• Title/Summary/Keyword: Fire Sprinkler System

Search Result 116, Processing Time 0.024 seconds

An Experimental Study on Piping Feasibility of PE Compound Pipe for Fire Protection Service (PE 이종강관의 소방용 배관 적용성에 관한 실험적 연구)

  • Park, Jeong-Hwa;Oh, Cheon-Young;Kwark, Ji-Heon;Son, Bong-Sei
    • Fire Science and Engineering
    • /
    • v.30 no.3
    • /
    • pp.55-61
    • /
    • 2016
  • In this study, to determine whether it is possible to apply Polyethylene (PE) compound pipe, which was developed to solve the problem caused by the corrosion of the fire protection piping currently in usein water based fire extinguishing systems, we performed an actual mockup fire test. Since no test standard was available related to the developed compound pipe, we compared and analyzed domestic and international technical materials and test standards and selected suitable fire test standards to evaluate the performance of the PE compound pipe. we applied two fire test standards to the PE compound pipe, viz. those for CPVC and metallic pipes, and conducted a total of 6 experiments to evaluate its performance. According to the results of the first and second fire tests based on the test standard for the CPVC pipe, neither the fitting nor the piping was damaged or deformed and no leakage was observed in the pressure test, which was performed for 5 minutes. For the fire test based on the metallic pipe test standard, a total of 4 experiments were conducted. The first two experiments were conducted to simulate the wet piping system. In the results of this fire test, neither leakage nor rupture was observed from the PE compound pipe and no damage was caused, such as the secession of the PE material. However, in the next two experiments, which simulated the dry system, the PE compound pipe suffered damage and rupture, including deformation before the fire fighting water was discharged. Therefore, we found that the piping performance of the PE compound pipe did not undergo any deterioration, including fusion, deformation, or damage, in the wet piping system simulated fire test.

Development of Vacuum Sprinkler Extinguishing System (부압식 스프링클러설비)

  • Oh, Ju-Hwan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.11a
    • /
    • pp.61-66
    • /
    • 2011
  • 부압식 스프링클러 설비는 우리나라에서 일반적으로 사용되고 있는 준비작동식이나 건식 또는 습식 스프링클러 설비의 2차측 배관내의 압력을 부압(진공)상태로 유지시켜 오작동(스프링클러 헤드의 파손 또는 배관의 누수) 시에 발생되는 소화수의 누수를 진공압(-0.05~-0.08MPa)으로 흡입하는 구조로 설계되어 수손피해에 대한 위험도를 제거 하여 기존의 스프링클러 시스템의 문제점을 해결 할 수 있는 획기적인 기술로 볼 수 있다. 또한 부압식 스프링클러 설비는 습식, 준비작동식에 해당하는 시설에 모두 적용이 가능하며 매년 국내, 외에서 건설되는 모든 대상물에도 설치가 가능하며 기존 설비된 건물에도 손쉽게 적용이 가능하여 앞으로 IT관련 산업, 반도체 제조공장, 호텔, 학교, 병원, 관공서, 지하철 역사, 정밀가공 제조설비 등 특히 내진설계에 적용되고 있는바 그 적용성이 무궁무진한바 본 부압식 스프링클러 시스템의 연구를 통한 확대에 대한 가능성은 무한할 것으로 예상된다.

  • PDF

A Smart Fire Detector System for Fire Prevention (화재 예방을 위한 스마트 화재 감지기 시스템)

  • Park, Cha-Hun;Kang, Yun-ho;Jang, Min-sung;Seo, Hee-jun;Kim, Yun-min
    • Proceedings of the Korean Society of Computer Information Conference
    • /
    • 2022.01a
    • /
    • pp.293-294
    • /
    • 2022
  • 본 프로젝트에서는 화재 발생 시 발견하기 어려운 곳이나 화재가 빈번한 곳에 구축하는 것을 목적으로 하고 있다. 가스와 불꽃을 감지하는 센서로 화재를 감지하고, 디스플레이와 LED 그리고 소리를 통해 화재발생을 알려준다. 그 후, 스프링클러가 작동하여 초기화재에 대응에 도움을 주고 119에 자동으로 신고가 된다. 일정 수치의 센서에 대한 감지 값을 인식하고 인식한 감지 값에 반응하여 화재 대처를 가능하게 구현하는 시스템을 제안한다. 감지센서를 통한 화재장소에서의 불꽃과 가스를 감지하게 되어 스프링클러가 1차적으로 화재의 번짐을 지연해 주고 은근 소방서에 자동적으로 신고를 하게 되는 자동화 프로그램 이행을 목표로 하고 있다.

  • PDF

Experimental Performance Evaluation of a Fire System for Apartment Buildings (공동주택 전용화재시스템의 성능평가를 위한 실험적 연구)

  • Jung, Jong-Jin;Hong, A-Reum;Son, Bong-Sei
    • Fire Science and Engineering
    • /
    • v.29 no.6
    • /
    • pp.51-56
    • /
    • 2015
  • In Korea, measures to maintain sustainable fire safety performance for apartment buildings are insufficient in terms of fire-fighting products, skilled personnel, and maintenance status. Also, because of the particular features of a fire compartment, it has structural problems that are very likely to cause damage to human life when a fire occurs. Currently, problems with the fire supervisory system installed in an apartment building cannot be checked in real time, so it is difficult to identify the location of a fire accurately. Protected areas are also not assigned to each household, and residents cannot be clearly informed of the occurrence of a fire. As a consequence, safety evacuation cannot be secured. In addition, it is impossible to test the operation performance for water detectors in sprinkler fire extinguishing systems outside of the household. Therefore, an experiment was conducted to evaluate the performance of a remote fire supervisory system. The results show that the system satisfies all performance requirements. Also, an household alarm system was installed in each household to alert of any occurrence of a fire accurately, and the performance of the alarm system was improved to ensure that residents were quickly evacuated.

The Study of Simulation for Reproduce Accidents of Narrow Dwelling Space (협소 거주공간 사고 재현을 위한 시뮬레이션 연구)

  • Lee, Changwoo;Choi, Beakyoul;Kim, Jinsung;Cho, Yongsun;Yoo, Juyoul
    • Journal of the Society of Disaster Information
    • /
    • v.12 no.3
    • /
    • pp.210-218
    • /
    • 2016
  • In this study, the fire analysis program FDS and Pathfinder was used to analysis a simulated accidental fire of a narrow dwelling space as a test bed. The results showed that the evacuation time of the H form internal building structure was the fastest at 285 seconds. In addition, when the automatic sprinkler system functioned with the entrances closed, the temperature distribution was lower and the visible smoke density was reduced.

A Study on the Fire Spread between Office Room and Atrium in the Atrium Building (아트륨 빌딩에서의 사무실과 아트륨간의 화재확산에 관한 연구)

  • Lee, Su-Kyung;Kim, Jong-Hoon
    • Journal of the Korean Society of Safety
    • /
    • v.15 no.2
    • /
    • pp.78-83
    • /
    • 2000
  • Generally, There is to install fire resist shutter or to compart between the office room and the atrium in the atrium buildings in Korea. But, Glass wall that is installed sprinkler which purpose to protect it from fire, is already installed between the office room and the atrium in the advanced nations. We study this problem as follow; We made the fire scenario, and analyze each scenario using FASTLite is fire modeling software and BREAK1 is to predict the window breakage time in the compartment fire. In this study, we can decide that fire compartmentalization between atrium and office rooms doesn't require in Atrium building if the material and fire protection system were reliable. Consequently, Korean Fire Protection Regulations have to consider in direction of increasing freedom of building.

  • PDF

Suggestion of the Attached Piping Material Rate for the Mechanical Fire Protection Facilities in Office Buildings (업무용 건축물의 기계소방시설 배관 부속자재 요율 제시)

  • Park, Lyool;Park, Kyung-Soon;Yoon, Hang-Mook
    • Journal of the Regional Association of Architectural Institute of Korea
    • /
    • v.20 no.6
    • /
    • pp.1-8
    • /
    • 2018
  • In generally, the estimation work regarding building mechanical service system in comparison with other architectural estimations is time-consuming, and the process is continuously getting more difficult because of the increased usage of the attached piping materials such as fittings and supports in addition to their complicated construction processes. In order to improve this problem, the Korean authority provides a simple method to estimate the attached material rate regarding the main piping material, which is the most time-consuming work in the architectural mechanical estimation. However, to be an applicable method on construction site, a proper conversion rate of the attached piping material is still required for the proposed method regarding building usage and working types. Therefore, the purpose of this research is the suggestion of the material and labor cost rate of the attached piping materials such as the fittings and supports by work types and fitting methods of indoor fire, sprinkler, and extinguishing gas piping work of mechanical fire protection facilities in office buildings that have been designed after 2010.

Implementation of Smart Fire Safety System (스마트 화재 안전 시스템의 구현)

  • Duk-Kyu Choi;Yun-Ho Kang;Min-Sung Jang;Ju-An Son;Hee-Jun Seo;Hyeon-Gyu Lee;Jin-Ho Kim
    • Proceedings of the Korean Society of Computer Information Conference
    • /
    • 2023.01a
    • /
    • pp.279-280
    • /
    • 2023
  • 소방청 국정감사에서 2020년 전국 자동화재속보설비 화재신고 32,764건 가운데 32,685건이 오작동으로 출동해 소방서 출동의 99.8%가 헛걸음이었다. 그리고 화재가 발생할 경우 화재경보장치와 대피경로를 안내하는 비상등이 미흡하고, 화재 연기가 제거되지 않아 대피가 힘들어질 뿐만 아니라 미처 대피 못한 인원을 파악하는 등의 신속한 대처가 힘들다. 본 논문은 화재 상황에서 피해를 최소화하기 위한 '스마트 화재 안전 시스템' 기술을 제안한다. 화재가 발생할 경우, 대피 경로를 안내하는 유도등 작동 및 경보음과 LED의 작동으로 화재발생을 경고하여 신속한 대처를 할 수 있게 도와주고, 문과 창문의 자동 개방 및 환기팬 작동으로 인한 유해가스를 환기시켜 준다. 그리고 스프링클러 작동과 소화제를 자동 분사하여 화재의 번짐 등 2차 피해를 예방하여 준다. 또한, 자동 신고 기능으로 더욱 빠르게 화재를 진압할 수 있게 도와주기 때문에 피해를 최소화할 것이다.

  • PDF

Design of Simulation Environment for Intelligent Disaster Prevention System and Implementation of Management Application (지능형 방재 시스템 시뮬레이션 환경 및 관리 어플리케이션 구현)

  • Cho, Young-Ho;Kang, Heau-Jo;Sung, Kyung
    • Journal of Advanced Navigation Technology
    • /
    • v.15 no.4
    • /
    • pp.602-608
    • /
    • 2011
  • In this paper, we implemented an android mobile management application of intelligent prevention of disaster system which can manage the current status monitoring and whether operating or not by using Ubiquitous Sensor Network based self wireless communication system of scattered emergency light, fire extinguishers and sprinkler inside the high complex building. This system is composed with fire facilities attached sensor nodes, management server for collection of information and control, and smart phone application that transmits and receives information with management server. As a result of the test, the embodied android-based smart phone application to be performed anywhere could confirm status and monitoring information of fire facilities which are communicated with the management server.

A study on prediction and improvement method of fire risk for a newly built college dormitory (신축 승선생활관의 화재 위험성 예측 및 개선방안에 관한 연구)

  • Kim, Byeol;Hwang, Kwang-Il
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.40 no.3
    • /
    • pp.228-234
    • /
    • 2016
  • As a college dormitory has the features of high dwelling density and a floating population that becomes crowded during particular times, when a disaster such as a fire occurs, it has the risk of causing much loss of life. In this study, the fire simulation program Fire Dynamics Simulator (FDS), is used to predict the risk when a fire occurs, to analyze the problem, and to suggest an improvement plan for a new cadet dormitory at an university in Korea. The research results are as follows. When a fire occurred in the ironing room inside the cadet dormitory, a smoke detector operated after 65 seconds. Thirteen seconds later, a sprinkler started to operate. The temperature and carbon monoxide density reached the limit value at 241 and 248 seconds, respectively. Because the limit visibility value was reached within 66 seconds after the occurrence of a fire, it is predicted that preparation must be finished and evacuation should begin within 1 minute after the fire occurs, in order to have no casualties. Synthesizing this dormitory fire risk prediction result, the visibility value is considered to be the most dangerous factor for personal safety. Because of this, installing a smoke extraction system is suggested to secure visibility. After the installation of a smoke extraction system, the problem of smoke diffusion in the corridors improved.