• Title/Summary/Keyword: Fire smoke movement

검색결과 120건 처리시간 0.021초

화재 시 연기거동 관련 연구 동향에 관한 조사 (A Study on the Research Trends of Smoke Movement in Fire)

  • 김형진;신이철;황은경;황금숙;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 춘계학술논문발표회 논문집
    • /
    • pp.317-320
    • /
    • 2008
  • Smoke is recognized as the major killer in fire situation. smoke often migrate to building locations remote the fire space, threatening life and elevator shafts frequently become smoke-logged, there by blocking evacuation and inhibiting rescue and fire fighting. It is the aim of this study to investigate and analyze the research trends of smoke movement in Fire.

  • PDF

화재시 연기거동에 관한 실험 및 해석적 연구 (An Experimental and Analytical Studies on the Smoke Movement by Fire)

  • 신이철;김수영;이주희;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 춘계학술논문발표회 논문집
    • /
    • pp.15-18
    • /
    • 2008
  • A study on the fire and smoke behavior on experiments and analysis through STAR-CD in using about behavior analysis of the smoke. Kerosene of 3L in using on the experimental garden of 30cm in diameter same applies to heat release rate(HRR), buoyant force by Plume can be calculated at a rate of 1m/s. The result of experiment in average of velocity were 0.29m/s, and interpreted result were 0.28m/s. Besides, it is proved by interpreted that behavior of smoke movement can be not observed in the experiment. After smoke is Plume increased, ceiling-jet in formation being descend in smoke layer will be more thick smoke layer, and then vertical wall is collapsed in formation of wall-jet being descend. It is defined that smoke layer is more thick through descending course in wall-jet and ceiling-jet.

  • PDF

실내화재에서 연기거동에 미치는 복사영향에 대한 수치해석적 연구 (A Numerical Study of Radiation Effect under Smoke Movement in Room Fire)

  • 정진용;유홍선;홍기배
    • 한국화재소방학회논문지
    • /
    • 제14권3호
    • /
    • pp.6-12
    • /
    • 2000
  • 본 연구는 두 가지 유형의 3차원 실내 공간 내에서 화재 발생시 연기거동에 미치는 복사영향을 알아보기 위해 자체개발한 SMEP(Smoke Movement Estimating Program) Seld 모델을 사용하여 수치해석하였다. PISO 알고리즘과 부력항을 포함한 수정 k - e 난류모델을 사용한 SMEP은 연속, 운동, 에너지, 농도 그리고 복사 열 전달 방정식을 풀었으며, 복사 열 전달 방정식의 해석을 위하여 S-N 구분종좌표법을 채택하여 사용하였다. 수치해석 결과 연기의 온도분포는 복사를 고려하지 않고 대류만을 고려했을 경우 실험치와 많은 오차를 보였으나 복사를 함께 고려했을 경우는 실험치와 작은 오차범위로 비슷한 경향을 나타내었다. 이것은 연기속에 포함되어 있는 연소생성물 중 H2O와 CO2 가스의 복사 영향 때문이며, 따라서 좀더 실제적인 화재해석에 있어서 복사는 반드시 고려되어야만 한다.

  • PDF

FDS를 이용한 실규모 공연장 무대 내 화재 시 연기 거동 분석: 방화막 및 자연배출구 면적의 영향 (Analysis of Smoke Behavior in Fire within Real-scale Theater Using FDS: Influences of Fire Curtain and Natural Smoke Vent Area)

  • 김재한;이치영;정이규;김동균
    • 한국화재소방학회논문지
    • /
    • 제32권6호
    • /
    • pp.7-14
    • /
    • 2018
  • 본 연구에서는 방화막 및 자연배출구 면적이 공연장 무대 화재 시 연기 거동에 미치는 영향에 대해 Fire Dynamics Simulator (FDS)를 이용하여 전산시뮬레이션(Numerical simulation)을 수행하였다. 공연장의 무대 크기는 폭 31 m, 깊이 34 m, 높이 32 m로 설정하였고, 자연배출구 면적은 무대 바닥면적의 약 10%, 약 8%, 약 5%, 약 1%로 하였다. 방화막은 프로시니엄(Proscenium) 벽과 0.5 m 이격하여 설정하였다. 방화막과 자연배출구 면적은 객석으로의 연기유출, 자연배출구 및 프로시니엄 개구부를 통한 유입 및 유출 질량 유량에 지대한 영향을 미치는 것으로 관찰되었고, 동일한 자연배출구 면적 조건에서 방화막이 설치된 경우가 미설치된 경우에 비해 무대 내 압력이 더 낮은 것으로 나타났다.

터널 화재시 터널 단면의 종횡비에 따른 연기 거동에 관한 (An Experimental Study of Smoke Movement in Tunnel Fires with Aspect Ratio of Tunnel Cross Section)

  • 이성룡;유홍선;김충익
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 추계학술대회
    • /
    • pp.115-120
    • /
    • 2003
  • In this study, smoke movement in tunnel fires was investigated with various aspect ratio(0.5, 0.667, 1.0, 1.5, 2.0) of tunnel cross section. Reduced-scale experiments were carried out under the Froude scaling using 8.27 kW ethanol pool fire. Temperatures were measured under the ceiling and vertical direction along the center of the tunnel. Smoke front velocity and temperature decrease rate were reduced as higher aspect ratio of the tunnel cross-section. Smoke movement was evaluated by analysis of vertical temperature distribution 3 m downstream from the fire source. Elevation of smoke interface according to N percent rule was under about 60% of tunnel height.

  • PDF

고층건물의 수직방향 연기거동에 미치는 발코니의 영향에 관한 실험적 연구 (An Experimental Study on the Effect of the Balcony on the Vertical Smoke Movement of the High Rise Building)

  • 양승신;김성찬;유홍선;심상훈
    • 한국안전학회지
    • /
    • 제20권1호
    • /
    • pp.42-48
    • /
    • 2005
  • The present study investigates the effect of balcony on external smoke movement of high rise building through the fire tests of the 1/10 reduced model scale using Froude scaling. A hexane pool fire is used to examine the smoke movement for various opening sizes of balcony and temperature distributions are measured by T-type thermocouples. Also, hydrogen bubble technique is applied to visualize the smoke movement near the balcony. Measured temperatures of the closed balcony is 2.5 times higher than those of the open balcony because the external smoke in case of the closed balcony rise along the vertical wall. The maximum vertical temperature of partially closed balcony is similar with fully closed balcony and mean temperature inside of balcony increases as opening size of balcony decreases. The experimental results show that the balcony space plays an important roles in preventing fire propagation and cooling of smoke layer. In order to ensure the fire safety in high rise building design, a series of systematic researches are required to examine the various type of balconies.

연기발생으로 인한 시야장애가 초고층 공동주택 거주자의 피난계단실 진입시간과 피난경로에 미치는 영향 (How Visual-Field Obstruction from Fire Smoke Influences a Resident's Necessary Time to Reach Fire Escape and Evacuation Route in a High-rise Apartment Housing)

  • 서상목;최준호;홍원화
    • 한국주거학회논문집
    • /
    • 제19권5호
    • /
    • pp.103-110
    • /
    • 2008
  • The purpose of this study is to know how visual-field obstruction from fire smoke influences a resident's necessary time to reach fire escape and evacuation movement in a high-rise apartment housing. Generally, fire smoke not only gives visual-field obstruction and breath troubles to residents but interrupts their evacuation behavior. If a fire smoke layer is formed in the core department when evacuee enters at the evacuation staircase until, residents will be made to undergo a range of vision obstacle. In order to set a situation like that, participants wore eye bandage which had been made especially before the experiment. Also as a comparative standard, through no.1442 Japanese construction ministry notices about the building evacuation safety verification method, this study calculated smoke layer's dissent time and evacuation time. Then to compare with the former, the participants without an eye bandage joined a experiment once again. This study has understood how fire smoke effects on one's evacuation delay by analyzing residents' evacuation time to reach the staircase and movement route, however, in this study a toxic gas is not considered because it might threaten participants not to breathe.

지하역사에서의 화재연기거동 실험 (Experiments of Smoke Behavior in an Underground Subway Station)

  • 김동현;장용준;박원희
    • 한국철도학회논문집
    • /
    • 제10권1호
    • /
    • pp.67-73
    • /
    • 2007
  • Experiments were carried out to investigate smoke movement in platform of a subway station which currently is in service in Pusan, the second largest city in Korea. The recently constructed underground station of the "bank type" (two platforms on both sides of track) which is the popular layout of platforms in Korea, is chosen in Pusan. The smoke generator and heater are used for simulating the smoke movement at the fire break in the platform located in the 2nd basement of the station. Video recordings were used to monitor smoke lowering. In this study, the movements of smoke in the underground station are investigated under various smoke-control operating modes. Three tests wire conducted according to its operating mode of the ventilation systems in the platform: no operation of any ventilation systems, smoke extraction mode in occurrence of fire (presently running mode) and full capacity of smoke extraction where all vents are activated in the platform. The results can be used for comparing with the numerical prediction results of fire subway stations.

어린이집 화재 시 연기 거동에 관한 실험적 연구 (An Experimental Study of Smoke Movement in a Kindergarten Fire)

  • 이성룡;한동훈
    • 한국화재소방학회논문지
    • /
    • 제27권2호
    • /
    • pp.62-69
    • /
    • 2013
  • 본 연구에서는 어린이집 화재 시 열 및 연기의 거동 특성을 파악하기 위하여 재개발 예정지의 어린이집에서 실험이 실시되었다. 실험대상 어린이집은 2층 구조로 되어있으며, 각 층의 연면적은 252 $m^2$이다. 가연물로는 헵탄 36리터를 사용하였다. 한 변의 길이가 0.8 m인 정사각형 화원을 사용하였으며, 정상상태에서 최대 열방출율은 약 1.7MW이다. 실험동안 연기의 이동 및 온도 변화를 측정하였다. 1층 복도에서, 화재 발생 1분 후 연기가 1.4 m 높이까지 하강하였으며, 화재 발생 약 4분 후 복도 전체가 연기로 가득 찼다. 2층 대부분의 영역에서 온도가 $70^{\circ}C$ 이하로 유지되었으나 실내가 연기로 가득 찼다.

급기가압 조건에서 복합 구획 공간 화재의 연기 거동에 대한 수치해석 연구 (Numerical Simulation on Smoke Movement in Multi-Compartment Enclosure Fires under Pressurized Air Supply Conditions)

  • 고권현
    • 한국화재소방학회논문지
    • /
    • 제32권6호
    • /
    • pp.15-21
    • /
    • 2018
  • 본 연구에서는 급기가압 조건에서 거실, 부속실 및 계단실로 구성된 복합 구획 공간에 대해 화재해석을 수행하고 가압 및 환기 조건에 따른 화재 연기의 유동 특성을 분석하였다. 화재 해석은 유효누설면적을 측정하기 위해 제작된 누기율 시험설비에 대하여 수행하였으며, 화재의 거시적 특성과 각 구획에 대한 유동 및 압력 특성의 분석을 통해 급기가압 조건에서의 화염 및 연기 거동에 대한 이해를 증진시키고자 하였다. 화재 해석 결과는 화재 발열량의 크기가 환기 시스템에 의해 공급되는 공기량에 의해서 민감하게 영향을 받게 됨을 보여주었다. 거실과 부속실에서의 속도분포 분석 결과를 통해 급기가압의 조건에서도 화재 연기가 문의 상층부를 통해 부속실로 유출될 수 있음을 확인하였다. 이를 통하여 급기가압 제연시스템의 설계와 적용에 있어서 화재 크기와 공간적 특성과 같은 요인을 고려하는 것이 매우 중요하다는 것을 확인할 수 있었다.