• Title/Summary/Keyword: Extinguishing performance

Search Result 149, Processing Time 0.026 seconds

Seismic Response Estimation of Water Extinguishing Facilities using Shaking Table Tests (진동대 실험을 통한 수계 소화설비의 지진응답평가에 관한 연구)

  • Nam, Min-Jun;Park, Seung-Hee;Kim, Dong-Joon;Choi, Jun-Sung
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.16 no.4
    • /
    • pp.9-18
    • /
    • 2012
  • In this study, a shaking table test was performed for the evaluation of water extinguishing facilities. Water extinguishing facilities, such as a general pipe, a seismic pipe (Loof type) and a pump, were used in the experiment. This captured the dynamic characteristics of water extinguishing systems by earthquake records at El-Centro with a 50%, 70%, 100%, 120% level. As a result, seismic type facilities have excellent seismic performance compared to general facilities. By using the acceleration response spectrum, not only is the performance evaluation of water extinguishing facilities able to be determined, but also the deformation of facilities in low earthquake levels can be known. This proposed approach can determine the seismic performance evaluation of water extinguishing facilities and verify seismic performance criteria.

A Study on the Measurement of Flame Extinguishing Concentration of Halon Alternatives by New Test Equipment (할론대체물질의 새로운 불꽃소화농도 측정장치에 관한 연구)

  • 김재덕;임종성;이윤우;이윤용
    • Fire Science and Engineering
    • /
    • v.8 no.1
    • /
    • pp.3-8
    • /
    • 1994
  • A new test system was established to measure the flame extinguishing concentration of Halon alternatives. The main characteristic of this system is to use the solid paraffin with a wick instead of liquid fuel, such as n-Heptane. Our results showed that the extinguishing concentration of compounds was lower than that of other existing data, but the trend was consistent with others. The flame extinguishing concentration of all tested compounds were not almost effected by gas flow velocity. The system produces good reliable data with a minimum error for measuring the flame extinguishing concentration. Therefore our new system can be utilized as a standard equipment to evaluate Halon alternatives.

  • PDF

Flame Extinguishing Concentrations of Mixed Gaseous Agents (가스계 혼합소화약제의 불꽃소화농도)

  • 김재덕;임종성;이윤우;이윤용
    • Fire Science and Engineering
    • /
    • v.15 no.1
    • /
    • pp.34-40
    • /
    • 2001
  • Fire extinguishing efficiency of mixed gaseous agents were investigated by the cup-burner test and predicting by the model of flame extinguishing concentration. The binary mixed agents that tested were carbon dioxide/HFC-23, carbon dioxide/HCFC-22, carbon dioxide/HFC-227ea, carbon dioxide/HFC-125, carbon dioxide/FIC-13I1, Hexafluoropropylene/HFC-23 and ternary mixed agents were carbon dioxide/HFC-23/HFC-l34a, carbon dioxide/HFC-23/HFC-227ea, carbon dioxide/HFC-23/HFC-125. A model which contains the flame extinguishing concentration and composition of pure components predicted the flame extinguishing concentration of mixture well. This model was superior when each component of the mixture exhibit physical fire extinguishing performance.

  • PDF

A Study on the Extinction Concentration of Inert Gas for Extinction Performance Estimation of Kerosene (등유의 소화성능 평가를 위한 불활성 가스의 소화농도에 관한 연구)

  • Choi, Jae-Wook
    • Journal of the Korean Society of Safety
    • /
    • v.22 no.3 s.81
    • /
    • pp.34-38
    • /
    • 2007
  • The experiment was done to investigate extinguishing concentrations of different inert gases of verying concentrations made in contact with Kerosene. The experimental results obtained are as follows; at a standard amount of air flow was 40L/min, the extinguishing concentration of Argon, Nitrogen, Carbon dioxide and Helium for Kerosene were 36.5%, 27.3%, 17.4%, 12.3%, respectively. And, according to these results, Helium of 12.3% showed the lowest extinguishing concentration.

Experimental Study on the Fire Extinguishing Characteristics of Water Mist System (미분무수 소화설비의 소화특성 실험)

  • Hwang, Won-Jun;Kim, Hwang-Jin;Oh, Kyu-Hyung;Lee, Sung-Eun
    • Fire Science and Engineering
    • /
    • v.23 no.2
    • /
    • pp.78-84
    • /
    • 2009
  • We carried out fire extinguishing experiments with three kinds of water mist nozzle system. Fire extinguishing experiment according to installed nozzle height and fuel pan location was done. And fire extinguishing performance was compared with plain water and foam agent mixed solution. Water mist nozzle height was varied with 4m, 3.5m and 3m and position of fuel fan was varied 0.5m and 1m from the center of water mist nozzle. Foam agent that used in this experiment is 3% type of AFFF (Aqueous Film Forming Foam) solution. Experimental result showed the door opening effect was little. Fire extinguishing performance of foam agent mixture water mist was better than the plain water mist only.

A Study on the Development of Fire Extinguishing Agent and Extinguishing System for ESS Fire (ESS 화재전용 소화약제 및 소화시스템 개발에 관한 연구)

  • Lee, Yeon-Ho;Lee, Joo-Hyung;Kim, Soo-Jin;Chon, Sung-Ho;Choi, Byoung-Chul;Oh, Seung-Ju;Kim, Si-Kuk
    • Fire Science and Engineering
    • /
    • v.34 no.2
    • /
    • pp.147-155
    • /
    • 2020
  • This paper presents a study on the development of a fire extinguishing agent and extinguishing system for an energy storage system (ESS) fire. The fire extinguishing agent designed to extinguish an ESS fire is a highly permeable fire extinguisher that reduces the surface tension and viscosity while bringing about cooling action. This is the main extinguishing effect of this type of wetting agent, which displays the characteristics of fire extinguishing agents used for penetrating the battery cells inside the ESS module. For the fire extinguishing system, a local application system was designed to suppress fire on a rack-by-rack basis. A 360° rotating nozzle was inserted into the rear hall of the ESS module, and general nozzles were installed in the rack to maximize the fire extinguishing effect. The fire extinguishing agent was strongly discharged by virtue of the gas release pressure. Experiments on fire suppression performance with ESS module 1 unit and module 3 units showed that all visible flames were extinguished in 8 s and 9 s, respectively, by the fire extinguishing agent. In addition, based on confirming reignition for 600 s after the fire extinguishing agent was exhausted, it was confirmed that the ESS fire was completely extinguished without reignition in all fire suppression performance experiments.

He Study of Fire Suppression Capability of Low Pressure Water-Mist System for Wooden Cultural Properties (목조한옥에 대한 저압식 미분무 소화설비의 소화성능에 관한 연구)

  • Roh, Sam-Kew;Kim, Dong-Cheol;Ham Eun-Gu
    • Journal of the Society of Disaster Information
    • /
    • v.8 no.4
    • /
    • pp.401-410
    • /
    • 2012
  • The study verified the extinguishing performance of the low pressure water-mist system, which is used to extinguish fire at domestic wooden architecture, through a fire test. Made of inflammable materials, a wooden house is vulnerable to fire, and the size of fire may vary from the early stage in case of arson. With the discharging pressure of 8 bar and the flow rate of 35 lpm, the low pressure water-mist nozzle used in the experiment has considerable discharging amount compared to other water-mist nozzles. The extinguishing performance was tested based on the size of fire and architecture. Test results demonstrated that the extinguishing performance was not affected by the size of a house, but decreased significantly when the size of fire was above unit 1. Taking into account that the environment of actual wooden cultural properties is more vulnerable than that of the experiment model, sufficient investigation on extinguishing performance is required to apply the water-mist extinguishing system to wooden architecture.

Flame Extinguishing Concentrations and Flue Gas Compositions of n-Heptane by Mixed Inert Gas Agents (불활성 가스계 혼합소화약제의 n-Heptane 불꽃소화농도 및 배가스 조성)

  • 김재덕;김영래;홍승태;이성철
    • Fire Science and Engineering
    • /
    • v.16 no.3
    • /
    • pp.77-83
    • /
    • 2002
  • We measured flame extinguishing concentration and flue gas composition in the n-heptane fuel cup-burner system using inert gas agents such as nitrogen, argon, carbon dioxide and their mixtures. The flame extinguishing concentration of binary gaseous mixture was well predicted by model which contains the flame extinguishing concentration and composition of pure components. The higher average specific gravity of the mixed inert gas agents, the more excellent flame extinguishing performance. And the structure of enclosed space also affects the fire extinguishing. The composition of carbon dioxide in the flue gas was decreased with increasing extinguishing agent used. Nitrogen monoxide production is not related with increasing nitrogen, but increased at rapid mass flow rate of air in the cup-burner.

Application of a Turbojet Engine for Fire Extinguishing

  • Slitenko, A.F.;Kim, SooYong
    • International Journal of Aeronautical and Space Sciences
    • /
    • v.1 no.1
    • /
    • pp.62-69
    • /
    • 2000
  • Present study deals with performance analysis of an inert gas generator (IGG) which can be used as effective means to suppress fire. The IGG uses a turbo-jet engine to generate inert gas for fire extinguishing. It is generally known that a less degree of oxygen content in the product of combustion will increase the effectiveness of fire extinguishing. An inert gas generator system with water injection has advantages of suffocating and cooling effects that are very important factors for fire extinguishing. Some aspects of influencing parameters, such as, air excess coefficient, compressor pressure ratio, air temperature before combustion chamber, gas temperature after combustion chamber, mass flow rate of water injection etc. on the performance of IGG system are investigated.

  • PDF

Performance Evaluation on Water-mist Extinguishing System of Railway Vehicles (철도차량 미분무수 소화설비 성능 평가)

  • Park, Won-Hee;Eum, Pu-Reun-Byul;Yoon, Kyung-Beom;Lee, Duck-Hee
    • The KSFM Journal of Fluid Machinery
    • /
    • v.17 no.1
    • /
    • pp.22-27
    • /
    • 2014
  • The test system for the performance of the water-mist extinguishing system in the railway vehicle is equipped and the details of the system are introduced. The three scenarios using different fire sources and performance criteria for the water-mist systems on railway vehicles are also introduced. Three different type of the nozzle at same operating pressure are evaluated. Amount of water-mist distribution is measured by many baskets on the bottom of the test room. Temperature on the ceil and the tree of the test room is measured during the tests that are used for the judgement of the performance on the water-mist extinguishing system.