The experiment was done to investigate extinguishing concentrations of different inert gases of verying concentrations made in contact with Kerosene. The experimental results obtained are as follows; at a standard amount of air flow was 40L/min, the extinguishing concentration of Argon, Nitrogen, Carbon dioxide and Helium for Kerosene were 36.5%, 27.3%, 17.4%, 12.3%, respectively. And, according to these results, Helium of 12.3% showed the lowest extinguishing concentration.

Keywords

References

  1. 김성찬, 유홍선, 박현태, 방기영, '물분무 노즐의 분사각이 화재실 내부의 온도장에 미치는 영향', 산업안전학회지, 제18권, 제2호, pp. 28-33, 2003
  2. 오율권, 서동표, 'Air-water 모델에서 기포특성에 관한 연구', 산업안전학회지, 제18권, 제1호, pp. 14-18, 2003
  3. 박외철, 유재환, 이수경, 이춘하, 전주함, 김영수, '최신소방설비', 東和技術, p. 33, 1999
  4. 청정소화약제소화설비의 화재안전기준(NFSC), 제 3조, 행정자치부고시제2004-15호
  5. A. Thomas, 'Voluntary Code of Practice for HFC and PFC Fire Protectio Agents', Halon Alternatives Research Corporation, 12th, pp. 1-7, 2002
  6. Y. Zou, N. Vahdat and M. Collins, 'Fire Extinguishing Ability of 1-bromo-1-propane and 1-methoxyonafluorobutane Evaluated by Cup Burner Method', Journal of Fluorine Chemistry, Vol. 111, Issue. 1, pp. 33-44, 2001 https://doi.org/10.1016/S0022-1139(01)00439-0
  7. 한용식, 김명배, 김수용, '불활성 가스 발생장치 (Inert Gas Generator)의 소화시스템 적용에 관한 연구', 한국화재소방학회 논문지, Vol. 19, No. 2, pp. 69-74, 2005
  8. FIS 002, '가스계 소화설비의 성능기준에 관한 인정기준', 한국소방검정공사, 2000
  9. NFPA 2001, 'Standard on Clean Agent Fire Extinguishing System', 1996
  10. I. Yamamoto, K. Sato and S. Yamashika, 'Flame Extinguishing concentration by Cup Burner Method', Rep. Fire Res. Institute. Japan, Vol. 57, pp. 41-48, 1984
  11. ISO/FDIS 14520 Final Draft, 'Gaseous Fire Extinguishing Systems- Physical Properties and System Design', 2000