• Title/Summary/Keyword: Electrical shocl

Search Result 1, Processing Time 0.013 seconds

Improvement of Lighting Installation Technical Standard in Waterpark, Public Bath and Similar Places for the Prevention of Electric Shock (감전사고 방지를 위한 물놀이.입욕시설의 조명설비 시설기준 개선방안 연구)

  • Kim, Chong-Min;Kim, Han-Sang;Kim, Gi-Hyun;Yi, Geon-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.4
    • /
    • pp.78-85
    • /
    • 2006
  • A person's body resistance in the waterpark, public bath and similar places is much lower than any other places due to effect of water. So low voltage may create a shock hazard for the human body in case of leakage or fault currents from lighting unit etc. We researched the related regulations which are internal standards, NEC, IEC and investigated the actual conditions for the prevention of electric shock due to lighting units in the waterpark, public bath and similar places. As a results internal standard is obscure as compared with NEC, IEC which is the limit of application and distinction of environment condition. And then internal standard's using voltage is higher than NEC, IEC in filed of water. Studies show that internal standard should be revision that raise the installation height of lighting unit, mark IP level surface of lighting unit and limit using voltage to line-to-line voltage