gu;Yi, Sang-Hwa;Kim, Kwang-Hwa;Kim, Ik-Soo;Kim, Jae-Chul
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제3C권6호
    • /
    • pp.224-229
    • /
    • 2003
  • An ultra high frequency (UHF) coupler possessing ultra wide band (UWB) characteristics ranging from hundreds of MHz to several GHz is desirable for the detection of the partial discharge (PD) pulses because the pulses propagate with rise time shorter than one nanosecond in a gas-insulated substation (GIS). Thus, the authors have proposed a log-periodic antenna for GIS PD detection. Various parameters of the coupler such as frequency bandwidth, coupler gain, radiation pattern, and coupler geometry were considered throughout the simulations. The experiments for the detection characteristics of the coupler were carried out in the mock-up GIS chamber. The results indicated that the detection characteristics of the coupler are dependent on the installation angle of the coupler, the position of the coupler in the hand hole and the existence of the spacer.