• Title/Summary/Keyword: Fire characteristic database

Search Result 8, Processing Time 0.03 seconds

An Experimental Study on the Warehouse Mock-up Fire Test (창고 모델 실물화재 특성에 대한 실험적 연구)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl
    • Fire Science and Engineering
    • /
    • v.24 no.4
    • /
    • pp.47-54
    • /
    • 2010
  • This study is analyze the damage of warehouse fire accident be made through the fire characteristic database of combustibles and real scale fire test of warehouse mock-up. Combustibles fire tests are carried out for database using RCT (Room Corner Tester) to predict fire growth the goods. A mockup ($3m{\times}3m{\times}2.4m$) of clothes warehouse was built and real scale fire test by LSC (Large Scale Calorimeter) base on the fire characteristic DB. The mock-up of clothes warehouse is made of two type sandwich panels (Glass wool, EPS foam sandwich panel). As a mock-up test result, test 1 (Glass wool sandwich panel) and test 2 (EPS foam sandwich panel) indicating fire growth such as 5 MW, 11 MW of maximum HRR (Heat Release Rate).

Reliance Analysis for Mechanical Characteristics of ACSR Transmission Line due to a Flame (화염에 의한 ACSR 송전선의 기계적 특성에 관한 신뢰성 분석)

  • 김영달
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.138-146
    • /
    • 2003
  • This paper deals with the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include tension load, extension rate and torsion number for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR 480$\textrm{mm}^2$ which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

A Study on Surface Characteristics of ACSR Transmission Line due to a Flame (화염에 의한 ACSR 송전선의 표면 특성에 관한 연구)

  • 김영달
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.173-180
    • /
    • 2003
  • This paper deals with the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include surface characteristics for a conductor. In addition, there's been an experiment and analysis about the surface characteristics of the wire of ACSR 480$\textrm{mm}^2$ which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

Mechanical characteristic of ACSR Transmission lines by forest fires (산불에 열화된 ACSR 전선의 기계적 특성 검토)

  • Kang, J.W.;Jang, T.I.;Hong, D.S.;Park, C.G.;Bang, H.K.;Kim, Y.D.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.506-508
    • /
    • 2003
  • In the case of a fire in the mountains, steel wires coated with zinc and aluminum wires of those power cables exposed to the fire or near around will be deteriorated by the blaze and the high temperature. This paper shows the experimental results that apply to a new wire by an artificial flame-maker and results including the intensity of extension and wrench for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR $480mm^2$ which was removed from A T/L by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

  • PDF

Reliance analysis for Mechanical characteristics of ACSR Transmission Line due to a Flame (화염에 의한 ACSR 송전선의 기계적 특성에 관한 신뢰성 분석)

  • Kim, Young-Dal;Shim, Jae-Myung;Kim, Jong-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.71-76
    • /
    • 2004
  • This paper deals with the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include tension load, extension rate and torsion number for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR $48mm^2$ which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

  • PDF

A study on Mechanical and Material Characteristics of Overhead Transmission Lines due to an Artificial Flame (인공 화염으로 인한 가공 송전선의 기계적, 재료적 특성에 관한 연구)

  • Lee, Dae-Dong;Hyun, Dong-Seok;Shim, Jae-Myung;Kim, Young-Dal
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.407_408
    • /
    • 2009
  • Generally, the deterioration characteristics of a conductor affected by a forest fire can be analyzed through simulation of a forest fire and results of the simulation. However, there are little accomplishments of that kind of simulation applied to the power transmission, and there aren't actual analysis for a sample exposed in a forest fire. This paper deals with the experimental results that apply to a new wire by an artificial flame equipment because it's difficult to directly analyze the characteristic by a forest fire. Also, after an artificial flame is applied to a normal ACSR for various experimental conditions, changes of mechanical and material characteristics of the ACSR were analyzed by the surface inspection and load-tests of tensile of the ACSR. Then, the database will be made to made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

  • PDF

A Study on Mapping Forest Fire Risk Using Combustion Characteristic of Forest Fuels : Focusing on Samcheok in Gangwon-do (산불연료의 연소특성을 활용한 산불위험지도 작성에 관한 연구 : 강원도 삼척 시를 중심으로)

  • Lee, Haepyeong;Park, Youngju
    • Journal of the Society of Disaster Information
    • /
    • v.13 no.3
    • /
    • pp.296-304
    • /
    • 2017
  • In order to predict about forest fire behavior we constructed a database for combustion characteristic of forest fuels in Samcheok, Gangwon-do and prepared fire risk map and fire risk rating using GIS method in this study. For the mapping autoignition temperature, ignition time, flame duration time, total heat release and total smoke release are selected as the standardized parameters and the overall risk rating was made up of the ignition risk parameters(autoignition temperature, ignition time) and the spread risk parameters(flame duration time, total heat release, total smoke release). Forest fire risk was classified into 5 grades and lower grade of fire risk rating mean to correspond to more dangerous forest fire. As a result, the overall risk rating of Samcheok was classified into three grades from 1 to 3 and Nogok-myeon and Miro-myeon were turned out the most dangerous areas for forest fire. Because of the colony of pine and oak trees and the higher fire loads, the flame propagation will be carried out quickly in these areas.

Mechanical Deterioration Characteristics of ACSR due to a Flame (화염으로 인한 ACSR의 기계적 열화 특성)

  • 박창기;이광식;강지원;김영달
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.160-168
    • /
    • 2003
  • In Korea, a large portion of aerial power-transmission cables is installed in the mountains. In the case of a fire in the mountains, steel wires coated with zinc and aluminum wires of those power cables exposed to the fire or near around will be deteriorated by the blaze and the high temperature. Deterioration proceeds by interactions of a variety of factors like quality, manufacturing process, the condition of installation and exposure environment of a wire, and so on. Generally, the characteristic of a conductor affect by a forest fire can not be analyzed without the effect through simulating a forest fire. However, there are little research accomplishments of that kind of simulation about it, and there's been no analysis of a sample exposed to an actual forest fire. This thesis shows the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include the intensity of extension and wrench for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR 480[$\textrm{mm}^2$] which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.