A study on the corrosion evaluation and lifetime prediction of fire extinguishing pipeline in residential buildings

  • Jeong, Jin-A;Jin, Chung-Kuk;Lee, Jin Uk
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.39 no.8
    • /
    • pp.828-832
    • /
    • 2015
  • This study is conducted for the evaluation of corrosion and lifetime prediction of fire extinguishing pipelines in residential buildings. The fire extinguishing pipeline is made of carbon steel. Twenty-four samples were selected among all the fire extinguishing pipelines in a building; the selection was based on specimenspositions, pipeline diameters, and pipeline thickness. Analysis was conducted by using the results of visual inspection, electrochemical potentiodynamic anodic polarization test, pitting depth measurements, and extreme value statistics with the Gumbel distribution. The maximum pitting depth and remaining life were statistically predicted using extreme value statistics. During visual inspection, pitting corrosion was observed in several samples. In addition, extreme value statistics demonstrated that there were several pipelines that were very sensitive to pitting corrosion. However, the pitting corrosion was not critical in all the pipelines; thus, it was necessary to change only those pipelines that were severely corroded.

A Study on Revise the Rule of Safety Controllers of Hazardous Substances (위험물 안전관리 제도의 개선에 관한 연구)

  • Park, Kyong-Jin;Shin, Soo-Kyung;Lee, Bong-Woo
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.23 no.3
    • /
    • pp.473-480
    • /
    • 2020
  • In this study, I analyzed problems of safety management system of hazardous substances and proposed improvement measures. By statistics of Korea National Fire Agency it shows that hazardous substances of not less than a designated quantity were 2,180 factorys, 24,732 handling places and 85,218 storing places in 2018. also It has been conformed that Fire accidents break out year after year in factory, etc. so In this study, I analyzed the safety controllers of hazardous substances of the present law and fire statistics. therefore I has been found out the problems that the first, safety controllers' status. the second, There is no laws related design, installation, installation supervision. the third, fire safety inspection. This study will be used a basic data for preventing of extensive hazazardous substances-related accident that is very difficult handling.

An Experimental Study on the Fire Risk of Electric Heaters According to Contact of Flammable Materials (가연물 접촉에 따른 전기히터의 화재위험성에 관한 실험적 연구)

  • Lee, Sung-Ryong
    • Fire Science and Engineering
    • /
    • v.25 no.3
    • /
    • pp.63-71
    • /
    • 2011
  • In this study, it was evaluated the fire risk of an electric heater as representative seasonal appliances. Two type of electric heaters were used in experiments. When electric heaters were operated, temperature variation was measured around the heater. Internal structure was understood by Nondestructive inspection. It was evaluated the tire risk of electric heaters, when flammable materials were positioned ear a heater. It was also estimated the probability of a tire in case of malfunction of a safety tip-over witch. When a heater was operated in a normal condition, temperature was maintained under $80^{\circ}C$ around the heater. The possibility of a fire is very high, when a heater is covered with flammable materials or malfunction of safety parts (safety tip-over switch, anti-overheating devices).

Evaluation of Material Properties of Fire-damaged Concrete Under Post-fire Curing Regimes Using Impact Resonance Vibration Method (충격 공진 기법을 이용한 화재 손상 콘크리트의 재양생 조건별 재료물성 평가)

  • Park, Sun-Jong;Yim, Hong Jae
    • Journal of the Korea institute for structural maintenance and inspection
    • /
    • v.21 no.5
    • /
    • pp.42-48
    • /
    • 2017
  • When concrete structures expose to fire, the structures were damaged accompanied with degradation of material properties of concrete. In order to determine the reuse of fire-damaged concrete structures, it is needed a careful determination considering conditions of fire damage, such as exposure temperature and exposure time, and also potential to restore fire damage. This study investigates on the evaluation of residual material properties of fire-damaged concrete under different post-fire curing regimes. An experimental study was performed on concrete samples to measure the dynamic elastic modulus by the impact resonance vibration method. Upon the experimental results, the evidence of restoration of material properties was confirmed on specific post-fire curing regimes, higher humidity conditions. Additionally, a correlation analysis was performed on the dynamic elastic modulus with the tensile strength for identifying the effects of post-fire curing regimes on both material properties of fire-damaged concrete.

A Checklist and Manual Developed to Review Fire Safety Facilities' Compliance with Fire Safety Requirements for Apartment Buildings (공동주택 소방시설 적법성 검토를 위한 화재안전규정 체크리스트 및 매뉴얼 개발)

  • Jeong, Soo-jin;Park, Yoo-na;Kim, Jae-jun
    • Korean Journal of Construction Engineering and Management
    • /
    • v.19 no.6
    • /
    • pp.94-102
    • /
    • 2018
  • Recently, there is a growing need to review compliance with legal requirements to ensure fire safety as the number of fires caused by noncompliant fire safety facilities in high-rise buildings has increased. While there are a large number of apartment buildings in Korea, there is a lack of review on fire safety facilities' compliance with fire safety requirements. The reason for this lack of review despite apartment buildings causing deaths due to their structural features in the event of a fire, lies in the misinterpretation of legal provisions as the Building Act and the Fire Services Act are mixed up; a final inspection when fire safety facilities are unnecessarily installed or missing could result in significant losses in terms of finances and time. Therefore, this study developed a checklist that makes it possible to review mixed-up legal requirements for fire safety facilities simultaneously, and examined the importance and current level of each item through IPA (Importance Performance Analysis). Based on these results, this study intends to develop a manual that considers its applicability to construction practices and contribute to reducing construction companies' fire safety inspection risks.

The Evaluation of Fire-Resistant Performance of the Non-bearing Steel Wall Using Fire Resistant Glass (내화유리를 적용한 강재 유리벽의 내화성능 평가)

  • Lee, Jae-Sung;Yim, Hyun-Chang;Yang, Seung-Cho
    • Journal of the Korea institute for structural maintenance and inspection
    • /
    • v.22 no.5
    • /
    • pp.72-81
    • /
    • 2018
  • Fireproof structures using concrete, built-up panels and dry walls are usually used in walls inside fire compartments. However, demand for glass walls is emerging due to increase in interest in visibility and external appearance. In this study on steel fire resistance walls using insulation glass, fire resistance tests and performance evaluations were conducted on 60 minute fire resistance walls and exterior walls which could be applied to interior fire compartments and 90 minute fire resistance walls which could be applied to curtain walls. According to the tests, the specimens satisfied the required fire resistance performance. The finite element analysis was conducted after the tests to evaluate the fire resistance performance of the glass walls. The analysis results showed that the preliminary evaluation of fire resistance performance would be feasible.