• 제목/요약/키워드: Electrical safety system

검색결과 1,366건 처리시간 0.032초

자동 고장 판별 및 거리 측정 기능을 갖는 휴대용 케이블 고장 검출 장치 개발 (Development of Portable Cable Fault Detection System with Automatic Fault Distinction and Distance Measurement)

  • 김재진;전정채
    • 전기학회논문지
    • /
    • 제65권10호
    • /
    • pp.1774-1779
    • /
    • 2016
  • This paper proposes a portable cable fault detection system with automatic fault distinction and distance measurement using time-frequency correlation and reference signal elimination method and automatic fault classification algorithm in order to have more accurate fault determination and location detection than conventional time domain refelectometry (TDR) system despite increased signal attenuation due to the long distance to cable fault location. The performance of the developed system method was validated via an experiment in the test field constructed for the standardized performance test of power cable fault location equipments. The performance evaluation showed that accuracy of the developed system is less than 1.34%. Also, an error of automatic fault type and location by detection of phase and peak value through elimination of the reference signal and normalization of correlation coefficient and automatic fault classification algorithm not occurred.

원자력발전소 직류 전력계통의 충전기 신뢰도 향상방안 연구 (A Study on Battery Charger Reliability Improvement of Nuclear Power Plants DC Distribution System)

  • 임혁순;김두현
    • 한국안전학회지
    • /
    • 제25권2호
    • /
    • pp.24-28
    • /
    • 2010
  • The nuclear power Plant onsite AC electrical power sources are required to supply power to the engineering safety facility buses if the offsite power source is lost. Typically, Diesel Generators are used as the onsite power source. The 125 VAC buses are part of the onsite Class 1E AC and DC electrical power distribution system. The DC power distribution system ensure the availability of DC electrical power for system required to shutdown the reactor and maintain it in a safety condition after an anticipated operational occurrence or a postulated Design Base Accident. Recently, onsite DC power supply system trip occurs the loss of system function. To obtain the performance such as reliability and availability, we analyzed the cause of battery charger trip and described the improvement of DC power supply system reliability. Finally, we provide reliability performance criteria of charger in order to ensure the probabilistic goals for the safety of the nuclear power plants.

접지시스템의 접촉전압 및 보폭전압 측정오차 감소 기법에 관한 연구 (Study on Measurement Error Reduction Technique when Measuring Touch and Step Voltage of Grounding System)

  • 김동우;임용배;이상익;최명일;문현욱
    • 전기학회논문지
    • /
    • 제64권1호
    • /
    • pp.188-195
    • /
    • 2015
  • This paper presents measurement error reduction technique of touch and step voltage of grounding system based on numerical analysis. When measuring touch and step voltage of grounding system, auxiliary current probes should be located at suitable places. However, the auxiliary probes can not be located at suitable places in such cases as there are buildings and pavements. Therefore, in this paper, we provided measurement error reduction technique of touch and step voltage of grounding system according to the positions of auxiliary probes and angle between auxiliary probes. Also, measurement error analyses of touch and step voltage of grounding system have been conducted using more than one current probe. Based on these analyses, recommended positions of auxiliary probes within allowable measurement errors were presented.

태양광 발전설비 검사기법 및 부적합설비 개선사례 분석 (Solar Power Plant Inspection Techniques and Practices to Improve Inadequate Facilities)

  • 박병하;고석일;안선주;최준호
    • 한국태양에너지학회:학술대회논문집
    • /
    • 한국태양에너지학회 2012년도 춘계학술발표대회 논문집
    • /
    • pp.439-444
    • /
    • 2012
  • Photovoltaic energy is regarded as the key solution to the instability of energy supply and environmental pollution, and it is spreading from the developed countries to world wide. This paper looks into guide lines of KESCO (Korea electrical Safety Corporation) on Photovoltaic system and analyzed case of inconsistencies of pre-service inspection. Through these analyses it will be possible to prevent possible accidents in the process of installing Photovoltaic system and thus ensure electrical safety of Photovoltaic system.

  • PDF

공연장의 전기설비중 지락보호설비에 대한 현장실태분석 연구 (A Study on the Analysis of Field Condition for Ground Fault Protection Installation among Electrical Installations in the Entertainment Area)

  • 배석명;김한상;길형준;이건호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1721-1723
    • /
    • 2002
  • This paper deals with the analysis of field condition for earth leakage current alarming system in the stage lighting, stage sound stage machinery installation. These analyses of field condition were carried out in accordance with investigating an installation of earth leakage current alarming system with respect to a main line of power source, dimmer, sound equipment, machinery mobile unit equipment and so on. As a result of analyses. The earth leakage current alarming system has been installed only a part of the main line of power source and the probability of places which were installed was less than 50(%). Therefore, it is desirable that the earth leakage current alarming system is installed at places which are suitable, for example, dimmer, each kind machinery etc. in order to prevent electrical hazard.

  • PDF

Electrical Fire Cause Diagnosis System Using a Knowledge Base

  • Lee, Jong-Ho;Kim, Doo-Hyun;Kim, Sung-Chul
    • International Journal of Safety
    • /
    • 제6권2호
    • /
    • pp.27-32
    • /
    • 2007
  • For last several decades with the achievement of fast economic development, the electrical fires occupies over 30 percent of total fire incidents almost every year in Korea and not decreased in spite of much times and efforts. Electrical fire cause diagnostics are to confirm a cause for the fire by examination of fire scene. Cause diagnosis methods haven't been systematized yet, because of limits for available information, investigator's biased knowledge, etc. Therefore, in order to assist the investigators and to find out the exact causes of electrical fires, required is research for an electrical fire cause diagnosis system using DB, computer programming and some mathematical tools. The electrical fire cause diagnosis system has two functions of DB and electrical fire cause diagnosis. The cause diagnosis is conducted by a case-based reasoning on a case base and rule-based reasoning on a rule base. For the diagnosis with high reliability, a mixed reasoning approach of a case-based reasoning and fuzzy rule-based reasoning has been adopted. The electrical fire cause diagnosis system proposes the electrical fire causes inferred from the diagnosis processes, and possibility of the causes as well.

Mash-up 분석기술 기반의 아크 고장 검출 알고리즘에 관한 연구 (A Study on Arc Fault Detection Algorithm Based on Mash-up Analysis Technique)

  • 이기연;문현욱;김동우;임용배;최종수
    • 전기학회논문지
    • /
    • 제66권6호
    • /
    • pp.995-1000
    • /
    • 2017
  • In this paper, we present an electrical arc detection algorithm using the mash-up analysis technique which is the core technology for the autonomous electrical safety management system(AESMS) of the multi-unit dwellings. The mash-up analysis technique analyzes the voltage, load current, zero phase current data simultaneously to judge arc faults. In order to develop the arc fault detection algorithm, the characteristics of series arc and parallel arc were analyzed. Also, we propose the mash-up analysis technique that analyzes waveforms of voltage, load current, and zero phase current at the same time. The arc fault detection algorithm was developed using the mash-up analysis technique. The developed algorithm can prevent electrical disasters in an effective way through accident prediction, and it will be used as a basic technology to introduce an autonomous electrical safety management system.

낙뢰 보호용 접지시스템 평가를 위한 고주파 접지임피던스 측정시스템의 설계 및 제작 (Design and Fabrication of High Frequency Ground Impedance Measuring System for Assessment of Grounding System for Lightning Protection)

  • 길형준;송길목;김영석;김종민;김영진
    • 한국안전학회지
    • /
    • 제31권3호
    • /
    • pp.47-52
    • /
    • 2016
  • This paper describes the design and fabrication of high frequency ground impedance measuring system for assessment of grounding system for Lightning protection. The ground impedance measuring system has been designed and fabricated which makes it possible to assess the ground impedance by frequency ranges from 100 Hz to 1 MHz. The effective grounding systems having a very low impedance to electromagnetic disturbance such as lightning surges and noises in microelectronics and high-technology branches are strongly required. In order to analyze the dynamic characteristic of grounding system impedances in lightning and surge protection grounding systems, it is highly desirable to assess the ground impedances as a measure of performance of grounding system in which lightning and switching surge currents with fast rise time and high frequency flow. The measuring system is based on the variable frequency power supply and consists of signal circuit part, main control part, data acquisition and processing unit, and voltage and current probe system. The ground impedance measuring system can be used to assess grounding system during occurrence of lightning.

Distribution of Potential Rise as a Function of Shape of Grounding Electrodes

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon
    • 조명전기설비학회논문지
    • /
    • 제21권4호
    • /
    • pp.73-79
    • /
    • 2007
  • In order to analyze the potential rise of grounding systems installed in buildings, a hemispherical grounding simulation system was studied. Potential rise was measured and analyzed regarding the shape and distance of the grounding electrodes by using this system. The system was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The potential rise was measured in real time by the horizontal moving probe of be potentiometer. The test grounding electrodes were fabricated through reducing the grounding electrode installed in real buildings such as the ground rod, grounding grid and so on. The potential rise was displayed in a two-dimensional profile and was analyzed regarding the shapes of the ground electrodes. The potential rise of the grounding grid combined with a ground rod was the lowest of every grounding electrode tested. The proposed results can be applicable to evaluating ground potential rise in grounding systems, and the analytical data can be used to stabilize the electrical installations and prevent electrical disasters.

원격 전기안전 교육을 위한 모바일 에이전트 시스템 설계 (Design of Mobile Agent System for Remote Electric Safety Education)

  • 조현섭;유인호;장성환;유기수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 D
    • /
    • pp.1951-1952
    • /
    • 2006
  • To effectively deal with video data, a semantic-based retrieval scheme that allows for processing diverse user queries and saving them on the database is required. In this regard, this paper proposes a semantic-based video retrieval system that allows the user to search diverse meanings of video data for electrical safetyrelated educational purposes by means of automatic annotation processing. If the user inputs a keyword to search video data for electrical safety-related educational purposes, the mobile agent of the proposed system extracts the features of the video data that are afterwards learned in a continuous manner, and detailed information on electrical safety education is saved on the database. The proposed system is designed to enhance video data retrieval efficiency for electrical safety-related educational purposes.

  • PDF